Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-07-07 Cont ID  
Sent By albarran Date 2015-07-07 Time 19:46 Rev Time 0.00
Received By albarran Date 2015-07-07 Time 18:57 Sent To I
Notes
2015-07-07 19:39:27IMPORTANT NOTICE:
 THE DISTANCE FOR THIS SERVICE LATERAL IS NOT CLEARLY
 DEFINED AS PART OF THIS SUBMITTAL. THEREFORE BE ADVISED
 THAT FOR THE AMPERAGE OF 200 AMP USING 250KCMILS THWN-2
 AL, THE MAXIMUM DISTANCE IS 122? FOR A 2% MAXIMUM OF 2%
 VOLTAGE DROP.
 ALL TRENCHING SHALL REMAIN OPEN FOR INSPECTION UNLESS
 PRIOR ARRANGEMENTS ARE MADE W/INSPECTOR. NO SITE TUBES
 ALLOWED
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-07-07 Cont ID  
Sent By albarran Date 2015-07-07 Time 19:40 Rev Time 0.00
Received By albarran Date 2015-06-29 Time 17:04 Sent To  
Notes
2015-07-07 19:42:017/7/15 - PASSED ELECTRICAL REVIEW AS NOTED. CONTRACTOR
 NOTIFIED VIA EMAIL. SENT TO SMALL READY BIN "E". MA
2015-06-29 17:05:16ROUTED TO ELECT <5K/CC