2015-07-08 12:22:18 | 7/8/2015 |
| PROJECT: PARKING AUTHORITY |
| PERMIT#: 15050564 |
| CODE: 2011EDITION OF THE NEC, FIFTH EDITION OF THE FBC |
| , WPB AMENDMENTS TO THE FBC, CHAPTER 1, ADMINISTRATION, |
| FBC SUPPLEMENTS. |
| 1ST ELECTRICAL PLAN REVIEW. REVISION 15070024 |
| ACTION: DENIED |
| |
| REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW |
| COMMENTS: |
| |
| 1) THE SUBMITTAL IS INDICATED AS A REVISION. THERE IS |
| NO WAY TO REVIEW THIS SUBMITTAL AS THERE ARE NO CLOUDED |
| OR OTHERWISE INDICATED REVISIONS. PLEASE INDICATE |
| CLEARLY WHAT HAS CHANGED FOR THE ORIGINAL. |
| |
| 2) PROVIDE THE ALTERRED RIDER DIAGRAM BATTERY |
| CALCULATIONS, VOLTAGE DROP CALCULATIONS. |
| |
| 3) PROVIDE MANUFACTURER PRODUCT INFORMATION FOR ANY |
| WIRING METHODS AND MATAERIALS. |
| |
| 3) PROVIDE A FIRE STOP DETAIL FOR ALL WALL AND FLOOR |
| PENETRATIONS OF FIRE RATED ASSEMBLIES. NEC 300.21 |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| REVIEW. |