Plan Review Details - Permit 15061278
Plan Review Stops For Permit 15061278
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2016-10-26 Cont ID  
Sent By jwitmer Date 2016-10-26 Time 16:46 Rev Time 0.00
Received By jwitmer Date 2016-10-26 Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-04-06 Cont ID  
Sent By jwitmer Date 2016-04-06 Time 08:07 Rev Time 0.00
Received By jwitmer Date 2016-04-06 Time 08:06 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-02-18 Cont ID  
Sent By jwitmer Date 2016-02-18 Time 12:55 Rev Time 0.00
Received By jwitmer Date 2016-02-18 Time 09:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-07-27 Cont ID  
Sent By jwitmer Date 2015-07-27 Time 11:41 Rev Time 0.00
Received By jwitmer Date 2015-07-27 Time 09:40 Sent To  
Notes
2015-07-27 11:41:26BUILDING PLAN REVIEW
 W. P. B. PERMIT:15061278
 ADD: 777 S. FLAGLER DR. FLOORS: 11TH & 12TH
 CONT: WOOLEMS INC.
 TEL: (561)835-0401
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JULY 27/ 2015
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION WILL NEED TO INCLUDE UNDER
 THE DESCRIPTION OF WORK THE 11TH FLOOR AS WELL AS THE
 12TH FLOOR. 107,2,1,3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 2) SHEET 008-A0.07 THE 11TH FLOOR AT GRID LINE F-H & 8
 THE SET OF HORIZONTAL SLIDING DOORS FROM THE ELEVATOR
 LOBBY TO RECEPTION AREA WILL NEED TO SHOW COMPLIANCE
 WITH: 2010 FBC-B 1008.1.4.3 PLEASE ALSO BE AWARE OF
 1008.1.10 PANIC HARDWARE FOR ASSEMBLY OCCUPANCIES. IF
 THIS DOOR IS TO HAVE ACCESS-CONTROLLED EGRESS THEN
 1008.1.4.4 WILL ALSO BE REQUIRED.
  
 3) SHEET 001-A1.03 FLOOR LEVEL 11 BREAKROOM 1113 THE
 BREAKROOM IS APPROXIMATELY 900 SQ. FT. WHICH WILL HAVE
 A OCCUPANT LOAD OF 50 OR GREATER. 2010 FBC-B TABLE
 1004.1.1 900 SQ. FT./ 15 = 60 OCCUPANTS. PLEASE SEE
 DOORS 1113A THEY SWING INTO THE ROOM. THE 2010 FBC-B
 SECTION 1008.1.2 REQUIRES DOORS TO SWING IN THE
 DIRECTION OF EGRESS TRAVEL WHENEVER THE OCCUPANT LOAD
 OF 50 OR MORE.
  
 4) SHEET 011-A1.03 PLEASE PROVIDE THE TOTAL SQ. FT. OF
 AREA FOR THE TENANT SPACE THIS FLOOR AND ALSO PROVIDE
 THE SQ. FOOTAGE FOR ROOMS 1113 THE BREAKROOM,
 CONFERENCE ROOM 1102 & CONFERENCE ROOM 1103 . IF THEY
 ARE OVER 10 % OF THE TENANT SPACE FLOOR AREA THIS WILL
 BE CONSIDERED A MIXED OCCUPANCY FLOOR. THE DESIGNER OF
 RECORD WILL NEED TO DECLARE THEN IF IT IS A SEPERATED
 OCCUPANCY OR NON-SEPARATED OCCUPNCY. SEE FBC-B 508.2.4
 VERSES 508.3.
  
 5) SHEET 011-A1.03 BOTH 2 HR RATED EXITS FAIL TO SHOW
 THE 1 1/2 HR. FIRE RATED DOOR ON THE EXIT ENCLOSURE.
 2010 FBC-B TABLE 715.4.
  
 6) SHEET 011-A1.03 SHOWS A SPIRAL STAIR FROM THE 11TH
 FLOOR TO THE 12TH FLOOR. PLEASE PROVIDE A CUT SECTION
 THROUGH THIS AREA PROVIDING DETAILS WITH 2010 FBC-B
 708.2 EXCEPTION 2.1 THE REQUIRED DRAFT CURTAIN AND
 CLOSELY SPACED FIRE SPRINKLERS.
  
