2015-07-29 16:49:27 | BUILDING PLAN REVIEW |
| PERMIT: 15061478 |
| ADD: 115 S OLIVE AVE |
| CONT: TO BE DETERMINED/ CONTACT SCOTT SMITH |
| TEL: (561)318-8821 |
| E-MAIL: ROXY'[email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 |
| ADMINISTRTION |
| |
| 1ST REVIEW |
| DATE: JULY 29/ 2015 |
| ACTION: DENIED |
| |
| 1A) PLANS SUBMITTED ON JUNE 30/ 2015 ARE TO BE DESIGNED |
| TO THE 5TH EDITION OF THE FLORIDA BUILDING CODE. THE |
| 5TH EDITION OF THE FBC WAS ADOPTED STATE WIDE JUNE 30/ |
| 2015. PLEASE UPDATE ALL CODE REFERENCES TO THE CURRENT |
| CODE. |
| |
| 1B) PLEASE SUBMIT 2014 ENERGY CALCULATIONS ALSO SEE |
| C103.2 INFORMATION ON CONSTRUCTION DOCUMENTS, C401.2 |
| APPLICATION & C401.1.2.1 APPLICATION TO EXISTING |
| BUILDINGS. |
| |
| 2) PLEASE SUBMIT A SURVEY TO ESTABLISH WHERE THE |
| PROPERTY LINE IS LOCATED IN REGAURDS TO THE BUILDING |
| LINE AND PROPOSED EXTERIOR WEST STAIR FROM THE 3RD |
| FLOOR AND THE EAST PROPERTY LINE THE EXTERIOR FOLDING |
| DOORS AND DOUBLE ENTRY DOORS APPEAR THEY SWING OVER THE |
| PROPERTY LINE. 2010 FBC-B 3202.2 |
| |
| 2A) PLEASE PROVIDE THE LOCATION OF THE PROPERTY LINE ON |
| THE ELEVATIONS SHEET A-10 TO REVIEW PLANS FOR CODE |
| COMPLIANCE WITH FBC-B 3202.2, 3202.3.2 , 1026.5 & |
| 1027.4 (1-2). |
| |
| 3) THIS BUILDING WILL REQUIRE A RESIDENT INSPESTOR, |
| 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION, 110.3.9 OTHER |
| INSPECTIONS SERVICES. THE BUILDING OFFICIAL MAY MAKE, |
| OR CAUSE TO BE MADE BY OTHERS, THE INSPECTIONS REQUIRED |
| BY SECTION 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS |
| OF RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER |
| INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR |
| QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED |
| FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT |
| BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING |
| AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE. |
| THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY |
| AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES: |
| 2. FOR ALL MAJOR STRUCTURAL ALTERATIONS |
| 6. FOR BUILDINGS MORE THAN 2 STORIES IN HEIGHT |
| |
| 3A) RESIDENT INSPECTOR FORMS MUST BE SIGNED BY ALL |
| PARTIES NOTARIZED AND RETURNED TO THE BUILDING |
| DEPARTMENT. FORMS WERE SENT TO SCOTT SMITH, E-MAIL |
| ADDRESS: ROXY'[email protected] 7/29/2015 04:12 PM. |
| RECEIVED A FAILURE TO ROUTE. |
| |
| 3B) FOR THE RESIDENT INSPECTOR PLEASE PROVIDE A RESUME' |
| OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE |
| RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| MEETING THE ABOVE CRITERIA. |
