Plan Review Details - Permit 15070309
Plan Review Stops For Permit 15070309
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2015-09-02 Cont ID  
Sent By shill Date 2015-09-02 Time 15:50 Rev Time 0.00
Received By shill Date 2015-09-02 Time 15:50 Sent To  
Notes
2015-09-02 15:50:53PROVISO
  
 STAIR / RAMP REQUIRED
 SUBMIT DETAIL FOR REVIEW BY BUILDING & FIRE (NO FEE)
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-10-06 Cont ID  
Sent By albarran Date 2015-10-06 Time 13:16 Rev Time 0.00
Received By albarran Date 2015-10-06 Time 11:15 Sent To I
Notes
2015-10-06 13:21:00ALL OF THE PREVIOUSLY MENTIONED ITEMS HAVE BEEN
 SATISFACTORILY ADDRESSED. A NOTE WAS ENTERED AND
 ATTACHED TO THE DRAWINGS AS A REMINDER NOT TO COVER ANY
 OF THE TRENCHING BEFORE INSPECTIONS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-09-02 Cont ID  
Sent By albarran Date 2015-09-02 Time 19:34 Rev Time 0.00
Received By albarran Date 2015-09-02 Time 17:57 Sent To Z
Notes
2015-09-02 20:06:13PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
  
 1. PROVIDE DETAIL AS TO THE CONNECTION OF EACH TRAILER.
 2. PROVIDE GROUNDING DETAIL FOR THE TRAILERS AS WELL AS
 THE SUPPORT POLES.
 3. THOUGH THE TRAILER IS A PREASSEMBLED UNIT, ALREADY
 INSPECTED AT THE MANUFACTURER, I NEED TO KNOW WHAT ARE
 THE ELECTRICAL REQUIREMENTS/LOAD DEMAND FOR EACH UNIT
 4. UPDATE THE APPLICABLE CODES: NEC 2011 & FBC 5TH
 EDITION
 5. CORRECT NOTES D-3 AS IT IS CONTRADICTORY.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-07-23 Cont ID  
Sent By wjolin Date 2015-07-23 Time 10:27 Rev Time 0.00
Received By wjolin Date 2015-07-23 Time 10:08 Sent To  
Notes
2015-07-23 10:27:284920 LORING DRIVE - CONSTRUCTION TRAILERS
 PERMIT #15070309
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVISO - SUBMIT REVISION ADDRESSING PLAN REVIEW
 COMMENTS
  
 **A #131 FIRE FINAL INSPECTION IS NEEDED BEFORE
 OCCUPANCY OF THE STRUCTURE IS PERMITTED**
  
 DRAWING A1 INDICATES A "DOUBLE-WIDE" TRAILER STRUCTURE
 WITH DIMENSIONS OF 44' X 23' (1,012 SQ.FT.); HOWEVER,
 SITE PLAN DRAWING SP1 INDICATES A STRUCTURE AREA OF
 3,278 SQ.FT. PROVIDE AN ACCURATE PLAN SHOWING THE
 CONFIGURATIONS AND LOCATIONS OF THE TRAILERS.
  