 7) SHEET 011-A1.03 PLEASE PROVIDE SPECIFICATIONS FOR
 THE SPIRAL STAIRCASE SIZE OF STAIRS, HEIGHT OF STAIRS,
 HANRAIL AND GAURD-RAIL REQUIREMENTS.
 2010 FBC-B 1009.9, 1012 & 1013.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
 6)
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2016-07-12 Cont ID  
Sent By albarran Date 2016-07-12 Time 11:10 Rev Time 0.00
Received By albarran Date 2016-07-12 Time 11:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2016-04-12 Cont ID  
Sent By albarran Date 2016-04-12 Time 20:16 Rev Time 0.00
Received By albarran Date 2016-04-04 Time 18:47 Sent To  
Notes
2016-04-12 20:18:19I AM WILLING TO ISSUE A PROVISO FOR THE ONLY ITEMS I
 SEE LACKING WHICH IS THE CONFERENCE ROOM D-F/13-10 IS
 MISSING EMERGENCY AND EXIT LIGHTING.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-02-29 Cont ID  
Sent By albarran Date 2016-02-29 Time 15:52 Rev Time 0.00
Received By albarran Date 2016-02-29 Time 13:05 Sent To  
Notes
2016-02-29 16:03:15SEE ATTACHED
 2ND ELECTRICAL REVIEW NOTES FOR REVISION #:15061278
 REVIEWED FOR COMPLIANCE WITH:
 FBC 2010 EDITION
 NFPA 70 2008 (NEC)
  
 CORRECTIONS REQUIRED:
 SHEET E1.01
 1. NOW THAT THE SHEET IS EASIER TO READ AND INTERPRET I
 FIND THE NEED FOR ADDITIONAL EMERGENCY ILLUMINATION IN
 THE VESTIBULE IN THE MEN?S AND WOMEN?S LOCKER ROOM.
 2. IN THE SAME AREA A DIRECTIONAL EXIT LIGHT IS MISSING
 POINTING TOWARDS THE DOORWAY.
 3. EXIT LIGHT REQUIRED AT THE MEN?S & WOMEN?S RESTROOM.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-07-06 Cont ID  
Sent By albarran Date 2015-07-06 Time 20:27 Rev Time 0.00
Received By albarran Date 2015-07-06 Time 19:06 Sent To  
Notes
2015-07-06 20:28:13PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER WAS UNABLE TO COMPLETE THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE CORRECTIONS NOTED.
  
 THE FOLLOWING ITEMS SHALL BE CORRECTED AND THE PLANS
 RESUBMITTED FOR A SECOND REVIEW:
  
 1. SEPARATE PERMIT REQUIRED FOR FIRE ALARM
 INSTALLATION. THEREFORE DO NOT INCLUDE THE FIRE ALARM
 DEVICES ON THIS SHEET.
 2. THESE PAGES ARE TOO CLUTTERED TO PROPERLY IDENTIFY
 THE DIFFERENT ROOMS. PROVIDE A SEPARATE SHEET FOR THE
 REFLECTED CEILING.
 3. EMERGENCY STAIRS NEED TO BE IDENTIFIED TO ASCERTAIN
 PROPER LOCATION OF EXIT LIGHTING.
 4. EMERGENCY LIGHTING IS NOT CLEARLY INDICATED
 ACCORDING TO THE LEGEND.
 5. IN THE 12TH FLR. INDICATE THE AREA DIRECTLY ADJACENT
 TO YOUR SCOPE OF WORK WITH RESPECT TO THE EXITS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2016-02-24 Cont ID  
Sent By pleduc Date 2016-02-24 Time   Rev Time 0.00
Received By pleduc Date 2016-02-24 Time 10:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2015-08-12 Cont ID  
Sent By wjolin Date 2015-08-12 Time 12:51 Rev Time 0.00
Received By wjolin Date 2015-08-12 Time 12:26 Sent To  
Notes
2015-08-12 12:51:18777 SOUTH FLAGLER DRIVE - 11TH/12TH FLOOR
 PERMIT #15061278
 REFER TO THE FOLLOWING PERMITS TO FULLY UNDERSTAND THE
 DESIGN:
 PERMIT #15061278 (11TH - 12TH FLOORS)
 PERMIT #15071149 (12TH, 14TH, 15TH FLOORS; NOTE NO 13TH
 FLOOR)
 MASTER #14060196
  
 REVIEW COMMENTS - FIRE DEPARTMENT
  
  
 THE CIRCULAR MONUMENTAL STAIR HAS BEEN REDESIGNED TO
 SERVE THREE FLOORS (11TH, 12TH & 14TH FLOOR - NO 13TH
 FLOOR); THEREFORE, THE OPEN STAIR DESIGN WILL NEED TO
 COMPLY WITH NFPA 101 SECTION 8.6 "VERTICAL OPENINGS" AS
 AN "ATRIUM" (SECTION 8.6.7). NOTE: THE OPEN STAIR WAS
 PREVIOUSLY DESIGNED AND PERMITTED AS A 2-STORY
 "CONVENIENCE OPENING."
  
