Plan Review Details - Permit 15070145
Plan Review Stops For Permit 15070145
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2016-02-26 Cont ID  
Sent By rmcdouga Date 2016-02-26 Time 09:46 Rev Time 0.00
Received By rmcdouga Date 2016-02-26 Time 07:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2016-02-10 Cont ID  
Sent By rmcdouga Date 2016-02-10 Time 09:18 Rev Time 0.00
Received By rmcdouga Date 2016-01-27 Time 19:04 Sent To  
Notes
2016-02-10 09:17:12PLAN
 REVIEW COMMENTS
  
 3RD REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE LOCATION OF THE PROPOSED STRUCTURES ON THE SITE
 PLAN ON SHEET S2.00/C1.00 DOES NOT MATCH THE SURVEY.
 FBC 107.2.1
  
 2) THE INSTALLATION INSTRUCTIONS, INDICATING WHICH
 APPROVED ROOFING ASSEMBLY WILL BE USED, WERE NOT
 SUBMITTED FOR THE GAF MODIFIED ROOF SYSTEM (FL16732).

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-11-10 Cont ID  
Sent By rmcdouga Date 2015-11-10 Time 18:45 Rev Time 0.00
Received By rmcdouga Date 2015-11-09 Time 17:45 Sent To  
Notes
2015-11-10 09:51:58PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PAPER PLANS AND DOCUMENTS THAT ARE SUBMITTED FOR
 PUBLIC RECORD ARE REQUIRED TO BE SIGNED, SEALED AND
 DATED BY THE PROFESSIONAL ENGINEER IN RESPONSIBLE
 CHARGE. THE ENGINEER'S HANDWRITTEN SIGNATURE IS
 REQUIRED ( FACSIMILES ARE NOT ACCEPTABLE). THE SEAL
 SHALL BE A MINIMUM OF 1-7/8 INCHES IN DIAMETER AND
 COMPLY WITH FAC 61G15-23.001. DIGITAL SEALS AND
 SIGNATURES CAN ONLY BE USED FOR ELECTRONICALLY
 TRANSMITTED PLANS AND OTHER DOCUMENTS. FS 471, FAC
 61G15-23.002 AND FAC 61G15-23.003
  
 2) SHOW COMPLIANCE WITH FBC R401.3 FOR SURFACE
 DRAINAGE. SEE COMMENT #5 FROM FIRST REVIEW.
  
 3) PROVIDE A SECTIONAL GARAGE DOOR BUCK DETAIL.
 INDICATE THE SPECIFIC ANCHORS AND SPACING. FBC 107.2.1
 & FBC-R612.7.2
  
 4) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 WAYNE DALTON GARAGE DOOR HAS DESIGN PRESSURES OF +30.0
 , -33.50 PSF AND THE PLANS REQUIRE +37.30, -45.70 PSF.
  
 5) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 THERMA TRU GLAZED OUTSWING STEEL DOOR FL7586.1 HAS
 DESIGN PRESSURES OF + 47.0, -47.0 PSF AND THE PLANS
 REQUIRE +41.24, -53.58 PSF.
  
 6) SUBMIT TWO SETS OF PRODUCT APPROVALS THAT HAVE BEEN
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD FOR THE PEEL AND STICK ROOFING TILE UNDERLAYMENT
 AS REQUIRED BY DCA RULE 9N-3 & FBC 107.3.4.1.
  
 7) SUBMIT TWO SETS OF PRODUCT APPROVALS THAT HAVE BEEN
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD FOR THE ROOFING MATERIAL FOR THE GARAGE ROOF
 FLAT DECK AS REQUIRED BY DCA RULE 9N-3 & FBC 107.3.4.1.
  
 8) SPECIFY THE METHOD OF ATTACHMENT THAT WILL BE USED
 TO INSTALL THE CEMENT ROOF TILE AND RESIST THE OVERTURN
 MOMENT. IF AN ADHESIVE IS USED, SUBMIT THE PRODUCT
 APPROVALS FOR IT. FBC 107.2.1 & FBC-R905.3
  
 9) R905.11.1 SLOPE. MODIFIED BITUMEN MEMBRANE ROOFS
 SHALL HAVE A DESIGN SLOPE OF A MINIMUM OF ONE-FOURTH
 UNIT VERTICAL IN 12 UNITS HORIZONTAL (2-PERCENT SLOPE)
 FOR DRAINAGE. (GARAGE) SPECIFY THE SLOPE ON THE PLANS.
  