 NO PLANS SUBMITTED FOR STAIRS, HANDRAILS OR GUARDRAILS.
 HANDRAILS ARE REQUIRED ON BOTH SIDES OF THE STAIR.
 HANDRAILS SHALL BE LOCATED NOT LESS THAN 34 INCHES AND
 NOT MORE THAN 38 INCHES ABOVE THE SURFACE OF THE TREAD,
 MEASURED VERTICALLY TO THE TOP OF THE RAIL FROM THE
 LEADING EDGE OF THE TREAD. HANDRAIL ENDS SHALL BE
 RETURNED TO THE WALL OR FLOOR OR SHALL TERMINATE AT
 NEWEL POSTS. HANDRAIL CROSS SECTION SHALL HAVE A
 DIAMETER OF NOT LESS THAN 1.25 INCHES AND NOT MORE THAN
 2 INCHES. GUARDS, AT LEAST 42-INCHES TALL, SHALL BE
 PROVIDED AT THE OPEN SIDES OF MEANS OF EGRESS (STAIRS,
 MEZZANINE, ETC.) THAT EXCEED 30-INCHES ABOVE THE FLOOR.
 OPEN GUARDS SHALL PROHIBIT THE PASSAGE OF A 4-INCH
 DIAMETER SPHERE UP TO A HEIGHT OF 34-INCHES. THE
 TRIANGULAR OPENINGS FORMED BY THE RISER, TREAD AND
 BOTTOM ELEMENT OF THE GUARDRAIL SHALL PROHIBIT THE
 PASSAGE OF A 6-INCH DIAMETER SPHERE. STAIR RISERS SHALL
 BE BETWEEN 4 INCHES AND 7 INCHES IN HEIGHT. STAIRS
 SHALL BE SLIP RESISTANT AND HAVE A MINIMUM TREAD DEPTH
 OF 11 INCHES AND PREVENT THE ACCUMULATION OF WATER.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 PER SECTION 10.12.1.2 (NFPA 1), PROVIDE BUILDING
 ADDRESS VISIBLE FROM THE STREET. NUMBERS SHALL BE
 ATTACHED TO THE BUILDING AND BE AT LEAST SIX-INCHES IN
 HEIGHT WITH 1-INCH STROKE AND SHALL CONTRAST THE
 BACKGROUND.
  
 STRUCTURES WITH LIGHT FRAME FLOOR/ROOF TRUSS
 CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO
 THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS
 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED
 REFLECTIVE COLOR AND BEAR THE APPROPRIATE LETTER R/F/RF
 DESIGNATION PER FLORIDA STATUTE 633.027 AND FLORIDA
 ADMINISTRATIVE CODE 69A-60.0081.
  
 NOTE: CIVIL DRAWING 1 OF 2 INDICATES THE INSTALLATION
 OF A NEW FIRE HYDRANT AND NEW UNDERGROUND FIRE MAIN. A
 SEPARATE PLAN AND PERMIT (UG FIRELINE) IS REQUIRED FOR
 THIS WORK.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-10-06 Cont ID  
Sent By albarran Date 2015-10-06 Time 13:22 Rev Time 0.00
Received By albarran Date 2015-09-29 Time 16:05 Sent To Z
Notes
2015-10-06 13:24:0110/6/15 PASSED ALL REQUIRED TRADE REVIEWS. CONTRACTOR
 NOTIFIED VIA EMAIL. SENT TO SMALL READY BIN "W". MA

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-09-11 Cont ID  
Sent By albarran Date 2015-09-02 Time 20:19 Rev Time 0.00
Received By eschneid Date 2015-08-18 Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-09-29 Cont ID  
Sent By albarran Date 2015-09-29 Time 16:04 Rev Time 0.00
Received By cpuell Date 2015-07-08 Time 08:46 Sent To  
Notes
2015-09-02 20:12:389/2/15 - FAILED ELECTRICAL REVIEW. PLANS WERE
 INADVERTENTLY STAMPED. CONTRACTOR NOTIFIED VIA EMAIL.
 ROUTED TO ZONING BOX FOR REVIEW. MA

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2015-09-02 Cont ID  
Sent By ccole Date 2015-08-31 Time 07:32 Rev Time 0.00
Received By ccole Date 2015-08-31 Time 06:55 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-07-27 Cont ID  
Sent By ccole Date 2015-07-27 Time 16:58 Rev Time 0.00
Received By ccole Date 2015-07-27 Time 16:58 Sent To  
Notes
2015-07-27 17:13:551ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15070309
 7/27/15
  