 SECTION 8.6.7
 (1) THE ATRIUM IS SEPARATED FROM THE ADJACENT SPACES BY
 FIRE BARRIERS WITH NOT LESS THAN A 1-HOUR FIRE
 RESISTANCE RATING, WITH OPENING PROTECTIVES FOR
 CORRIDOR WALLS, UNLESS ONE OF THE FOLLOWING IS MET:
 (A) THE REQUIREMENT OF 8.6.7(1) SHALL NOT APPLY TO
 EXISTING, PREVIOUSLY APPROVED ATRIUMS.
 (B) ANY NUMBER OF LEVELS OF THE BUILDING SHALL BE
 PERMITTED TO OPEN DIRECTLY TO THE ATRIUM WITHOUT
 ENCLOSURE, BASED ON THE RESULTS OF THE ENGINEERING
 ANALYSIS REQUIRED IN 8.6.7(5).
 (C) GLASS WALLS AND INOPERABLE WINDOWS SHALL BE
 PERMITTED IN LIEU OF THE FIRE BARRIERS WHERE ALL THE
 FOLLOWING ARE MET:
 I. AUTOMATIC SPRINKLERS ARE SPACED ALONG BOTH SIDES OF
 THE GLASS WALL AND THE INOPERABLE WINDOWS AT INTERVALS
 NOT TO EXCEED 6 FT (1830 MM).
 II. THE AUTOMATIC SPRINKLERS SPECIFIED IN
 8.6.7(1)(C)(I) ARE LOCATED AT A DISTANCE FROM THE GLASS
 WALL NOT TO EXCEED 12 IN. (305 MM) AND ARRANGED SO THAT
 THE ENTIRE SURFACE OF THE GLASS IS WET UPON OPERATION
 OF THE SPRINKLERS.
 III. THE GLASS WALL IS OF TEMPERED, WIRED, OR LAMINATED
 GLASS HELD IN PLACE BY A GASKET SYSTEM THAT ALLOWS THE
 GLASS FRAMING SYSTEM TO DEFLECT WITHOUT BREAKING
 (LOADING) THE GLASS BEFORE THE SPRINKLERS OPERATE.
 IV. THE AUTOMATIC SPRINKLERS REQUIRED BY 8.6.7(1)(C)(I)
 ARE NOT REQUIRED ON THE ATRIUM SIDE OF THE GLASS WALL
 AND THE INOPERABLE WINDOW WHERE THERE IS NO WALKWAY OR
 OTHER FLOOR AREA ON THE ATRIUM SIDE ABOVE THE MAIN
 FLOOR LEVEL.
 V. DOORS IN THE GLASS WALLS ARE OF GLASS OR OTHER
 MATERIAL THAT RESISTS THE PASSAGE OF SMOKE.
 VI. DOORS IN THE GLASS WALLS ARE SELF-CLOSING OR
 AUTOMATIC-CLOSING UPON DETECTION OF SMOKE.
 VII. THE GLASS IS CONTINUOUS VERTICALLY, WITHOUT
 HORIZONTAL MULLIONS, WINDOW TREATMENTS, OR OTHER
 OBSTRUCTIONS THAT WOULD INTERFERE WITH THE WETTING OF
 THE ENTIRE GLASS SURFACE.
 (2) ACCESS TO EXITS IS PERMITTED TO BE WITHIN THE
 ATRIUM, AND EXIT DISCHARGE IN ACCORDANCE WITH 7.7.2 IS
 PERMITTED TO BE WITHIN THE ATRIUM.
 (3) THE OCCUPANCY WITHIN THE ATRIUM MEETS THE
 SPECIFICATIONS FOR CLASSIFICATION AS LOW OR ORDINARY
 HAZARD CONTENTS. (SEE 6.2.2.)
 (4) THE ENTIRE BUILDING IS PROTECTED THROUGHOUT BY AN
 APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH SECTION 9.7.
 (5) AN ENGINEERING ANALYSIS IS PERFORMED THAT
 DEMONSTRATES THAT THE BUILDING IS DESIGNED TO KEEP THE
 SMOKE LAYER INTERFACE ABOVE THE HIGHEST UNPROTECTED
 OPENING TO ADJOINING SPACES, OR 6 FT (1830 MM) ABOVE
 THE HIGHEST FLOOR LEVEL OF EXIT ACCESS OPEN TO THE
 ATRIUM, FOR A PERIOD EQUAL TO 1.5 TIMES THE CALCULATED
 EGRESS TIME OR 20 MINUTES, WHICHEVER IS GREATER.
 (6) WHERE AN ENGINEERED SMOKE CONTROL SYSTEM IS
 INSTALLED TO MEET THE REQUIREMENTS OF 8.6.7(5), THE
 SYSTEM IS INDEPENDENTLY ACTIVATED BY EACH OF THE
 FOLLOWING:
 (A) REQUIRED AUTOMATIC SPRINKLER SYSTEM
 (B) MANUAL CONTROLS
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-07-06 Cont ID  
Sent By scaldero Date 2015-07-06 Time 16:11 Rev Time 0.00
Received By scaldero Date 2015-07-06 Time 16:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2016-11-02 Cont ID  
Sent By cpuell Date 2016-11-02 Time 16:22 Rev Time 0.00
Received By cpuell Date 2016-10-18 Time 13:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-08-15 Cont ID  
Sent By lmarchan Date 2016-08-15 Time 07:46 Rev Time 0.00
Received By lmarchan Date 2016-06-22 Time 08:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-04-19 Cont ID  
Sent By lmarchan Date 2016-04-19 Time 10:27 Rev Time 0.00
Received By lmarchan Date 2016-04-01 Time 14:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-02-29 Cont ID  
Sent By lmarchan Date 2016-02-29 Time 16:12 Rev Time 0.00
Received By lmarchan Date 2016-02-10 Time 15:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-07-27 Cont ID  
Sent By jwitmer Date 2015-07-27 Time 11:41 Rev Time 0.00
Received By jwitmer Date 2015-06-30 Time 15:01 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2016-04-05 Cont ID  
Sent By ccole Date 2016-04-05 Time 16:49 Rev Time 0.00
Received By ccole Date 2016-04-05 Time 16:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-02-25 Cont ID  
Sent By ccole Date 2016-02-25 Time 15:31 Rev Time 0.00
Received By ccole Date 2016-02-25 Time 15:31 Sent To  
Notes
2016-02-25 15:52:452ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #15061278
 2/25/16
  