 10) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-09-15 Cont ID  
Sent By rmcdouga Date 2015-09-15 Time 11:38 Rev Time 0.00
Received By rmcdouga Date 2015-09-08 Time 17:15 Sent To  
Notes
2015-09-14 09:51:33PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PLANS HAVE SEVERAL REFERENCES TO THE 2010 FBC.
 THE FBC FIFTH EDITION (2014) WENT INTO EFFECT ON JUNE
 30, 2015. ALL NEW PERMITS APPLIED FOR ON OR AFTER THAT
 DATE ARE REQUIRED TO COMPLY WITH AND REFERENCE THE FBC
 FIFTH EDITION. THIS PROJECT SHOULD REFERENCE THE FBC
 FIFTH EDITION (2014) RESIDENTIAL.
  
 2) THE COMPONENT AND CLADDING PRESSURES ON SHEET A1.00
 ARE FOR 10 SQFT WITH A 15' MEAN ROOF HEIGHT. THIS TWO
 STORY HOUSE WITH A MEAN ROOF HEIGHT OF AROUND 23 FEET.
 THE DETACHED GARAGE HAS A MRH OF ABOUT 12 FEET. FBC -
 R301.2.1
  
 3) THE OCCUPANCY TYPE IS R-3 PER FBC 301.
  
 4) THE CONSTRUCTION TYPE IS V-B PER FBC 602.
  
 5) R401.3 DRAINAGE. SURFACE DRAINAGE SHALL BE DIVERTED
 TO A STORM SEWER CONVEYANCE OR OTHER APPROVED POINT OF
 COLLECTION THAT DOES NOT CREATE A HAZARD. LOTS SHALL BE
 GRADED TO DRAIN SURFACE WATER AWAY FROM FOUNDATION
 WALLS. THE GRADE SHALL FALL A MINIMUM OF 6 INCHES (152
 MM) WITHIN THE FIRST 10 FEET (3048 MM).
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL
 WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE
 CONSTRUCTED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE.
 IMPERVIOUS SURFACES WITHIN 10 FEET (3048 MM) OF THE
 BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF 2
 PERCENT AWAY FROM THE BUILDING.
 SUBMIT TWO COPIES OF A SURFACE WATER DRAINAGE PLAN.
  
 6) ON SHEET S1.00 THE FOOTINGS FOR THE INTERIOR WALLS
 ON THE FOUNDATION PLAN ARE INCORRECTLY MARKED DETAIL #3
 AND THE SHOULD BE DETAIL #4. FBC 107.2.1
  
 7) PROVIDE A LINTEL SCHEDULE ON THE PLANS. FBC107.2.1
  
 8) R905.11.1 SLOPE. MODIFIED BITUMEN MEMBRANE ROOFS
 SHALL HAVE A DESIGN SLOPE OF A MINIMUM OF ONE-FOURTH
 UNIT VERTICAL IN 12 UNITS HORIZONTAL (2-PERCENT SLOPE)
 FOR DRAINAGE. (GARAGE)
  
 9) R318.5 PROTECTION AGAINST DECAY AND TERMITES.
 GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON ALL BUILDINGS
 WITH EAVES OF LESS THAN 6 INCHES (152 MM) HORIZONTAL
 PROJECTION EXCEPT FOR GABLE END RAKES OR ON A ROOF
 ABOVE ANOTHER ROOF. (GARAGE)
  
 10) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT
 APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION
 INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR EACH OF
 THE DIFFERENT ROOFING MATERIALS, WINDOW/GLASS TYPES,
 STRUCTURAL MULLIONS AND EXTERIOR DOOR TYPES.
  
