Plan Review Details - Permit 15070224
Plan Review Stops For Permit 15070224
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-07-24 Cont ID  
Sent By shill Date 2015-07-24 Time 16:45 Rev Time 0.00
Received By shill Date 2015-07-24 Time 16:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-07-17 Cont ID  
Sent By shill Date 2015-07-17 Time 14:12 Rev Time 0.00
Received By shill Date 2015-07-17 Time 14:12 Sent To  
Notes
2015-07-17 14:16:34****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. THE USE OF THE ROOM IS NOT CLEAR. PLAN STATES THIS
 IS A "REPUMP ROOM." A FIRE RATED DOOR WITH A CLOSER IS
 PROPOSED.
  
 SEE FBC 1008.1.10:
  
 ELECTRICAL ROOMS WITH EQUI9PMENT RATED 1200 AMPERES OR
 MORE AND OVER 6 FEET WIDE THAT CONTAIN OVER-CURRENT
 DEVICES, SWITCHING DEVICES OR CONTROL DEVICES WITH EXIT
 OR EXIT ACCESS DOORS SHALL BE EQUIPPED WITH PANIC
 HARDWARE OR FIRE EXIT HARDWARE.
  
 REVISE PLAN TO SHOW COMPLIANCE.
  
 2. ON THE PLAN, PROVIDE THE PRINTED NAME AND SIGNATURE
 OF THE INDIVIDUAL TAKING RESPONSIBILITY FOR THE PLAN,
 FBC 107.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-07-24 Cont ID  
Sent By shill Date 2015-07-24 Time 16:45 Rev Time 0.00
Received By shill Date 2015-07-24 Time 11:33 Sent To  
Notes
2015-07-24 11:33:42RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-07-17 Cont ID  
Sent By shill Date 2015-07-17 Time 14:16 Rev Time 0.00
Received By shill Date 2015-07-07 Time 15:26 Sent To  
Notes
2015-07-07 15:26:23ROUTED TO BLDG $5000 & UNDER