| CONTACT KEN CONRAD |
| TEL: 561-805-6666 |
| E-MAIL: [email protected] |
| |
| 3C) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR |
| HISTORY FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE |
| SUBMITTED TO KEN CONRAD BY E-MAIL. KEN CONRAD: |
| [email protected] |
| |
| 3D) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE |
| REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, THE |
| PERMIT LIBRARIAN WILL E-MAIL YOU, THE APPROVED AND |
| BATCH STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO |
| SETS OF PLANS WILL NEED TO BE PRINTED IN COLOR, (1) FOR |
| THE RESIDENT INSPECTOR, THE OTHER FOR THE MEP |
| INSPECTORS. |
| |
| 3E) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED |
| TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR |
| IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE |
| INSPECTIONS. |
| |
| 4) SHEET A-8 / BUILDING CODE ANALYSIS |
| |
| 4A) CONSTRUCTION TYPE IS LISTED AS BLDG TYPE: 3A- |
| UNSPRINKLERED / MAXIMUM BLDG HEIGHT: 55 FT + 20 FT=75 |
| FT. PER 504.2. |
| WITHIN THE ABOVE STATEMENT THERE ARE VARIOUS |
| DISCREPANCIES, FOR A TYPE 3A BUILDING YOU ARE ALLOWED |
| 65 FT. UNSPRINKLERED. FOR A 3A TYPE BUILDING STRUCTURAL |
| FRAMING MEMBERS WILL NEED TO BE FIRE RATED PER TABLE |
| 601. I BELIEVE THE DESIGNER IS LOOKING AT A 3B BUILDING |
| TYPE UNSPRINKLERED THE BUILDING ALLOWABLE HEIGTH OF 55 |
| FT. AND NO FIRE RESISTANT MEMBERS ARE REQUIRED. |
| |
| 4B) THE BUILDING CODE ANALYSIS INDICATES THE BUILDING |
| TO BE UNSPRINKLERED. PLEASE REVIEW THE 2014 FBC (5TH |
| EDITION OF THE FBC-B) SECTION 903.2.11.3 FIRE |
| SPRINKLERS REQUIRES ALL (3) STORY BUILDINGS TO BE FIRE |
| SPRINKLERED. |
| 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL |
| BUILDINGS : |
| FIRE SUPPRESSION SYSTEMS SHALL INCLUDE: |
| SCHEMATIC FIRE SPRINKLERS |
| STANDPIPES |
| |
| 4C) OCCUPANT LOADS: OCCUPANT LOADS FOR EGRESS WHEN YOU |
| END UP WITH A FRACTION, YOU ALWAYS ROUND UP TO THE NEXT |
| WHOLE OCCUPANT. SEE BOAF INFORMAL INTERPRETATION 5479. |
| 1ST FLOOR BENCH SEATING TO 29 OCCUPANTS/ TOTAL 153 |
| 2ND FLOOR KITCHEN 3/ TOTAL 171 |
| 3RD FLOOR CLARIFY THE SQUARE FOOTAGE IN KITCHEN IT |
| APPEARS THERE IS (2) AREAS 780 SQ. FT. +517 SQ. FT.= |
| 1297 SQ. FT./ 100= 13 OCCUPANTS |
| |
| 4D) INTERIOR FINISHES (COMMON TO ALL FLOORS) DOES NOT |
| MATCH THE A2 OCCUPANCY FOR SPRINKLERED OR |
| NON-SPRINKLERED BUILDINGS SEE 2014 FBC-B TABLE 803.9. |
| THERE ARE NO INTERIOR WALL ELEVATIONS WITH FINISHES |
| CONCERNS ARE 2014 FBC-B: |
| 4D)(1) 803.11.1 DIRECT ATTACHMENT & FURRED |
| |
| 4D)(2) 803.11.2 SET OUT CONSTRUCTION. |