 11 ) IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE
 CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER
 INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN
 ADDRESSED.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-02-09 Cont ID  
Sent By rmcdouga Date 2016-02-09 Time 19:07 Rev Time 0.00
Received By rmcdouga Date 2016-02-09 Time 18:31 Sent To  
Notes
2016-02-09 19:07:33RED LINED PLANS.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-11-12 Cont ID  
Sent By rmcdouga Date 2015-11-12 Time 13:36 Rev Time 0.00
Received By rmcdouga Date 2015-11-12 Time 13:36 Sent To  
Notes
2015-11-10 18:47:27PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY ELECTRIC
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PAPER PLANS AND DOCUMENTS THAT ARE SUBMITTED FOR
 PUBLIC RECORD ARE REQUIRED TO BE SIGNED, SEALED AND
 DATED BY THE PROFESSIONAL ENGINEER IN RESPONSIBLE
 CHARGE. THE ENGINEER'S HANDWRITTEN SIGNATURE IS
 REQUIRED ( FACSIMILES ARE NOT ACCEPTABLE). THE SEAL
 SHALL BE A MINIMUM OF 1-7/8 INCHES IN DIAMETER AND
 COMPLY WITH FAC 61G15-23.001. DIGITAL SEALS AND
 SIGNATURES CAN ONLY BE USED FOR ELECTRONICALLY
 TRANSMITTED PLANS AND OTHER DOCUMENTS. FS 471, FAC
 61G15-23.002 AND FAC 61G15-23.003
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-09-09 Cont ID  
Sent By rmcdouga Date 2015-09-09 Time 14:04 Rev Time 0.00
Received By rmcdouga Date 2015-09-08 Time 19:02 Sent To  
Notes
2015-09-09 09:26:40PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014) / 2011 NEC
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY ELECTRICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE FBC FIFTH EDITION (2014) WENT INTO EFFECT ON
 JUNE 30, 2015. THE PERMIT APPLICATION FOR THIS PROJECT
 WAS SUBMITTED ON JULY 6, 2015. UPDATE REFERENCES TO THE
 2010 FBC TO THE 2014 FBC.
  
 2) THE PLANS DO NOT INDICATE HOW THE ELECTRIC WILL BE
 SUPPLIED TO THE DETACHED GARAGE. PROVIDE ALL DETAILS,
 WIRE SIZES, CONDUIT SIZE, DISCONNECTS, PANEL LOCATIONS,
 PANEL SCHEDULES, ETC. TO SHOW COMPLIANCE WITH THE 2011
 NEC. INCLUDING DISCONNECT, PANEL SCHEDULES, ETC. FBC
 107.2.1
  
 3) NEC 210.52 (C) (1) - A RECEPTACLE OUTLET SHALL BE
 INSTALLED AT EACH COUNTERTOP SPACE 12 INCHES OR WIDER
 SO THAT NO POINT ALONG THE WALL LINE IS MORE THAN 2
 FEET MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET IN
 THAT SPACE. THE COUNTERTOP SPACE ACROSS FROM THE PANTRY
 DOES NOT HAVE ANY RECEPTACLE OUTLETS SPECIFIED ON THE
 PLANS.
  
 4) NEC 210.52(A) - (H) OUTLET SPACING, IT APPEARS SOME
 POINTS ALONG THE WALL SPACE EXCEED 6' FROM AN OUTLET
 AND SOME USEABLE WALL SPACES 2 FT OR MORE IN WIDTH ARE
 MISSING THE REQUIRED RECEPTACLE OUTLETS.
  
 5) THE ELECTRICAL RISER DOES NOT MATCH THE FLOOR PLAN.
 THE FLOOR PLAN HAS A 200 AMP SUB-PANEL IN A CLOSET ON
 THE FIRST FLOOR AND ANOTHER 200 AMP SUB-PANEL LOCATED
 IN THE HALL ON THE SECOND FLOOR. PLEASE CLARIFY. NEC
 240.24 (D) ELECTRICAL PANELS SHALL NOT BE LOCATED IN
 THE VICINITY OF EASILY IGNITIBLE MATERIAL, SUCH AS
 CLOTHES CLOSETS.
  
