Plan Review Details - Permit 15070113
Plan Review Stops For Permit 15070113
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-07-08 Cont ID  
Sent By albarran Date 2015-07-08 Time 20:08 Rev Time 0.00
Received By albarran Date 2015-07-08 Time 19:36 Sent To I
Notes
2015-07-08 20:08:58ELECTRICAL PROVISOS FOR PERMIT 15070113:
 PER NEC 314.27 CEILING OR WALL OUTLET INTENDED FOR
 LUMINAIRE SHALL BE LISTED TO SUPPORT 50LB.
 PER NEC 210.52 D, YOU SHALL HAVE A GFCI OUTLET WITHIN
 3FT. OF THE BATHROOM SINK. (SAME OR ADJACENT WALL)
 PER NEC 410.10D, LUMINAIRES DIRECTLY ABOVE SHOWER OR
 TUB SHALL BE LISTED FOR WET LOCATION
 PER NEC 404.2, UNLESS WORK IS IN CONDUIT WITH AMPLE
 SPARE ROOM, A NEUTRAL SHALL BE RUN TO EVERY SWITCH
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-07-08 Cont ID  
Sent By albarran Date 2015-07-08 Time 20:09 Rev Time 0.00
Received By albarran Date 2015-07-06 Time 09:07 Sent To  
Notes
2015-07-08 20:10:357/8/15 - PASSED ELECTRICAL REVIEW WITH THE NOTED
 PROVISOS. CONTRACTOR NOTIFIED VIA PHONE MESSAGE. SENT
 TO SMALL READY BIN "E". MA
2015-07-06 09:07:31ROUTED TO ELECTRIC $5000 & UNDER