 1) 2ND REQUEST FOR AC COOLING AND HEATING CALCULATIONS
 FOR THE NEW AHU/CU 11-20.
 2) SHEET M4.01: THE VENTILATION CALCULATIONS FOR THE
 LAUNDRY ROOMS IS NOT IN COMPLIANCE WITH TABLE 403.3.
 PLEASE REVIEW THE TABLE AND REVISE THE CALCULATIONS
 ACCORDINGLY.
 3) THE RESPONSE NARRATIVE FROM RGD CONSUILTING
 ENGINEERS IS INDICATING THAT THE SCOPE OF WORK FOR THE
 12TH FLOOR "HAS BEEN REMOVED FROM THE PROJECT", HOWEVER
 THE 12TH FLOOR PLAN SHEETS ARE STILL INCLUDED IN THE
 PLAN SETS. PLEASE CONTACT PLAN REVIEW LIBRARIAN
 CAROLINE PUELL OR LAURA MARCHANT AND HAVE ALL 12TH
 FLOOR PLAN SHEETS REMOVED.
 4) M2.02: THE EXHAUST GRILL IN THE WOMEN'S TOILET ROOM
 IS MISLABELED AS A SUPPLY DIFFUSER.
 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE DRYERS
 WITH AN APPROVAL SIGNATURE FROM THE ENGINEER OF RECORD.
 6) SUBMIT TWO COPIES OF THE NOA FOR THE ROOF STAND WITH
 AN APPROVAL SIGNATURE FROM THE ENGINEER OF RECORD.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-07-14 Cont ID  
Sent By ccole Date 2015-07-14 Time 13:48 Rev Time 0.00
Received By ccole Date 2015-07-14 Time 12:45 Sent To  
Notes
2015-07-14 14:33:521ST REVIEW: FBC 2010 MECHANICAL
 PERMIT #15061278
 7/14/15
  