 6) FBC 107.2.1 IT APPEARS FROM THE MECHANICAL PLANS
 THAT THE AIR HANDLER IS LOCATED IN THE ATTIC. SHOW THE
 LOCATION OF THE AHU ON THE ELECTRICAL PLANS. NEC 440.11
 & 440.14 SHOW THE LOCATION OF THE REQUIRED A/C
 EQUIPMENT DISCONNECTING MEANS ON THE PLANS. NEC 210.63
 - PROVIDE A GFCI PROTECTED SERVICE OUTLET FOR WITHIN
 25' OF MECHANICAL EQUIPMENT. NEC 110.26 SUFFICIENT
 ACCESS AND WORKING SPACE SHALL BE PROVIDED AND
 MAINTAINED ABOUT ALL ELECTRICAL EQUIPMENT TO PERMIT
 READY AND SAFE OPERATION AND MAINTENANCE OF SUCH
 EQUIPMENT. NEC 210.70 (A)(3) PROVIDE A SWITCHED
 LIGHTING OUTLET AT OR NEAR THE EQUIPMENT. NEC 110.33
 (B) PERMANENT LADDERS OR STAIRWAYS SHALL BE PROVIDED TO
 GIVE SAFE ACCESS TO THE WORKING SPACE AROUND ELECTRICAL
 EQUIPMENT INSTALLED ON PLATFORMS, BALCONIES, OR
 MEZZANINE FLOORS OR IN ATTIC OR ROOF ROOMS OR SPACES.
  
 7) NEC 210.8(A)(2) THE GARAGE DOOR OPENER RECEPTACLE
 OUTLETS ARE REQUIRED TO BE GFCI PROTECTED.
  
 8) NEC 406.11 - TAMPER-RESISTANT RECEPTACLES ARE
 REQUIRED.
  
 9) NEC 110.3 (B) SMOKE ALARMS AND CARBON MONOXIDE
 ALARMS SHALL BE INSTALLED IN ACCORDANCE WITH THEIR
 LISTINGS OR LABELING AND PER MANUFACTURER'S
 INSTRUCTIONS IN ORDER TO INSURE OPTIMUM COVERAGE.
  
  
  
  
  
  

Review Stop HIST HISTORICAL
Rev No 4 Status P Date 2016-02-24 Cont ID  
Sent By fmittner Date 2016-02-24 Time 14:48 Rev Time 0.00
Received By fmittner Date 2016-02-24 Time 14:48 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 3 Status F Date 2016-02-10 Cont ID  
Sent By fmittner Date 2016-02-10 Time 14:14 Rev Time 0.00
Received By fmittner Date 2016-02-10 Time 14:14 Sent To  
Notes
2016-02-10 14:16:55ROOFING TILE NOT HIGH PROFILE.

Review Stop HIST HISTORICAL
Rev No 2 Status F Date 2015-11-05 Cont ID  
Sent By fmittner Date 2015-11-05 Time 09:52 Rev Time 0.00
Received By fmittner Date 2015-11-05 Time 09:52 Sent To  
Notes
2015-11-05 09:54:03PER HPB, REQUIRE PARAPET ON GARAGE WALL TO SURROUND ALL
 SIDES, ROOF TILE TO BE HIGH PROFILE, OUTRIGERS SHALL BE
 WOOD - NO PRODUCT APPROVALS.

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2015-07-24 Cont ID  
Sent By fmittner Date 2015-07-24 Time 10:17 Rev Time 0.00
Received By fmittner Date 2015-07-24 Time 10:17 Sent To  
Notes
2015-07-24 10:18:31NEW CONSTRUCTION IN HISTORIC DISTRICT REQUIRES APPROVAL
 BY THE HPB VIA SUBMITTAL OF CERTIFICATE OF
 APPROPRIATENESS APPLICATION. QUESTIONS CONTACT
 FRIEDERIKE MITTNER AT 822-1457.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-02-26 Cont ID  
Sent By rmcdouga Date 2016-02-26 Time 09:46 Rev Time 0.00
Received By rmcdouga Date 2016-02-19 Time 14:38 Sent To  
Notes
2016-02-19 14:39:05RESUB ROUTED TO FMITTNER VIA SGRAHAM'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-02-11 Cont ID  
Sent By rmcdouga Date 2016-02-11 Time 07:19 Rev Time 0.00
Received By rmcdouga Date 2015-12-28 Time 13:59 Sent To  
Notes
2015-12-28 14:00:04R15