 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE AC
 SYSTEMS- REFER TO SECTION 13-407.1.ABC.1 FLORIDA
 BUILDING CODE 2004, OR THE CURRENT CODE IN EFFECT-
 SECTION C403.2.1 FLORIDA BUILDING CODE ENERGY
 CONSERVATION- 2014. PLEASE NOTE THAT 6-TONS OF COOLING
 FOR A 1026 SF. BUILDING SEEMS TO BE OVERSIZED- REFER TO
 SECTION C403.2.2. PLEASE ALSO NOTE THAT THE ELECTRICAL
 SCHEDULE ON SHEET A-1 DOES NOT SHOW CIRCUIT BREAKER
 SIZES FOR THE TWO 3 TON SYSTEMS WHICH SEEMS TO INDICATE
 THAT THESE SYSTEMS ARE BEING INSTALLED NEW: PLEASE
 CLARIFY.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-08-27 Cont ID  
Sent By tklarge Date 2015-08-27 Time 09:50 Rev Time 0.00
Received By tklarge Date 2015-08-27 Time 09:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-07-24 Cont ID  
Sent By tklarge Date 2015-07-24 Time 04:27 Rev Time 0.00
Received By tklarge Date 2015-07-24 Time 03:06 Sent To  
Notes
2015-07-24 04:27:421) SHT. C1 - ACCESSIBILITY NOTES - NOTE #2 REFERS TO
 ACCESSIBLE DRINKING FOUNTAINS IN THE TRAILER.THERE ARE
 NO DRINKING FOUNTAINS IN THIS TRAILER NOR DOES IT
 APPEARS THAT PROVISIONS ARE IN PLACE TO CONNECT ANY. A
 MINIMUM OF 2 DRINKING FOUNTAINS ARE REQUIRED (HI-LO)
 PER THE 2014 FBC-ACCESSIBILITY SEC. 211.2.
 2) INDICATE OCCUPANT LOAD PER FBC-BUILDING, TABLE
 1004.1.2.
 3) INDICATE THE OCCUPANCY TYPE PER 2014 FBC SEC.302.1.
 4) SHT. C1 - PLUMBING NOTES - PLUMBING NOTE #5 - THE
 RELIEF LINE FOR THE WATER HEATER SHALL DISCHARGE
 THROUGH AN AIR GAP LOCATED IN THE SAME ROOM AS THE
 WATER HEATER PER 2014 FBC-PLUMBING, SEC.504.6 (2).
 5) SUBMIT 2 COPIES OF MANUFACTURER'S SPECIFICATION
 SHEETS/INSTALL MANUAL FOR THE EEMAX WATER HEATER. WPB
 AMEND. TO FBC SEC. 107.2.1.
 6) SHOW THE INSIDE CLEAR DIMENSIONS FOR THE TOILET
 ROOM.WPB AMEND. TO FBC SEC. 107.2.1.
 7) THERE APPEARS TO BE A DISCREPANCY ON THE PLANS
 REGARDING THE SIZE OF THE TRAILER. SHT. C 1 STATES THE
 TRAILER AS BEING 24 FEET WIDE BY 44 FEET LONG AND THE
 SITE PLAN NOTES THE CONSTRUCTION OFFICE AS 3278 SQ,
 FEET. CLARIFY.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2015-10-05 Cont ID  
Sent By albarran Date 2015-10-06 Time 13:24 Rev Time 0.50
Received By eschneid Date 2015-10-05 Time 14:47 Sent To E
Notes
2015-10-05 14:48:40PERMIT WILL NOT BE ISSUED UNTIL A LANDSCAPE PLAN FOR
 THE RESTORATION OF THE LIMITS OF WORK IS SUBMITTED.

Review Stop Z ZONING
Rev No 2 Status F Date 2015-09-11 Cont ID  
Sent By eschneid Date 2015-09-11 Time 15:14 Rev Time 0.50
Received By eschneid Date 2015-09-04 Time 10:05 Sent To  
Notes
2015-09-11 15:16:13FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSES TO COMMENTS.
  