 1) PROVIDE COOLING AND HEATING LOAD CALCULATIONS FOR
 THE NEW AHU/CU 11-20 SYSTEM IN ACCORDANCE WITH ACCA
 MANUAL N OR THE ACCA/ASHRAE STANDARD 183- REFERENCE
 SECTION 503.2.1 FBC-10 ENERGY CONSERVATION.
 2) IN ACCORDANCE WITH SECTION 709.1 FBC-10 EXISTING
 BUILDING, PROVIDE MINIMUM VENTILATION CALCULATIONS FOR
 THE RECONGFIGURED ROOMS AND SPACES ON THE 11TH AND 12TH
 FLOORS- REFERENCE TABLE 403.3 FBC-10 MECHANICAL.
 PROVIDE A SCHEDULE ON THE PLAN INDICATING THE MINIMUM
 REQUIRED CFM'S OF O/A OR EXHAUST, AND THE CFM'S
 PROVIDED. REFERENCE SECTIONS 503.4.5.1 AND 503.4.5.2
 FBC-10 ENERGY CONSERVATION, AND ADD NOTES ON SHEET M6.1
 TO INDICATE VAV TERMINAL DEVICE COMPLIANCES REGARDING
 O/A.
 3) NEW FIRE DAMPERS ARE SHOWN ON THE PLANS: PROVIDE AN
 EQUIPMENT SCHEDULE ON THE PLAN LISTING THE MAKES AND
 MODELS, FIRE-RESISTANCE RATINGS, AND HOW THEY WILL BE
 ACTUATED- PROVIDE A SEQUENCE OF OPERATION, AND CLARIFY
 IF ANY OTHER ALTERATIONS TO THE SMOKE CONTROL SYSTEM
 ARE PROPOSED.
 4) THE 12TH FLOOR PLAN LAYOUT ON THE ARCHITECTURAL
 DEMOLITION SHEET (A1.02) DOES NOT MATCH THE LAYOUT
 SHOWN ON THE MECHANICAL DEMO SHEET (M2.0).
 5) SHEET M2.02: EXHAUST VENTILATION FOR THE TOILET
 ROOMS IS REQUIRED. PLEASE PROVIDE THE DETAILS, EXHAUST
 DUCT RUNS, AND EXHAUST FAN SCHEDULES ON THE PLANS-
 TABLE 403.3 FBC-10 MECHANICAL.
 6) M2.04: EXHAUST VENTILATION FOR THE LOCKER/TOILET
 ROOMS IS REQUIRED. PROVIDE THE DETAILS, DUCT RUNS, AND
 FAN SCHEDULES ON THE PLAN.
 7) M2.02 & M2.04 PROVIDE MAKE-UP AIR FOR THE DRYERS-
 REFERENCE SECTION 504.5 FBC-10 MECHANICAL. NOTE THERE
 IS A DUCT DROP SHOWN AT THE FRONT OF THE 12TH FLOOR
 DRYER CLOSET, HOWEVER DOOR 1117 ENCLOSING THE CLOSET IS
 NOT LISTED AS A LOUVERED DOOR ON THE SCHEDULE ON SHEET
 A6.01. PROVIDE THE TOTAL LENGTHS OF THE DRYER EXHAUST
 DUCT RUNS IN COMPLIANCE WITH SECTION 504.6.4, AND
 SUBMIT PRODUCT DATA CUTSHEETS FOR THE APPLIANCES.
 8) M5.02: THE DESIGN PROFESSIONAL OF RECORD SHALL
 CERTIFY THAT THE CU WILL BE INSTALLED TO WITHSTAND 170
 MPH WIND LOADS AND PRESSURES- REFERENCE 301.12 FBC-10
 MECHANICAL. PROVIDE NOTES ON THE PLAN INDICATING
 COMPLIANCE.
  