| |
| 4D)(3) 803.4 USE OF FOAM PLASTICS |
| |
| 4D)(4) 803.5 TEXTILE WALL COVERINGS |
| |
| 4D)(5) 803.6 TEXTILE CEILING COVERINGS |
| |
| 4D)(6) DECROTIVE MATERIAL & TRIM |
| |
| 5) SHEET A-8: |
| |
| 5A) SHEET A-8 SHOWS A EXIT DIRECTIONAL SIGN IN THE 1ST |
| FLOOR DINING ROOM TAKING THE PATH OF EGRESS TRAVEL |
| THROUGH THE PRE-KITCHEN. THE 2014 FBC-B SECTION |
| 1014.2(4) EGRESS SHALL NOT PASS THROUGH KITCHENS. |
| |
| 5B) SHEET A-8 THE MAIN DINING ROOM, WITH THE PATH OF |
| EGRESS TRAVEL THROUGH THE KITCHEN NOT ALLOWED, THE |
| DINING ROOM WILL NEED A 2ND MEANS OF EGRESS SINCE THE |
| OCCUPANT LOAD IS GRATER THAN 49. 2014 FBC-B TABLE |
| 1015.1. |
| |
| 5C) SHEET A-8, THE MAIN DINING ROOM WILL ALSO NEED TO |
| SHOW COMPLIANCE WITH 2014 FBC-B 1028.10.1.2 SEATING AT |
| TABLE AISLE LENGTH. ACCESS AISLES SHALL NOT EXCEED 30 |
| FT. WHERE THE OCCUPANT HAS A CHOICE OF 2 OR MORE PATHS |
| OF EGRESS TRAVLE TO SEPARATE EXITS. |
| |
| 5D) SHEET A-8 SHOWS A ENCLOSED EXIT STAIR EMPTYING INTO |
| THE PRE-KITCHEN AS PART OF A MEANS OF EGRESS. THE 2014 |
| FBC-B SECTION 1014.2(4) EGRESS SHALL NOT PASS THROUGH |
| KITCHENS. |
| |
| 5E) SHEET A-8 SHOWS A PASSENGERE ELEVATOR, THE TRAVEL |
| DISTANCE FROM THE 1ST FLOOR TO THE 3RD FLOOR IS |
| APPROXIMATELY 26 FT. 3 IN. WITH THIS TRAAVEL DISTANCE |
| PLEASE SHOW COMPLIANCE WITH 2014 FBC-B 3002.4 ELEVATOR |
| CAR TO ACCOMMODATE AMBULANCE STRETHER. |
| |
| 5F) ARCHITECTURAL PLANS DO NOT SHOW ANY DETAILS OF THE |
| ELEVATOR HOISTWAY, THE STRUCTURAL SHEETS SHOW ON SHEET |
| S-3 DETAIL 14 ON SHEET S-13. THE STRUCTURAL PLANS ONLY |
| GO TO S-10 THERE IS NO SHEET S-13. 107.2.1.3 ADDITIONAL |
| INFORMATION IS REQUIRED FOR CODE COMPLIANCE. PLEASE |
| NOTE THE PLANS DO NOT SHOW A MACHINE ROOM. PLEASE |
| PROVIDE DOCUMENTATION OF THE TYPE OF ELEVATOR AND |
| EQUIPMENT TO BE INSTALLED. ALSO ON THE DUMBWAITER. |
| |
| 5G) SHEET A-8 IS THE 1ST FLOOR LIFE SAFETY PLAN,(COMMON |
| COMMENT FOR ALL 3 FLOORS!!!!!) NONE OF THE REQUIRED |
| RATED WALLS ARE SHOWN ON THIS PLAN, VERTICAL |
| STAIRWELLS,AND SHAFTS DO NOT INDICATE HOURS OF RATING |
| NEITHER DOES SHEET A-2. |
| |
| 5H) SHEET A-8 NOR A-2 (COMMON COMMENT FOR ALL FLOORS) |
| SHOW A WALL TYPE LEGEND FOR WALL TYPES RATED OR |
| NON-RATED WALLS, WALL IDENTIFICATION TAGS, NOR UL OR |
| GYPSUM WALL ASSEMBLIES. 2014 FLORIDA BUILDING CODE W |
| 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1 ADMINISTRTION: |
| 107.3.5 MINIMUM PLAN REVIEW FOR COMMERCIAL BUILDINGS |
| CRITERIA FOR BUILDINGS : |
| FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL INCLUDE |
| THE FOLLOWING COMPONENTS: |
| FIRE-RESISTANT SEPARATIONS |
| FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION |
| PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS |
| WALL SYSTEMS |
| FLOOR SYSTEMS |
| ROOF SYSTEMS |
| FIRE BLOCKING AND DRAFTSTOPPING AND CALCULATED FIRE |
| RESISTANCE |
| |
| 5I) SHEET A-8 NOR A-2 SHOW COMPLIANCE WITH 2014 FBC-B |
| 906.1 LOCATION FOR PORTABLE FIRE EXTINGUISHERS, THIS |
| COMMENT STAND FOR ALL FLOORS. |
| |
| 6) SHEET A9 LIFE SAFETY 2ND FLOOR AND SHEET A-3 : |
| |
| 6A)(1) SHEET A9 LIFE SAFETY 2ND FLOOR AND SHEET A-3 |
| SHOW (2) EXIT STAIRWAYS ENTRY POINTS WITHIN 12 FT. OF |
| EACH OTHER, FOR A FIRE SPRINKLERED BUILDING THEY HAVE |
| TO BE 1/3 THE MAXIMUM DIAGONAL DISTANCE APART FOR |
| EITHER THE BUILDING OR AREA SERVED 2014 FBC-B 1015.2.1. |
| |
| 6A)(2) THE WEST STAIRWELL THE DOOR SWING AGAINST THE |
| MEANS OF EGRESS TRAVEL, WITH A OCCUPANT LOAD GREATER |
| THAN 50. 2014 FBC-B 1008.1.2. |
| |
| 6B)(A) SHEET A9 LIFE SAFETY 2ND FLOOR AND SHEET A-3 THE |
| SOUTH EXTERIOR WALL SHOWS A NEW OPENING OF 250 SQ. FT. |
| SET BACK 3FT. 4 INCHES. TABLE 602 WALLS 0-5 FT. FROM |
| THE PROPERTY LINE FOR AN ASSEMBLY OCCUPANCY REQUIRE A 1 |
| HOUR FIRE RATED WALL. TABLE 708.5 FOR ALLOWABLE |
| OPENINGS BETWEEN 0-3 FEET FROM THE PROPERTY LINE NOT |
| PERMITTED. TABLE 708.5 MAXIMUM AREA OF EXTERIOR WALL |
| OPENINGS BASED ON FIRE SEPARATION DISTANCE AND DEGREE |
| OF OPENING PROTECTION, ONLY ALLOWS 15 % OF THE WALL TO |
| BE PROTECTED BY EITHER A FIRE DOOR OR FIRE SHUTTER. THE |
| (3) OPENINGS CONSTITUTES 77 % OF THE WALL IN OPENINGS. |
| |
| 6B((B) THE 2ND ISSUE WITH THE PROPOSED 250 SQUARE FOOT |
| OPENING IN THE SOUTH WALL IS COMPLYING WITH 2014 FBC-B |
| 706.6.1 STEPPED BUILDINGS. THE PROPOSED PLAN SHEET A-10 |
| SHOWS WHAT APPEARS TO BE THE ROOF PARAPET THE ACTUAL |
| ROOF LEVEL IS UNKNOWN. THIS UNKNOWN FACT MAY ALSO |
| AFFECT THE GLASS HANDRAILS ON THE 3RD LEVEL IN THIS |
| SAME AREA. PLEASE NOTE THE EXTERIOR WALL FOR A HEIGHT |
| OF 15 FEET ABOVE THE LOWER ROOF IS NOT LESS THAN 1-HOUR |
| FIRE RESISTANCE RATED CONSTRUCTION FROM BOTH SIDES WITH |
| OPENING PROTECTIVED BY FIRE ASSEMBLIES HAVING A FIRE |
| PROTECTION RATING OF NOT LESS THAN 3/4 HOUR. |
| |
| 6C) THE OPENINGS ON BOTH THE SOUTH AND EAST SIDE OF THE |
| BUILDING SHOW OVERHEAD TYPE GLAZED GARAGE DOORS (DOOR # |
| 203-208) WILL NEED TO COMPLY WITH 2014 FBC-B 2405.2 |
| SLOPED GLAZING. ALLOWABLE GLAZING MATERIALS AND |
| LIMITATIONS. |
| |
| 6D) THE 2ND FLOOR THE EAST STAIRWELL SHOWS A INSWING |
| EGRESS DOOR AT THE RATED VERTICAL EXIT. PLEASE PROVIDE |
| CODE COMPLIANCE WITH 2014 FBC-B 1008.1.6. |
| |
