2015-07-13 09:56:45 | PLAN |
| REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC 2010 |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY ELECTRIC |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) SHOW COMPLIANCE WITH FBC ENERGY CONSERVATION 402.4.5 |
| RECESSED LIGHTING. |
| RECESSED LUMINAIRES INSTALLED IN THE BUILDING THERMAL |
| ENVELOPE SHALL BE SEALED TO LIMIT AIR LEAKAGE BETWEEN |
| CONDITIONED AND UNCONDITIONED SPACES. |
| |
| 2) NEC 240.24(A) & (B) PANELS SHALL BE READILY |
| ACCESSIBLE AND EACH OCCUPANT SHALL HAVE READY ACCESS. |
| SPECIFY THE LOCATIONS OF THE PANELS AND METER ON THE |
| ELECTRICAL FLOOR PLAN. |
| |
| 3) FBC-R 315.1 - PROVIDE CARBON MONOXIDE ALARMS WITHIN |
| 10 FEET OF EACH SLEEPING ROOM. |
| |
| 4) NEC 210.52(A) - (H) OUTLET SPACING, IT APPEARS SOME |
| POINTS ALONG THE WALL EXCEED 6' FROM AN OUTLET. |
| |
| 5) NEC 210.52 (C) (1) - A RECEPTACLE OUTLET SHALL BE |
| INSTALLED AT EACH COUNTERTOP SPACE 12 INCHES OR WIDER |
| SO THAT NO POINT ALONG THE WALL LINE IS MORE THAN 2 |
| FEET MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET IN |
| THAT SPACE. |
| |
| 6) NEC 210.8 (A)(6) RECEPTACLES SERVING COUNTERTOP |
| SURFACES ARE REQUIRED TO BE GFCI PROTECTED. |
| |
| 7) R314.3.1 WHEN ALTERATIONS, REPAIRS OR ADDITIONS |
| REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING |
| ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE |
| INDIVIDUAL DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE |
| ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS. A SMOKE |
| ALARM IS REQUIRED IN BOTH UPSTAIRS BEDROOMS. |
| |
| 8) NEC 210.12 (B) - OUTLETS ARE REQUIRED TO BE AFCI |
| PROTECTED. |
| |
| 9) NEC 406.11 - TAMPER-RESISTANT RECEPTACLES ARE |
| REQUIRED. |
| |
| 10) NEC 250.50 - BOND ALL GROUNDING ELECTRODES THAT ARE |
| PRESENT. |
| |
| 11) NEC 250.104(B) THE GAS PIPING IS REQUIRED TO BE |
| BONDED. |
| |
| 12) NEC 250.94 - INTERSYSTEM BONDING TERMINATION SHALL |
| BE PROVIDED. |
| |
| 13) NEC 440.11 & 440.14 SHOW THE LOCATION OF THE |
| REQUIRED A/C EQUIPMENT DISCONNECTING MEANS ON THE |
| PLANS. |
| |
| |
| |
| |
| |
2015-07-10 18:50:11 | ON RMCDOUGAL'S DESK |