 1) REPEAT COMMENT: PROVIDE A REVISED SITE PLAN THAT
 SHOWS THE SPECIFIC TRAILERS BEING USED AND THEIR EXACT
 LOCATIONS IN RELATIONSHIP TO THE INTERIOR LANDSCAPE
 ISLAND AND THE EXISTING CURBLINES. THE TRAILER TOW BARS
 ARE NOT SHOWN ON THE SITE PLAN. SINCE THE TRAILER PLANS
 DO NOT INCLUDE WHICH WAY THEY ARE ORIENTED, STAFF IS
 UNABLE TO DETERMINE IMPACT ? IF THE TOW BARS ARE ON THE
 EAST SIDE THEN ONE WILL BE DIRECTLY INTO A TREE.
 ADDITIONALLY, THE RAMPS SHALL BE SHOWN ON THE SITE PLAN
 TO SEE HOW THEY AFFECT THE SURROUNDING LANDSCAPE AND
 PARKING.
  
 2) WILL THERE BE MEETINGS OR NON-CONSTRUCTION PERSONAL
 USING THE TRAILERS? IF SO, PLEASE COORDINATE WITH THE
 BUILDING REVIEWER HOW THE ADA PARKING WILL BE
 ADDRESSED. THIS SHALL BE SHOWN ON THE SITE PLAN.
  
 3) PRIOR TO ZONING APPROVAL OF THIS PERMIT, THE
 LANDSCAPE PLAN SHALL BE SUBMITTED AS A SEPARATE PERMIT,
 WITH PLANS. IT SHALL INCLUDE THE REPLACEMENT OF THE
 REQUIRED TREES IN THE INTERIOR AND TERMINAL ISLANDS
 ALONG THE EAST PARKING ROW AND THE REPLACEMENT OF THE
 TREE IN THE NORTH/SOUTH DIVIDER MEDIAN. PLEASE NOTE
 THAT THE PROPOSED LANDSCAPE PLAN SUBMITTED WITH THIS
 PERMIT DOES NOT SHOW TWO OF THE REQUIRED TREES.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2015-07-30 Cont ID  
Sent By eschneid Date 2015-07-30 Time 13:44 Rev Time 0.75
Received By eschneid Date 2015-07-28 Time 10:49 Sent To  
Notes
2015-07-30 14:34:54FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSES TO COMMENTS.
  
 1) THE SITE AND CIVIL PLANS SHOW THE CONSTRUCTION
 OFFICE AREA AS HAVING 3,278 SQUARE FEET YET THE MODULAR
 STRUCTURE PLAN SHOWS THE TRAILERS HAVING ONLY 1,026.5
 SQUARE FEET. PLEASE EXPLAIN THIS DISCREPANCY.
  
 2) THE 60 FOOT BY 54.7 FOOT BOX SHOWN AS THE
 CONSTRUCTION OFFICE AREA NOR THE ACTUAL CONSTRUCTION
 TRAILERS, SHOWN AS 44 FOOT BY 23.33 FOOT, MAY ENCROACH
 ONTO THE INTERIOR LANDSCAPE ISLAND.
  
 3) PROVIDE A REVISED SITE PLAN THAT SHOWS THE SPECIFIC
 TRAILERS BEING USED AND THEIR EXACT LOCATIONS IN
 RELATIONSHIP TO THE INTERIOR LANDSCAPE ISLAND AND THE
 EXISTING CURBLINES. THIS PLAN SHALL INCLUDE THE CANOPY
 OF THE EXISTING TREES SURROUNDING THE TRAILER SITE. THE
 TRAILERS SHALL NOT BE PLACED SO AS TO DISRUPT THE TREE
 CANOPY (IE. TOUCHING CANOPY SO AS TO RELOCATE OR BREAK
 BRANCHES OR REQUIRING THE CANOPY TO BE TRIMMED BACK TO
 CREATE A TREE THAT DOES NOT MEET FLORIDA GRADE NO. 1).
  
 4) THERE SHALL BE A TURN AROUND SPACE/BACKOUT ASSIST
 FOR THE USERS OF THE DEAD END PARKING ROW THAT IS
 TERMINATED BY THE NEW TRAILER PLACEMENT. THIS SHALL BE
 SHOWN ON THE SITE PLAN.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
  