Plan Review Stops For Permit 15070113 |
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2015-07-08 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2015-07-08 |
Time |
20:08 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2015-07-08 |
Time |
19:36 |
Sent To |
I |
|
Notes |
2015-07-08 20:08:58 | ELECTRICAL PROVISOS FOR PERMIT 15070113: | | PER NEC 314.27 CEILING OR WALL OUTLET INTENDED FOR | | LUMINAIRE SHALL BE LISTED TO SUPPORT 50LB. | | PER NEC 210.52 D, YOU SHALL HAVE A GFCI OUTLET WITHIN | | 3FT. OF THE BATHROOM SINK. (SAME OR ADJACENT WALL) | | PER NEC 410.10D, LUMINAIRES DIRECTLY ABOVE SHOWER OR | | TUB SHALL BE LISTED FOR WET LOCATION | | PER NEC 404.2, UNLESS WORK IS IN CONDUIT WITH AMPLE | | SPARE ROOM, A NEUTRAL SHALL BE RUN TO EVERY SWITCH | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2015-07-08 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2015-07-08 |
Time |
20:09 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2015-07-06 |
Time |
09:07 |
Sent To |
|
|
Notes |