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-11-12 Cont ID  
Sent By rmcdouga Date 2015-11-12 Time 13:36 Rev Time 0.00
Received By rmcdouga Date 2015-11-04 Time 13:30 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-09-15 Cont ID  
Sent By rmcdouga Date 2015-09-15 Time 11:38 Rev Time 0.00
Received By rmcdouga Date 2015-07-06 Time 13:05 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2015-09-08 Cont ID  
Sent By rmcdouga Date 2015-09-08 Time 16:53 Rev Time 0.00
Received By rmcdouga Date 2015-09-08 Time 16:53 Sent To  
Notes
2015-09-08 16:54:46MU 2015-11612, NO FEES DUE.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2016-02-09 Cont ID  
Sent By rmcdouga Date 2016-02-09 Time 18:15 Rev Time 0.00
Received By rmcdouga Date 2016-02-09 Time 18:14 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-11-10 Cont ID  
Sent By rmcdouga Date 2015-11-10 Time 09:51 Rev Time 0.00
Received By rmcdouga Date 2015-11-10 Time 09:51 Sent To  
Notes
2015-11-10 09:51:15PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PAPER PLANS AND DOCUMENTS THAT ARE SUBMITTED FOR
 PUBLIC RECORD ARE REQUIRED TO BE SIGNED, SEALED AND
 DATED BY THE PROFESSIONAL ENGINEER IN RESPONSIBLE
 CHARGE. THE ENGINEER'S HANDWRITTEN SIGNATURE IS
 REQUIRED ( FACSIMILES ARE NOT ACCEPTABLE). THE SEAL
 SHALL BE A MINIMUM OF 1-7/8 INCHES IN DIAMETER AND
 COMPLY WITH FAC 61G15-23.001. DIGITAL SEALS AND
 SIGNATURES CAN ONLY BE USED FOR ELECTRONICALLY
 TRANSMITTED PLANS AND OTHER DOCUMENTS. FS 471, FAC
 61G15-23.002 AND FAC 61G15-23.003
  
 2) REVISE PLANS TO SHOW THE SUPPLY DUCT FROM THE AHU IN
 THE SECOND FLOOR ATTIC DOWN TO THE FIRST FLOOR CEILING.
 SPECIFY THE DUCT SIZE AND SHOW THE CHASE THAT WILL
 ENCLOSE THE DUCT. FBC 107.2.1
  
 3) THE ENERGY FORM 405 THAT WAS SUBMITTED IS THE 2010
 VERSION. SUBMIT THE 2014 VERSION OF FORM 405. 2014 FBC
 ENERGY CONSERVATION
  
 4) THE JURISDICTION NUMBER FOR WEST PALM BEACH IS
 604700, NOT 603800.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-09-09 Cont ID  
Sent By rmcdouga Date 2015-09-09 Time 15:46 Rev Time 0.00
Received By rmcdouga Date 2015-09-09 Time 15:46 Sent To  
Notes
2015-09-09 15:46:28PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) IT APPEARS THAT THE AHU IS LOCATED IN THE ATTIC.
 SHOW COMPLIANCE WITH FBC-R - M1305.1.3 ATTICS
 CONTAINING APPLIANCES SHALL BE PROVIDED WITH AN OPENING
 AND A CLEAR AND UNOBSTRUCTED PASSAGEWAY LARGE ENOUGH TO
 ALLOW REMOVAL OF THE LARGEST APPLIANCE, BUT NOT LESS
 THAN 30 INCHES (762 MM) HIGH AND 22 INCHES (559 MM)
 WIDE AND NOT MORE THAN 6 FEET (1829 MM) LONG MEASURED
 ALONG THE CENTERLINE OF THE PASSAGEWAY FROM THE OPENING
 TO THE APPLIANCE. THE PASSAGEWAY SHALL HAVE CONTINUOUS
 SOLID FLOORING IN ACCORDANCE WITH CHAPTER 5 NOT LESS
 THAN 24 INCHES (610 MM) WIDE. A LEVEL SERVICE SPACE AT
 LEAST 30 INCHES (762 MM) DEEP AND 30 INCHES (762 MM)
 WIDE SHALL BE PRESENT ALONG ALL SIDES OF THE APPLIANCE
 WHERE ACCESS IS REQUIRED. THE CLEAR ACCESS OPENING
 DIMENSIONS SHALL BE A MINIMUM OF 20 INCHES BY 30 INCHES
 (508 MM BY 762 MM), AND LARGE ENOUGH TO ALLOW REMOVAL
 OF THE LARGEST APPLIANCE.
  
