Plan Review Details - Permit 15061472
Plan Review Stops For Permit 15061472
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-09-29 Cont ID  
Sent By jwitmer Date 2015-09-29 Time 11:29 Rev Time 0.00
Received By jwitmer Date 2015-09-29 Time 11:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-08-31 Cont ID  
Sent By jwitmer Date 2015-08-31 Time 14:17 Rev Time 0.00
Received By jwitmer Date 2015-08-31 Time 14:08 Sent To  
Notes
2015-08-31 14:10:03BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15061472
 ADD: 930 MALCOLM CHANDLER LN.
 CONT: KAST
 TEL: (561)346-4994
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W
 * 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION,
 2014 EXISTING BUILDING CODE LEVEL II 801.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. AUGUST 31/ 2015
 ACTION: DENIED
  
 1) 2ND REQUEST THIS UNIT HAS NOT BEEN ADDRESSED AS TO
 SUITE NUMBER NOR THE CORRECT BUILDING ADDRESS. THE
 PLANS INDICATE THE OLD 800 HANK AARRON DR. THE
 DEVELOPER HAS RENAMED THE STREETS WITHIN THE COMPLEX,
 BUILDING # 3'S ADDRESS IS 930 MALCOLM CHANDLER LN. THE
 SUITE NUMBER IS STILL UNKNOWN.
  
 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE,
 CHAPTER 1, ADMINISTRATION, 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK.
  
 2) 2ND REQUEST. THE DESIGNER OF RECORD HAS DECLARED
 THIS SUITE TO BE A LEVEL 2 ALTERATION. PLEASE NOTE THE
 PLANS WERE SUBMITTED JUNE 30/ 2015 THE FIRST DAY OF THE
 ADOPTED 2014 5TH EDITION OF THE FLORIDA BUILDING CODE
 AND EXISTING BUILDING CODE. PLEASE REFER TO THE 2014
 EXISTING BUILDING CODE CHAPTER 10 FOR CHANGE OF
 OCCUPANCY SECTION 1001.3.1 FOR BUILDINGS WITH A PARTIAL
 CHANGE OF OCCUPANCY. "BUSINESS OCCUPANCY".
  
 3) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-07-22 Cont ID  
Sent By jwitmer Date 2015-07-22 Time 11:47 Rev Time  
Received By jwitmer Date 2015-07-22 Time   Sent To  
Notes
2015-07-22 10:50:45BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15061472
 ADD: 930 MALCOLM CHANDLER LN.
 CONT: KAST
 TEL: (561)346-4994
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W
 * 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION,
 2014 EXISTING BUILDING CODE LEVEL II 801.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JULY 22/ 2015
 ACTION: DENIED
  
 1) THIS UNIT HAS NOT BEEN ADDRESSED AS TO SUITE NUMBER
 JUST THE BUILDING ADDRESS. 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, ADMINISTRATION, 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK.
  
 2) THE DESIGNER OF RECORD HAS NOT DECLARED TO WHAT
 PLANS THIS PROJECT IS BEING DESIGNED TO. PLEASE NOTE
 THE PLANS WERE SUBMITTED JUNE 30/ 2015 THE FIRST DAY OF
 THE ADOPTED 2014 5TH EDITION OF THE FLORIDA BUILDING
 CODE AND EXISTING BUILDING CODE. PLEASE REFER TO THE
 2014 EXISTING BUILDING CODE CHAPTER 10 FOR CHANGE OF
 OCCUPANCY SECTION 1001.3.1 FOR BUILDINGS WITH A PARTIAL
 CHANGE OF OCCUPANCY. "BUSINESS OCCUPANCY".
  
 3) SHEET A201 SHOWS A NEW MATER BATH DETAIL # 4/ A201.
 THIS DETAIL SHOWS THE EXTERIOR WALL OF THE RESTROOM
 WITH A 3'-6" GRAB BAR BUT IT APPEARS TO ONLY BE SECURED
 AT TWO POINTS, THERE IS WHAT APPEARS TO BE 1/2 OF THE
 GRAB BAR FLOATING IN MID-AIR. PLEASE SHOW COMPLIANCE
 WITH 2014 FBC-ACCESSIBILITY 609.8 ALLOWABLE STRESSES
 SHALL NOT BE EXCEEDED FOR MATERIALS USED WHEN A
 VERTICAL OR HORIZONTAL FORCE OF 250 POUNDS (1112 N) IS
 APPLIED AT ANY POINT ON THE GRAB BAR, FASTENER,
 MOUNTING DEVICE, OR SUPPORTING STRUCTURE.
  
 4) PLEASE REVIEW SHEET A201 OFFICE # 2, THE ENTRY DOOR
 INTO THE OFFICE DOES NOT HAVE THE 18 INCHES ON THE
 LATCH SIDE OF THE DOOR AS REQUIRED BY 2014
 FBC-ACESSIBLITY CODE 404.2.4 MANEUVERING CLEARANCES &
 TABLE 404.2.4.1.
  
