Plan Review Details - Permit 15070489
Plan Review Stops For Permit 15070489
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-09-11 Cont ID  
Sent By jwitmer Date 2015-09-11 Time 15:48 Rev Time 0.00
Received By jwitmer Date 2015-09-11 Time 15:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-07-31 Cont ID  
Sent By jwitmer Date 2015-07-31 Time 08:27 Rev Time 0.00
Received By jwitmer Date 2015-07-31 Time 08:12 Sent To  
Notes
2015-07-31 08:27:04BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15070489
 ADD: 400 N. FLAGLER DR. DOCK E
 CONT: CURRENT CONNECTIONS
 TEL: (561)863-0010
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W
 * 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION,
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE:
 ACTION: DENIED
  
 1) THE PLANS DO NOT PROVIDE THE MANUFACTURERS
 SPECIFICATIONS FOR THE PEDESTALS NOR HAS THE ANCHORING
 OF THE PEDESTALS TO THE DECK BEEN PROVIDED. PLEASE
 PROVIDE ANCHORING OF PEDESTAL AND THE WIND DESIGN
 CRITERIA PROVIDED FOR THE ANCHORING.
  
  
 2014 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 1.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 1.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 1.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 1.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 1.5) COMPONENTS & CLADDING PRESSURES POSITIVE &
 NEGATIVE TABLE 1609.2(2) .
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-09-17 Cont ID  
Sent By dharvey Date 2015-09-17 Time 13:59 Rev Time 0.00
Received By dharvey Date 2015-09-17 Time 13:59 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-09-10 Cont ID  
Sent By dharvey Date 2015-09-10 Time 21:04 Rev Time 0.00
Received By dharvey Date 2015-09-10 Time 20:58 Sent To  
Notes
2015-09-10 21:07:31PREVIOUS NOTE 7 - THE ELECTRICAL DATUM PLANE AND
 DISCONNECTING REQUIREMNENTS ARE A FAIRLY NEW
 REQUIREMENT IN THE ELECTRICAL CODE AND NOT PREVIOUSLY
 ADDRESSED. PROVIDE AN ACTUAL ELEVATION FOR THE
 ELECTRICAL DATUM PLANE AND SHOW COMPLIANCE WITH THE NEC
 REQUIREMENTS.
 PREVIOUS NOTE 9 - IF THE ELECTRICAL DATUM PLANE IS NOT
 SHOWN AND ESTABLISHED, THE PLANS ARE NOT IN COMPLIANCE
 WITH THE GOVERNING ELECTRICAL REQUIREMENTS. COMPLETE
 REVIEW SHOULD REVEAL OTHER NON-COMPLIANT ITEMS.
 PREVIOUS NOTE 16 - PROVIDE INFORMATION TO THE FIELD
 INSPECTOR AT THE TIME OF THE INSPECTION SHOWING THE
 COMPATIBILITY AND LISTING INFORMATION OF THE COMPONENTS
 TO BE CONNECTED FOR SUITABILITY OF USE.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-08-21 Cont ID  
Sent By dharvey Date 2015-08-21 Time 11:25 Rev Time 0.00
Received By dharvey Date 2015-08-20 Time 14:11 Sent To  
Notes
2015-08-20 14:51:09 
 17 PEDESTALS CALLED OUT ON TABLE, ONLY 10 INDICATED ON
 PLAN, RISER INDICATES 16 SETS OF CONDUCTORS
 PROVIDE COPY OF FPL METERED LOADS FOR FILE TO JUSTIFY
 LOAD CALCULATIONS
 PLEASE EXPLAIN THE FEEDER SCHEDULE - QUANTITY OF PHASE
 CONDUCTORS, SIZE OF GROUNDED AND GROUNDING CONDUCTORS
 IF PHASE CONDUCTORS ARE INCREASED FOR VOLTAGE DROP, EGC
 MUST BE RESIZED ACCORDINGLY
 PROVIDE VOLTAGE DROP CALCULATIONS
 PLANS CALL FOR 2008 NEC, THE CURRENT EDITION IS THE
 2011 NEC
 CORRECT EDITION OF THE FLORIDA BUILDING CODE IS THE 5TH
 EDITION
 PROVIDE TOPOGRAPHIC INFORMATION FOR ELECTRICAL DATUM
 PLANE AND AND COMPLIANCE WITH 555.2 AND 555.9. OTHER
 SECTIONS AS APPLICABLE
 PROVIDE LOAD CALCULATION SHOWING CONFORMANCE WITH
 555.12
 ENSURE INSTALLATION IS IN COMPLIANCE WITH NEC ARTICLE
 555
 PROVIDE SPECIFICATIONS AND LISTING INFORMATION ON
 PEDESTALS. INVESTIGATED MANUFACTURERS SITE AND COULD
 NOT LOCATE LISTING INFO
 THE NUMBER OF PEDESTALS IN THE TABLE, SHOWN ON THE SITE
 PLAN AND IN THE ONE LINE DIAGRAM DOES NOT APPEAR TO
 MATCH. WHAT WAS USED FOR THE LOAD CALCULATION?
 HOW WAS THE KW FOR RECEPTACLES IN THE LOAD CALCULATION
 DETERMINED?
 IS NOTE 1 TO TABLE 555.12 BEING UTILIZED?
 INDICATE PROVISION OF GFP PER 555.3
 PROVIDE CALCULATIONS OR CONFORMATION OF VOLTAGE DROP
 COMPLIANCE WITH FLORIDA BUILDING CODE - ENERGY
 CONSERVATION AND NECA STANDARDS OF INSTALLATION
 PROVIDE LISTING OR INTENT FOR FIELD EVALUATION OF
 EQUPMENT THAT WILL BE FIELD MODIFIED (SUCH AS MSB #4)
 110.3
 PROVIDE ARC FLASH PROTECTION PER NEC 110

