Plan Review Details - Permit 15070501
Plan Review Stops For Permit 15070501
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-08-03 Cont ID  
Sent By spalmer Date 2015-08-03 Time 12:36 Rev Time 0.00
Received By spalmer Date 2015-07-15 Time 16:20 Sent To  
Notes
2015-07-15 16:21:16ROUTED TO MECHANICAL $5000 & UNDER

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-08-03 Cont ID  
Sent By ccole Date 2015-07-29 Time 12:39 Rev Time 0.00
Received By ccole Date 2015-07-29 Time 12:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-07-23 Cont ID  
Sent By ccole Date 2015-07-23 Time 11:17 Rev Time 0.00
Received By ccole Date 2015-07-23 Time 11:17 Sent To  
Notes
2015-07-23 11:25:231ST REVIEW: FBC 2014 MECHANICAL
  
 1) PLEASE REMOVE THE AC CHANGE OUT FORM FROM THE PERMIT
 SUBMITTAL PACKAGE: THIS IS NOT A CHANGE OUT, IT IS A
 NEW INSTALLATION.
 2) PROVIDE AN AC EQUIPMENT SCHEDULE ON THE PLAN
 INDICATING THE MAKE AND MODEL NUMBERS OF THE CONDENSER
 AND THE AIR HANDLER, COOLING AND HEATING CAPACITIES,
 EFFICIENCY RATING, AND ELECTRICAL DATA.
 3) CLARIFY THE SCOPE OF THE PROJECT WITH NOTES ON THE
 PLANS. INDICATE IF THE SYSTEM IS SUPPLEMENTAL TO A MAIN
 SYSTEM AND IDENTIFY THE ROOM IT IS CONDITIONING-
 BEDROOM, DEN, ENCLOSED PORCH?
 4) PROVIDE STRUCTURAL DETAILS FOR INSTALLATION OF THE
 CONDENSER PAD, AND WIND LOAD TIE DOWN ENGINNERING FOR
 THE CONDENSER PER MANUFACTURER'S SPECIFICATIONS- REFER
 TO SECTION M1401.4 FBC-10 RESIDENTIAL.
 5) PROVIDE AN ELECTRICAL PLAN AND AN ELECTRICAL
 SUB-PERMIT.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  