Plan Review Stops For Permit 15061358 |
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2015-07-07 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2015-07-07 |
Time |
19:46 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2015-07-07 |
Time |
18:57 |
Sent To |
I |
|
Notes |
2015-07-07 19:39:27 | IMPORTANT NOTICE: | | THE DISTANCE FOR THIS SERVICE LATERAL IS NOT CLEARLY | | DEFINED AS PART OF THIS SUBMITTAL. THEREFORE BE ADVISED | | THAT FOR THE AMPERAGE OF 200 AMP USING 250KCMILS THWN-2 | | AL, THE MAXIMUM DISTANCE IS 122? FOR A 2% MAXIMUM OF 2% | | VOLTAGE DROP. | | ALL TRENCHING SHALL REMAIN OPEN FOR INSPECTION UNLESS | | PRIOR ARRANGEMENTS ARE MADE W/INSPECTOR. NO SITE TUBES | | ALLOWED | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2015-07-07 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2015-07-07 |
Time |
19:40 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2015-06-29 |
Time |
17:04 |
Sent To |
|
|
Notes |
2015-07-07 19:42:01 | 7/7/15 - PASSED ELECTRICAL REVIEW AS NOTED. CONTRACTOR | | NOTIFIED VIA EMAIL. SENT TO SMALL READY BIN "E". MA | 2015-06-29 17:05:16 | ROUTED TO ELECT <5K/CC |
|
|
|