Review Stop P PLUMBING
Rev No 5 Status P Date 2016-11-02 Cont ID  
Sent By gjohnson Date 2016-11-02 Time 16:04 Rev Time 0.00
Received By gjohnson Date 2016-11-02 Time 16:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2016-08-14 Cont ID  
Sent By tklarge Date 2016-08-14 Time 04:42 Rev Time 0.00
Received By tklarge Date 2016-08-14 Time 04:06 Sent To  
Notes
2016-08-14 04:21:311) SINCE THIS IS THE THIRD TIME THE PLANS HAVE BEEN
 REJECTED FOR THE SAME COMMENT REGARDING THE DRINKING
 FOUNTAIN, THE NEXT PLAN REVIEW SUBMITTAL IS SUBJECT TO
 BEING CHARGED 4 TIMES THE PLAN REVIEW FEE IN ACCORDANCE
 WITH FL. STATUTE 553.80.
 2) DRINKING FOUNTAINS ARE REQUIRED IN THE 11TH FLOOR
 SPACE PER 2010 FL. PLUMBING CODE TABLE 403.1. A MINIMUM
 OF 2 DRINKING FOUNTAINS ARE REQD. PER SEC. 211.2 OF THE
 2010 FAC AND FPC TABLE 403.1 FOOTNOTE (E). 3RD REQUEST.
 THE RESPONSE REGARDING ACCESS TO DRINKING WATER IN THE
 BREAK ROOM AND BUSINESS CENTER DOES NOT COMPLY WITH THE
 CODES. THE DRINKING FOUNTAIN FIXTURE IS REQUIRED IN THE
 NUMBER MANDATED BY THE CODE SECTIONS. SUBMIT REVISED
 SANITARY AND WATER RISERS THAT SHOW THESE FIXTURES.
 3) GRAB BARS IN THE ACCESSIBLE SHOWERS SHALL COMPLY
 WITH THE 2010 FAC SEC.609. SHT. SK 1.0 SHOWS THE GRAB
 BARS MEASURED TO THE CENTERLINE OF THE BAR. GRAB BARS
 SHALL BE MEASURED TO THE TOP OF THE GRIPPING SURFACE
 FROM THE FINISH FLOOR IN ACCORDANCE WITH THE 2010 FAC
 SEC. 609.
 4) SHT. SK 1.0 SHALL BEAR THE DIGITAL SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL OF RECORD IN ACCORDANCE
 WITH THE F.A.C. RULE 61G1-16.001, 61G1-16.005. THIS WAS
 OVERLOOKED IN THE PREVIOUS REVIEW.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805 PLUMBING PLAN REVIEW
 -6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2016-04-19 Cont ID  
Sent By tklarge Date 2016-04-19 Time 10:25 Rev Time 0.00
Received By tklarge Date 2016-04-19 Time 05:29 Sent To  
Notes
2016-04-19 09:21:501) DRINKING FOUNTAINS ARE REQUIRED IN THE 11TH FLOOR
 SPACE PER 2010 FL. PLUMBING CODE TABLE 403.1. A MINIMUM
 OF 2 DRINKING FOUNTAINS ARE REQD. PER SEC. 211.2 OF THE
 2010 FAC AND FPC TABLE 403.1 FOOTNOTE (E). 2ND REQUEST.
 THE RESPONSE REGARDING ACCESS TO DRINKING WATER IN THE
 BREAK ROOM AND BUSINESS CENTER DOES NOT COMPLY WITH THE
 CODES. THE DRINKING FOUNTAIN FIXTURE IS REQUIRED IN THE
 NUMBER MANDATED BY THE CODE SECTIONS. SUBMIT REVISED
 SANITARY AND WATER RISERS THAT SHOW THESE FIXTURES.
 2) TOILET ROOM #1152 - THE DOOR SWINGS INTO THE CLEAR
 FLOOR SPACE FOR THE LAVATORY. DOORS SHALL NOT SWING
 INTO THE CLEAR FLOOR SPACE FOR THE LAVATORY PER THE
 2010 FBC-ACCESSIBILITY SEC.603.2.3.( SEE EXCEPTION
 #2).2ND REQUEST.
 3) SHOW THE INSIDE CLEAR LENGTH AND WIDTH OF THE
 SHOWERS ON SHEET SK-1.0. COMPLY WITH SEC. 417.4 OF 2010
 FPC AND SEC. 608 OF THE 2010 FAC.
 4) THE SHOWER CONTROLS SHALL COMPLY WITH THE 2010 FAC
 SEC.608.5. SUBMIT DETAILS.FBC 107.1.
 5) GRAB BARS IN THE ACCESSIBLE SHOWERS SHALL COMPLY
 WITH THE 2010 FAC SEC.609. PROVIDE DETAILS. CLEARLY
 INDICATE THE ACCESSIBLE SHOWER ON THE PLANS OR ARE THEY
 ALL ACCESSIBLE? CLARIFY.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-02-20 Cont ID  
Sent By tklarge Date 2016-02-20 Time 06:00 Rev Time 0.00
Received By tklarge Date 2016-02-20 Time 04:43 Sent To  
Notes
2016-02-20 05:34:231) THE RESPONSE NARRATIVE STATES THAT THE 12TH FLOOR
 HAS BEEN REMOVED FROM THE SCOPE OF WORK BUT THERE ARE
 STILL PLANS FOR THE 12TH FLOOR BUILDOUT INCLUDED IN
 THIS SUBMITTAL. CLARIFY.
 2) SHT.005-A0.4 - MOUNTING HEIGHTS- THE HEIGHT OF THE
 GRAB BARS SHALL BE MEASURED FROM THE FINISH FLOOR TO
 THE TOP OF THE GRIPPING SURFACE PER THE 2010
 FBC-ACCESSIBILITY SEC. 609.4.
 3) SUBMIT THE OCCUPANT LOAD FOR THE 11TH LEVEL IN
 ACCCORDANCE WITH 2010 FBC-BUILDING, TABLE 1004.1.1.
 4) WASHING MACHINES AND CLOTHES DRYERS SHALL COMPLY
 WITH THE 2010 FBC-ACCESSIBILITY, SECS.611.1 THROUGH
 611.4. A CLEAR FLOOR SPACE POSITIONED FOR A PARALLEL
 APPROACH SHALL BE PROVIDED. THE CLEAR FLOOR SPACE SHALL
 BE CENTERED ON THE APPLIANCE.
