Plan Review Details - Permit 15070293
Plan Review Stops For Permit 15070293
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-08-10 Cont ID  
Sent By skennedy Date 2015-08-10 Time 11:12 Rev Time 0.00
Received By skennedy Date 2015-08-10 Time 11:12 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-08-02 Cont ID  
Sent By skennedy Date 2015-08-02 Time 11:43 Rev Time 0.00
Received By skennedy Date 2015-08-02 Time 11:43 Sent To  
Notes
2015-08-02 11:49:261ST REVIEW: FBC 2014 5TH ED.
  
 FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN.
  
 PLEASE PROVIDE DETAILS FOR THE "NEW BULKHEAD" AT THE
 DEMOLISHED WALL. IS IT A STRUCTURAL COMPONENT INTENDED
 TO CARRY A DEAD LOAD?
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-08-10 Cont ID  
Sent By skennedy Date 2015-08-10 Time 11:12 Rev Time 0.00
Received By skennedy Date 2015-08-10 Time 11:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-08-02 Cont ID  
Sent By skennedy Date 2015-08-02 Time 11:44 Rev Time 0.00
Received By skennedy Date 2015-08-02 Time 11:43 Sent To  
Notes
2015-08-02 11:56:081ST REVIEW: FBC 2014 5TH ED. NEC 2011
  
 FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN.
  
 FBC 107.3.5.3 PROVIDE A CIRCUITING PLAN OR NOTES UPON
 THE PLAN TO DEMONSTRATE THE FOLLOWING. WIRE SIZE,
 WIRING METHOD, OCP.
  
 FBC-R 315.1 ? PROVIDE CARBON MONOXIDE ALARMS WITHIN 10
 FEET OF EACH SLEEPING ROOM, IF APPLICABLE.
  
 FBC- 107.3.5.3 ? PROVIDE SMOKE DETECTORS PURSUANT TO
 FBC-R 314.3.1 AS REQUIRED FOR NEW DWELLINGS.
  
 NEC 406.11- PROVIDE TAMPER RESISTANT RECEPTACLES.
  
 NEC 210.12B - OUTLETS TO BE AFCI PROTECTED.
  
 NEC 210 - PROVIDE GFCI PROTECTED OUTLET ON BATHROOM.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-08-10 Cont ID  
Sent By skennedy Date 2015-08-10 Time 11:12 Rev Time 0.00
Received By skennedy Date 2015-08-07 Time 13:06 Sent To  
Notes
2015-08-07 13:06:16RESUB ROUTED TO SKENNEDY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-08-02 Cont ID  
Sent By skennedy Date 2015-08-02 Time 11:44 Rev Time 0.00
Received By skennedy Date 2015-07-08 Time 08:16 Sent To  
Notes
2015-08-01 14:15:258/1 TO SAK DESK
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2015-08-10 Cont ID  
Sent By skennedy Date 2015-08-10 Time 11:11 Rev Time 0.00
Received By skennedy Date 2015-08-10 Time 11:11 Sent To  
Notes
2015-08-10 11:12:29MECHANICAL BY SEPARATE PERMIT IF NEEDED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-08-02 Cont ID  
Sent By skennedy Date 2015-08-02 Time 11:44 Rev Time 0.00
Received By skennedy Date 2015-08-02 Time 11:44 Sent To  
Notes
2015-08-02 11:59:181ST REVIEW: FBC 2014 5TH ED.
  
 FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN.
  
 FBC 107 - THERE ARE INADEQUATE NOTES OR INFORMATION AS
 TO THE MECHANICAL VENTILATION SYSTEM PROVIDED.
  
 FBC- 107.3.5.3 ? PROVIDE A MECHANICAL PLAN OR NOTES TO
 SHOW SUPPLY DUCTS PER FBC-R M16 & BATH EXHAUST PER
 FBC-R M15.
  
 AND PURSUANT TO FBC-R-M 1602.4 BALANCED AIR RETURN IS
 PROVIDED AT BEDROOMS AFFECTED.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  