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2015-07-23 Cont ID  
Sent By cranford Date 2015-07-23 Time 10:47 Rev Time 0.00
Received By cranford Date 2015-07-23 Time 10:44 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-08-28 Cont ID  
Sent By pleduc Date 2015-08-28 Time   Rev Time 0.00
Received By pleduc Date 2015-08-28 Time 17:07 Sent To  
Notes
2015-08-28 17:09:16THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 ALL WORK SHALL COMPLY WITH NFPA 303.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-09-11 Cont ID  
Sent By jwitmer Date 2015-09-11 Time 15:48 Rev Time 0.00
Received By jwitmer Date 2015-09-01 Time 15:26 Sent To  
Notes
2015-09-01 15:26:26RESUB ROUTED TO DHARVEY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status P Date 2015-08-28 Cont ID  
Sent By dharvey Date 2015-08-28 Time 16:03 Rev Time 0.00
Received By skennedy Date 2015-07-10 Time 14:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-08-01 Cont ID  
Sent By tklarge Date 2015-08-01 Time 05:30 Rev Time 0.00
Received By tklarge Date 2015-08-01 Time 05:21 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2015-09-17 Cont ID  
Sent By eschneid Date 2015-09-17 Time 09:42 Rev Time 0.75
Received By eschneid Date 2015-09-17 Time 09:42 Sent To  
Notes
2015-09-17 09:43:19PASSED W/PROVISOS:
  
 1) A NEW UTILITY PEDESTAL MAY ONLY BE INSTALLED AFTER
 THE REMOVAL OF AN EXISTING UTILITY PEDESTAL.
  
 2) IN ACCORDANCE WITH THE STATE LEASE - NO MORE THAN
 196 DOCKING CONNECTIONS (SLIPS) MAY EXIST AT ANY ONE
 TIME.

Review Stop Z ZONING
Rev No 1 Status F Date 2015-08-10 Cont ID  
Sent By eschneid Date 2015-08-10 Time 10:04 Rev Time 0.25
Received By eschneid Date 2015-08-10 Time 10:04 Sent To  
Notes
2015-08-10 10:06:55FAILED
  
 THE RELOCATION OF DOCKS IS NOT PERMITTED. THE CC2
 ZONING DOES NOT PERMIT THE MARINA, COMMERCIAL, USE.
  
 THERE IS CURRENTLY A CODE REVISION APPLICATION TO ALLOW
 THE USE. IF THE AMENDMENT IS PASSED, ZONING WILL REVIEW
 THE PERMIT.