| 7) SHEETS A9 3RD FLOOR LIFE SAFETY PLAN AND SHEET A-4: |
| |
| 7A) SHEET A-4 ROOM # 306 IS LABELED MENS RESTROOM WHERE |
| AS A9 THE 3RD FLOOR PLAN SHOWS THIS AS A BEER COOLER |
| ROOM. DISCREPANCY IN PLANS. 107.2.1.3. |
| |
| 7B) SHEETS A9 3RD FLOOR LIFE SAFETY PLAN AND SHEET A-4 |
| THE MENS RESTROOM WILL NEED TO SHOW COMPLIANCE WITH |
| 2014 FBC-ACCESSIBLITY 404.2.6 DOORS IN SERIES. |
| |
| 8A) SHEET A-10 OR A-11 DO NOT PROVIDE THE DESIGN |
| CRITERIA FOR THE 42 INCH HIGH GLASS GUARD RAILS TO SHOW |
| CODE COMPLIANCE WITH FBC-B 1607.8, 2406.4.4 & 2607. |
| |
| 8B) SHEET A-11 THE EXTERIOR REAR STAIR DOES NOT SHOW |
| COMPLIANCE WITH RISE/ RUN OF STAIRS, HANDRAILS AND |
| GAURDRAILS IN COMPLIANCE WITH THE 2014 FBC-B 1013.3, |
| 1607.8, 1012.4, 1012.5 OR 1012.6. |
| |
| 9) SHEET A-11 SHOWS AN ALUMINUM SUSPENDED CANOPY, THERE |
| ARE NO CUT SECTIONS OR DETAILS FOR THIS CANOPY HOW IT |
| IS TO BE ANCHORED NOR IS THERE WIND DESIGN CRITERIA TO |
| BASE A DESIGN. 2014 FBC-B 3106. IS FOR FIXED CANOPIES |
| (MARQUEES), PLEASE NOTE THIS SECTION IS FOR FIXED |
| CANOPIES AND WILL NEED TO COMPLY WITH 3106.5 |
| CONSTRUCTION. |
| |
| 10) SHEET A-11 SHOWS ON THE WEST SIDE OF THE 3RD FLOOR |
| WHAT APPEARS TO BE ROOF TOP A/C COMPRESSORS, PLEASE BE |
| AWARE THEY WILL NEED TO BE ANCHORED TO EITHER ROOF TOP |
| CURBS IF THEY ARE DOWN TURNED UNITS, IF PACKAGED |
| COMPRESSORS THEY WILL NEED TO MEET THE REQUIREMENTS FOR |
| ROOF TOP A/C STANDS AND REQUIRED CLEAANCES 2014 FBC-B |
| TABLE 1509.6.5. |
| |
| 11) SHEET S-8 UNDER NOTES # 1 THE WIND DESIGN IS 140 |
| MPH. PLEASE UPDATE TO THE 2014 FBC-B WIND DESIGN MAP |
| FIGURE 1609A. |
| |
| 12) SHEET S-8 UNDER NOTES 2A INDICATE THIS PLAN IS |
| DESIGNED TO THE 2007 FBC-B. PLEASE NOTE JUNE 30/ 2015 |
| THE 2014 FBC. 5TH EDITION WAS ADOPTED STATE WIDE. |
| |
| 13) SHEET S-8 WIND LOAD SCHEDULE INDICATES THE DESIGN |
| IS TO THE 2010 FBC. PLEASE UPDATE PRESSURES TO THE 2014 |
| FBC-B PLEASE PROVIDE THE EXPOSURE AND MEAN ROOF HEIGHT |
| FOR THIS BUILDING. |
| |
| 2014 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- |
| CHAPTER 6 OF ASCE 7-10. |
| 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| 1609.3 WIND SPEED CONVERSION |
| 13.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| ACCORDANCE WITH 1609.3.1 & ASCE 7-10 |
| |
| 13.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10. |
| |
| 13.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| ACCORDANCE WITH 1609.4 & ASCE 7-10 |
| |
| 13.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. |
| |
| 13.5) COMPONENTS & CLADDING PRESSURES POSITIVE & |
| NEGATIVE TABLE 1609.2(2) . |
| |