 5) BREAK ROOM SINKS AND SINKS IN THE BUSINESS CENTER
 ROOMS SHALL COMPLY WITH 2010 FBC-ACCESSIBILITY
 SECS.212.1, 606.
 6) SUBMIT ENLARGED TOILET ROOM PLANS SHOWING THE INSIDE
 CLEAR DIMENSIONS OF THE TOILET ROOMS. IF THE WATER
 CLOSET AND LAVATORY ARE LOCATED ON THE SAME WALL THE
 MINIMUM WIDTH SHALL BE 85 INCHES IF BUILT PERFECT. 86
 INCHES ALLOWS FOR TOLERANCES.
 7) SHOW THE INSIDE CLEAR DIMENSIONS OF THE SHOWERS &
 TOILET COMPARTMENTSL ON SHT.012 A1.03. COMPLY WITH 2010
 FBC-ACCESSIBILITY & PLUMBING VOLUMES.
 8) 2010 FBC -ACCESSIBILITY SEC.213.3.1 - WHERE TOILET
 COMPARTMENTS ARE PROVIDED, AT LEAST ONE SHALL COMPLY
 WITH SEC.604.8.1.
 9) WHERE LAVATORIES ARE PROVIDED AT LEAST ONEE SHALL
 COMPLY W/FBC-ACCESSIBILITY SEC.606, 213.3.4.
 10) DRINKING FOUNTAINS ARE REQUIRED IN THE 11TH FLOOR
 SPACE PER 2010 FL. PLUMBING CODE. A MINIMUM OF 2
 DRINKING FOUNTAINS ARE REQD. PER SEC. 211.2 OF THE 2010
 FAC.
 11) TOILET ROOM #1152 - THE DOOR SHALL NOT SWING INTO
 THE CLEAR FLOOR SPACE FOR THE LAVATORY PER THE 2010
 FBC-ACCESSIBILITY SEC.603.2.3.
 12) CLEANOUTS ARE REQUIRED IN STACKS PER 2010 FPC
 SEC.708.3.4.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-07-25 Cont ID  
Sent By tklarge Date 2015-07-25 Time 09:44 Rev Time 0.00
Received By tklarge Date 2015-07-25 Time 06:07 Sent To  
Notes
2015-07-25 09:44:021) SHT.005-A0.4 - MOUNTING HEIGHTS- THE HEIGHT OF THE
 GRAB BARS SHALL BE MEASURED FROM THE FINISH FLOOR TO
 THE TOP OF THE GRIPPING SURFACE PER THE 2010
 FBC-ACCESSIBILITY SEC. 609.4.
 2) SUBMIT THE OCCUPANT LOAD FOR EACH LEVEL IN
 ACCCORDANCE WITH 2010 FBC-BUILDING, TABLE 1004.1.1.
 3) WASHING MACHINES AND CLOTHES DRYERS SHALL COMPLY
 WITH THE 2010 FBC-ACCESSIBILITY, SECS.611.1 THROUGH
 611.4. A CLEAR FLOOR SPACE POSITIONED FOR A PARALLEL
 APPROACH SHALL BE PROVIDED. THE CLEAR FLOOR SPACE SHALL
 BE CENTERED ON THE APPLIANCE.
 4) BREAK ROOM SINKS AND SINKS IN THE BUSINESS CENTER
 ROOMS SHALL COMPLY WITH 2010 FBC-ACCESSIBILITY
 SECS.212.1, 606.
 5) SUBMIT ENLARGED TOILET ROOM PLANS SHOWING THE INSIDE
 CLEAR DIMENSIONS OF THE TOILET ROOMS. IF THE WATER
 CLOSET AND LAVATORY ARE LOCATED ON THE SAME WALL THE
 MINIMUM WIDTH SHALL BE 85 INCHES IF BUILT PERFECT. 86
 INCHES ALLOWS FOR TOLERANCES.
 6) SHT.012A1.04 - ROOMS 1212 & 1213 - A CLEARANCE OF 36
 INCHES WIDE MINIMUM BY 48 INCHES LONG MINIMUM MEASURED
 FROM THE CONTROL WALL SHALL BE PROVIDED PARALLEL TO THE
 SHOWER ENTRANCES PER THE 2010 FBC-ACCESSIBILITY,
 SEC.608.2.1. THE PLANS DO NOT SHOW THE CLEARANCE.
 7) SHOW THE INSIDE CLEAR DIMENSIONS OF THE SHOWERS,
 TOILET COMPARTMENTS, & URINAL STALL ON SHT.012 A1.04.
 COMPLY WITH 2010 FBC-ACCESSIBILITY & PLUMBING VOLUMES.
 8) 2010 FBC -ACCESSIBILITY SEC.213.3.1 - WHERE TOILET
 COMPARTMENTS ARE PROVIDED, AT LEAST ONE SHALL COMPLY
 WITH SEC.604.8.1.
 9) WHERE LAVATORIES ARE PROVIDED AT LEAST ONEE SHALL
 COMPLY W/FBC-ACCESSIBILITY SEC.606, 213.3.4.
 10) DRINKING FOUNTAINS ARE REQUIRED IN THE 11TH AND
 12TH FLOOR SPACES PER 2010 FL. PLUMBING CODE. A MINIMUM
 OF 2 DRINKING FOUNTAINS ARE REQD. ON EACH FLOOR PER
 SEC. 211.2 OF THE 2010 FAC.
 11) TOILET ROOM #1152 - THE DOOR SHALL NOT SWING INTO
 THE CLEAR FLOOR SPACE FOR THE LAVATORY PER THE 2010
 FBC-ACCESSIBILITY SEC.603.2.3.
 12) SHTS.070 P5.11 & 071 P5.12 - THE STACKS FOR THE
 WASHING MACHINES SHALL BE A MINIMUM OF 3" PER THE 2010
 FPC SEC.406.3.
 13) BRANCH VENTS EXCEEDING 40 FEET IN DEVELOPED LENGTH
 SHALL BE INCREASED ONE PIPE SIZE FOR THE ENTIRE
 DEVELOPED LENGTH OF THE VENT PIPE PER 2010 FPC
 SEC.916.4.1.(SEE VENTS FOR TOILET ROOMS IN LOCKERS ON
 LEVEL 12).
 14) CLEANOUTS ARE REQUIRED IN STACKS PER 2010 FPC
 SEC.708.3.4.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2016-11-28 Cont ID  
Sent By jwitmer Date 2016-11-28 Time 08:13 Rev Time 0.00
Received By jwitmer Date 2016-11-22 Time 12:36 Sent To  
Notes
2016-11-28 08:09:43DIGITAL PLAN REVIEW/ SIGNATURES
 W. P. B. PERMIT: 15061278
 ADD: 777 S. FLAGLER DR. FLOORS: 11TH & 12TH
 CONT: WOOLEMS INC.
 TEL: (561)835-0401
 E-MAIL: [email protected]
  