 2) FBC ENERGY CONSERVATION R403.2.4
 AIR-HANDLING UNITS SHALL BE ALLOWED IN ATTICS IF THE
 FOLLOWING CONDITIONS ARE MET:
 1. THE SERVICE PANEL OF THE EQUIPMENT IS LOCATED WITHIN
 6 FEET (1829 MM) OF AN ATTIC ACCESS.
 2. A DEVICE IS INSTALLED TO ALERT THE OWNER OR SHUT THE
 UNIT DOWN WHEN THE CONDENSATION DRAIN IS NOT WORKING
 PROPERLY.
 3. THE ATTIC ACCESS OPENING IS OF SUFFICIENT SIZE TO
 REPLACE THE AIR HANDLER.
 4. A NOTICE IS POSTED ON THE ELECTRIC SERVICE PANEL
 INDICATING TO THE HOMEOWNER THAT THE AIR HANDLER IS
 LOCATED IN THE ATTIC.
  
 3) FBC-R - M1305.1.3.1 ELECTRICAL REQUIREMENTS. A
 LUMINAIRE CONTROLLED BY A SWITCH LOCATED AT THE
 REQUIRED PASSAGEWAY OPENING AND A RECEPTACLE OUTLET
 SHALL BE INSTALLED AT OR NEAR THE APPLIANCE LOCATION IN
 ACCORDANCE WITH CHAPTER 34.
  
 4) SPECIFY THE SIZE OF THE DUCT THAT SUPPLIES THE FIRST
 FLOOR. SPECIFY THE LOCATION OF THE DUCT CHASE ON THE
 MECHANICAL PLAN. FBC 107.2.1
  
 5) SPECIFY THE GRILL SIZES AND CFMS AT EACH SUPPLY
 OUTLET. FBC 107.3.5.1.4
  
 6) SPECIFY THE CLOTHES DRYER EXHAUST SYSTEM ON THE
 PLANS. FBC - R - M1502
  
 7) FBC - R - M1501.1 SPECIFY THAT THE AIR REMOVED BY
 THE MECHANICAL EXHAUST SYSTEMS SHALL BE DISCHARGED TO
 THE OUTDOORS IN ACCORDANCE WITH SECTION M1506.2.
  
  
  
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2016-01-20 Cont ID  
Sent By tklarge Date 2016-01-20 Time 13:02 Rev Time 0.00
Received By tklarge Date 2016-01-20 Time 12:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-11-06 Cont ID  
Sent By tklarge Date 2015-11-06 Time 06:53 Rev Time 0.00
Received By tklarge Date 2015-11-06 Time 06:25 Sent To  
Notes
2015-11-06 06:57:23THE PLANS SHALL BE SIGNED AND SEALED BY THE DESIGN
 PROFESSIONAL OF RECORD PER FAC RULE 61G15-23.002. A
 DIGITAL SEAL APPLIES TO PLANS THAT HAVE BEEN SUBMITTED
 DIGITALLY FOR REVIEW.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-07-28 Cont ID  
Sent By tklarge Date 2015-07-28 Time 05:18 Rev Time 0.00
Received By tklarge Date 2015-07-28 Time 04:45 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2016-02-24 Cont ID  
Sent By fmittner Date 2016-02-24 Time 14:48 Rev Time 0.00
Received By fmittner Date 2016-02-24 Time 14:48 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2016-02-10 Cont ID  
Sent By fmittner Date 2016-02-10 Time 14:14 Rev Time 0.00
Received By fmittner Date 2016-02-10 Time 14:14 Sent To  
Notes
2016-02-10 14:14:59FRONT SETBACK NOT AT 25'-0"

Review Stop Z ZONING
Rev No 2 Status P Date 2015-11-05 Cont ID  
Sent By rmcdouga Date 2015-11-12 Time 13:36 Rev Time 0.00
Received By fmittner Date 2015-11-05 Time 09:52 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2015-07-24 Cont ID  
Sent By fmittner Date 2015-07-24 Time 10:18 Rev Time 0.00
Received By fmittner Date 2015-07-24 Time 10:18 Sent To  
Notes
***NONE***