Plan Review Details - Permit 15070296
Plan Review Stops For Permit 15070296
Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2015-08-11 Cont ID  
Sent By cranford Date 2015-08-11 Time 10:21 Rev Time 0.00
Received By cranford Date 2015-08-11 Time 10:13 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2015-07-15 Cont ID  
Sent By cranford Date 2015-07-15 Time 14:14 Rev Time 0.00
Received By cranford Date 2015-07-15 Time 08:55 Sent To  
Notes
2015-07-15 14:14:33PLEASE INDICATE WHERE THE SAMPLING PORT FOR THE GREASE
 TRAP WILL BE LOCATED. ALL INTERCEPTION UNITS SHALL BE
 INSTALLED AT A LOCATION ON THE PREMISES TO BE EASILY
 ACCESSIBLE FOR CLEANING AND INSPECTION. (SECTION 90-127
 OF THE CODE OF ORDINANCES)
  
 KELLY CRANFORD, P.E.
 LAND DEVELOPMENT ENGINEER
 PUBLIC WORKS DEPARTMENT
 CITY OF WEST PALM BEACH
 [email protected]
 561-494-1098 (OFFICE)

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-08-11 Cont ID  
Sent By cranford Date 2015-08-11 Time 10:21 Rev Time 0.00
Received By cranford Date 2015-08-03 Time 08:26 Sent To  
Notes
2015-08-04 08:27:59ON TLARGE DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-07-15 Cont ID  
Sent By cranford Date 2015-07-15 Time 14:14 Rev Time 0.00
Received By cranford Date 2015-07-15 Time 14:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-08-07 Cont ID  
Sent By tklarge Date 2015-08-07 Time 09:48 Rev Time 0.00
Received By tklarge Date 2015-08-07 Time 09:48 Sent To  
Notes
2015-08-07 09:49:37PASSED W/ PROVISO - WATER RISER DIAGRAM SHALL BE
 SUBMITTED FOR REVIEW AND APPROVAL PRIOR TO 2ND ROUGH
 INSPECTION. TKL.

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-07-13 Cont ID  
Sent By tklarge Date 2015-07-13 Time 06:11 Rev Time 0.00
Received By tklarge Date 2015-07-13 Time 05:46 Sent To  
Notes
2015-07-13 06:11:471) SUBMIT SIZING CALCULATIONS FOR THE GREASE
 INTERCEPTOR IN ACCORDANCE WITH FBC-PLUMBING
 SEC.1003.3.4. THE SIZING CALCULATIONS CAN BE DONE BY
 SCHIER. YOU CAN CONTACT LEE SCHNEEWEISS AT
 1-800-538-4792.
 2) THE FLOOR DRAIN SHALL BE EQUIPPED WITH A TRAP PRIMER
 PER 2014 FPC SEC.1002.4.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  