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW/ SIGNATURES
 DATE: MON. NOV. 28/ 2016
 ACTION: DENIED
  
 REVIEW FOR DIGITAL SIGNATURES:
 1) PAPER PLANS SUBMITTED SHEET A0.06 INDICATES REV. # 3
 WHEREAS THE DIGITAL PLAN DOES NOT HAVE REVISION # 3.
  
 2) DIGITAL PLANS ARE MISSING SHEET A1.02
  
 3) DIGITAL PLANS ARE MISSING SHEET A1.04
  
 4) DIGITAL PLANS ARE MISSING SHEET A1.06
  
 5) DIGITAL PLANS ARE MISSING SHEET A1.08
  
 6) THE DIGITAL PLANS FOR FIRE SPRINKLER, ELECTRICAL,
 MECHANICAL & PLUMBING SHEETS ARE NOT DIGITALLY SIGNED
 NOR IS THERE ANY DOCUMENTATION IN THE SIGNATURE FOLDER
 FILE. THERE WERE NO SHEETS SUBMITTED IN THE PAPER
 DOCUMENTS FOR THESE TRADES, FIRE SPRINKLER, ELECTRICAL,
 MECHANICAL & PLUMBING.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
2016-11-22 12:38:30DIGITALLY SIGNED PLANS RECIEVED VIA FEDEX, PUT TO
 JWITMER'S DESK

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2016-11-02 Cont ID  
Sent By gjohnson Date 2016-11-02 Time 16:05 Rev Time 0.00
Received By gjohnson Date 2016-11-02 Time 16:04 Sent To  
Notes
2016-11-02 16:07:24NONE OF THE PAGES IN THIS PLAN SET HAVE BEEN DIGITALLY
 SIGNED
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
2016-10-26 16:45:53NONE OF THE ARCHITECTURAL SHEETS NOR SK-1.0 ARE SIGNED
 NOR SEALED ELECTRONICLLY. JW.