| 14) SHEET S-8 WIND SCHEDULE WILL NEED TO PROVIDE |
| PRESSURES FOR BOTH A FLAT ROOF AND SLOPED ROOF. SLOPED |
| ROOF 4:12. COMPONENTS & CLADDING PRESSURES POSITIVE & |
| NEGATIVE TABLE 1609.2(2) . |
| |
| 15) SHEET S-6 DETAIL 1-A SHOWS THE INSTALATION OF 3/4 |
| INCH T & G DECKING WITH RAFTERS @ 24 INCHES ON CENTER. |
| 15A) NEITHER THE ARCHITECTURAL SHEETS NOR STRUCTURAL |
| SHEETS INDICATE WHAT TYPE OF FINISH ROOFING PRODUCT IS |
| TO BE INSTALLED ON THIS STRUCTURE. |
| FOR ROOF UNDERLAYMENTS THAT REQUIRE TIN TAGS THE |
| ROOFING NAILS ARE TO PENETRATE INTO THE ROOF DECKING A |
| MINIMUM OF 3/4 INCHES, MAY HAVE BLEMISHES ON THE |
| INTERIOR FINISH ROOF SHEATHING. 107.2.1.3 ADDITIONAL |
| INFORMATION IS REQUIRED. |
| |
| 15B) SHEET S-6 DETAIL # 1 WILL ALSO NEED TO INDICATE |
| THE WIDTH OF THE T & G ROOF DECKING AND THE QUANITY OF |
| NAILS PER BOARD TYPE OF FASTENER AND LENGTH OF FASTENER |
| FOR THE 3RD FLOOR ROOF SHEATHING. 107.2.1.3. |
| |
| 16) 2014 EXISTING BUILDING CODE 1103.3.1 VERTICAL |
| ADDITION. ANY ELEMENT OF THE LATERAL FORCE RESISTING |
| SYSTEM SUBJECT TO AN INCREASE IN VERTICAL OR LATERAL |
| LOADS FROM THE VERTICAL ADDITION SHALL COMPLY WITH THE |
| FLORIDA BUILDING CODE, BUILDING WIND PROVISIONS AND THE |
| FBC-LEVEL SEISMIC FORCES SPECIFIED IN 301.4.1 OF THIS |
| CODE. |
| |
| 17) PLEASE PROVIDE THE MINIMUM BEARING VALUE OF THE |
| SOILS AND HOW THE EXISITNG FOUNDATIONS WERE BUILT FOR |
| THE ADDITIONA LOADING OF THE 3RD FLOOR. 2014 FBC-B |
| 1803.5.2. QUSTIONABLE SOILS. |
| |
| 18) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| (B) WINDOWS |
| (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| LOUVERS, EFIS SYSTEMS, |
| (D) ROOFING PRODUCTS AND ASSEMBLIES |
| (E) SHUTTERS |
| (F) SKYLIGHTS |
| (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| STANDS |
| |
| 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS |
| SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR |
| DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE |
| REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING |
| OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED |
| SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE |
| IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING. |
| THE |
| DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL |
| THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY |
| THE BUILDING OFFICIAL. |
| |
| 19) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE |
| PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| |
| 20) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| 21) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |