Plan Review Details - Permit 15070024
Plan Review Stops For Permit 15070024
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-08-10 Cont ID  
Sent By skennedy Date 2015-08-12 Time 15:33 Rev Time 0.00
Received By dhayes Date 2015-08-10 Time 16:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-07-08 Cont ID  
Sent By dhayes Date 2015-07-08 Time 12:12 Rev Time 0.00
Received By dhayes Date 2015-07-08 Time 12:12 Sent To  
Notes
2015-07-08 12:22:187/8/2015
 PROJECT: PARKING AUTHORITY
 PERMIT#: 15050564
 CODE: 2011EDITION OF THE NEC, FIFTH EDITION OF THE FBC
 , WPB AMENDMENTS TO THE FBC, CHAPTER 1, ADMINISTRATION,
 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW. REVISION 15070024
 ACTION: DENIED
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) THE SUBMITTAL IS INDICATED AS A REVISION. THERE IS
 NO WAY TO REVIEW THIS SUBMITTAL AS THERE ARE NO CLOUDED
 OR OTHERWISE INDICATED REVISIONS. PLEASE INDICATE
 CLEARLY WHAT HAS CHANGED FOR THE ORIGINAL.
  
 2) PROVIDE THE ALTERRED RIDER DIAGRAM BATTERY
 CALCULATIONS, VOLTAGE DROP CALCULATIONS.
  
 3) PROVIDE MANUFACTURER PRODUCT INFORMATION FOR ANY
 WIRING METHODS AND MATAERIALS.
  
 3) PROVIDE A FIRE STOP DETAIL FOR ALL WALL AND FLOOR
 PENETRATIONS OF FIRE RATED ASSEMBLIES. NEC 300.21
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-08-12 Cont ID  
Sent By skennedy Date 2015-07-29 Time 15:32 Rev Time 0.00
Received By skennedy Date 2015-07-29 Time 15:32 Sent To  
Notes
2015-08-12 15:33:56REVIEW BY PLEDUC

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-08-12 Cont ID  
Sent By pleduc Date 2015-07-07 Time   Rev Time 0.00
Received By skennedy Date 2015-07-07 Time 10:40 Sent To E
Notes
2015-07-07 10:45:48THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THE SUBMITTAL IS INDICATED AS A REVISION. THERE IS
 NO WAY TO REVIEW THIS SUBMITTAL AS THERE ARE NO CLOUDED
 OR OTHERWISE INDICATED REVISIONS. PLEASE INDICATE
 CLEARLY WHAT HAS CHANGED FOR THE ORIGINAL.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-08-12 Cont ID  
Sent By skennedy Date 2015-08-12 Time 15:33 Rev Time 0.00
Received By skennedy Date 2015-07-27 Time 14:17 Sent To  
Notes
2015-07-27 14:20:37FIRE BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-07-08 Cont ID  
Sent By dhayes Date 2015-07-08 Time 12:24 Rev Time 0.00
Received By dhayes Date 2015-07-01 Time 16:05 Sent To  
Notes
***NONE***