 5) SHEET A201 IS NOW A OFFICE AND WILL NEED TO SHOW
 COMPLIANCE WITH 2014 FBC-ACCESSIBILITY CODE SECTION
 606.1-5.
  
 6) THIS UNIT IS NOW CONSIDERED A COMMERICIAL OR
 BUSINESS OFFICE. PLEASE REVIEW 2014 FBC-B 903.3
 EXCEPTION REQUIREMENT FOR EXHAUST HOODS PROTECTED WITH
 A FIRE-EXTINGUISHING SYSSTEM IN ACCORDANCE WITH SECTION
 904.
  
 7) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-10-13 Cont ID  
Sent By skennedy Date 2015-10-13 Time 11:35 Rev Time 0.00
Received By skennedy Date 2015-10-13 Time 11:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-08-03 Cont ID  
Sent By skennedy Date 2015-08-03 Time 13:24 Rev Time 0.00
Received By skennedy Date 2015-08-03 Time 13:24 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-09-16 Cont ID  
Sent By pleduc Date 2015-09-16 Time   Rev Time 0.00
Received By pleduc Date 2015-09-15 Time 14:45 Sent To  
Notes
2015-09-16 09:34:13THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF THE
 FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE AND
 COMPLIANCE. ANY REMOVAL AND/OR CONSTRUCTION OF WALLS
 REQUIRES AN EVALUATION.
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-07-07 Cont ID  
Sent By pleduc Date 2015-07-07 Time   Rev Time 0.00
Received By pleduc Date 2015-07-07 Time 14:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-10-13 Cont ID  
Sent By skennedy Date 2015-10-13 Time 11:35 Rev Time 0.00
Received By skennedy Date 2015-09-14 Time 14:59 Sent To  
Notes
2015-09-14 14:59:10B13

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-08-31 Cont ID  
Sent By jwitmer Date 2015-08-31 Time 14:17 Rev Time 0.00
Received By jwitmer Date 2015-08-12 Time 15:49 Sent To  
Notes
2015-08-12 15:49:54RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-08-03 Cont ID  
Sent By skennedy Date 2015-08-03 Time 13:24 Rev Time 0.00
Received By skennedy Date 2015-06-30 Time 15:38 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2015-09-29 Cont ID  
Sent By jwitmer Date 2015-09-29 Time 11:29 Rev Time 0.00
Received By jwitmer Date 2015-09-29 Time 11:28 Sent To  
Notes
2015-09-29 11:29:28IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2015-08-31 Cont ID  
Sent By jwitmer Date 2015-08-31 Time 14:17 Rev Time 0.00
Received By jwitmer Date 2015-08-31 Time 14:17 Sent To  
Notes
2015-08-31 14:17:00IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-07-22 Cont ID  
Sent By jwitmer Date 2015-07-22 Time 11:47 Rev Time 0.00
Received By jwitmer Date 2015-07-22 Time 11:47 Sent To  
Notes
2015-07-22 11:47:55BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2015-10-02 Cont ID  
Sent By tklarge Date 2015-10-02 Time 05:51 Rev Time 0.00
Received By tklarge Date 2015-10-02 Time 05:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-08-15 Cont ID  
Sent By tklarge Date 2015-08-15 Time 04:46 Rev Time 0.00
Received By tklarge Date 2015-08-15 Time 04:34 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-07-23 Cont ID  
Sent By tklarge Date 2015-07-23 Time 10:22 Rev Time 0.00
Received By tklarge Date 2015-07-23 Time 09:15 Sent To E
Notes
2015-07-23 10:13:151) THE LAVATORY SHALL COMPLY WITH 2014 FBC
 -ACCESSIBILITY SEC.606.1 THROUGH 606.5.
 2) THE LAVATORY SHAL HAVE KNEE AND TOE CLEARANCES PER
 THE 2014 FBC-ACCESSIBILITY SECS. 306.2 & 306.3.
 3) FLOORS, WALL BASES AND WALLS IN THE TOILET ROOM
 SHALL COMPLY W/2014 FBC SEC.1210.2.1 THROUGH 1210.2.2.
 4) SUBMIT THE SQUARE FOOTAGE OF THE UNIT. WPB AMEND. TO
 FBC SEC. 107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2015-10-02 Cont ID  
Sent By sgraham Date 2015-10-02 Time 14:20 Rev Time 0.00
Received By sgraham Date 2015-10-02 Time 14:20 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2015-07-13 Cont ID  
Sent By sgraham Date 2015-07-13 Time 14:52 Rev Time 0.00
Received By sgraham Date 2015-07-13 Time 14:52 Sent To  
Notes
***NONE***