Plan Review Details - Permit 15061269
Plan Review Stops For Permit 15061269
Review Stop E ELECTRICAL
Rev No 5 Status P Date 2015-10-30 Cont ID  
Sent By albarran Date 2015-10-30 Time 11:19 Rev Time 0.00
Received By albarran Date 2015-10-29 Time 14:02 Sent To  
Notes
2015-10-30 11:19:49ALL PREVIOUSLY MENTIONED DEFICIENCIES HAVE BEEN
 SATISFACTORILY CORRECTED.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2015-10-20 Cont ID  
Sent By albarran Date 2015-10-20 Time 15:35 Rev Time 0.00
Received By albarran Date 2015-10-20 Time 09:13 Sent To  
Notes
2015-10-20 15:38:23BELOW ARE THE COMMENTS WITH REGARDS TO MY FINDINGS:
 PG. FA-2.1.1
 1. SEE CHANGEMARKS 1, 2 & 3.THOUGH YOU ARE EXEMPT FROM
 MANUAL PULL STATION DEVICES, THIS UNIT ON THE GROUND
 FLOOR SHOULD BE RELOCATED CLOSER TO THE EXIT AS MARKED.
 2. SEE CHANGEMARK 4. SMOKE DETECTOR PROTECTION INSIDE
 THE ELECTRICAL ROOM AS WELL AS THE EQUIPMENT ROOMS IS
 REQUIRED BY FBC, SECTION 907.2.18.1, AND IS A WISER
 CHOICE THAN RUNNING FIRE SPRINKLER IN THERE.
 3. SEE CHANGEMARK 5 ALL ELECTRICAL AND/OR EQUIPMENT
 ROOMS ARE NOT IDENTIFIED AS REQUIRED BY FBC SECTION
 907.1.2(1). SMOKE DETECTOR PROTECTION INSIDE THE
 ELECTRICAL AND/OR EQUIPMENT ROOMS AS REQUIRED BY FBC,
 SECTION 907.2.18.1 AND IS A WISER CHOICE THAN RUNNING
 FIRE SPRINKLER IN THERE. YOU SHALL SUBMIT
 MANUFACTURER?S DATA SHEETS ON ALL THE PROPOSED
 EQUIPMENT AND DEVICES BEING INSTALLED. AS PER FBC
 SECTION 907.1.2(10)
 PG. FA-2.1.2
 1. ALL ELECTRICAL AND/OR EQUIPMENT ROOMS ARE NOT
 IDENTIFIED AS REQUIRED BY FBC SECTION 907.1.2(1). SMOKE
 DETECTOR PROTECTION INSIDE THE ELECTRICAL AND/OR
 EQUIPMENT ROOMS AS REQUIRED BY FBC, SECTION 907.2.18.1
 AND IS A WISER CHOICE THAN RUNNING FIRE SPRINKLER IN
 THERE. YOU SHALL SUBMIT MANUFACTURER?S DATA SHEETS ON
 ALL THE PROPOSED EQUIPMENT AND DEVICES BEING INSTALLED.
 AS PER FBC SECTION 907.1.2(10)
 PG. FA-2.1.3
 1. SEE CHANGEMARKS 1, 2 & 3. SMOKE DETECTOR PROTECTION
 INSIDE THE ELECTRICAL AND/OR EQUIPMENT ROOMS AS
 REQUIRED BY FBC, SECTION 907.2.18.1 AND IS A WISER
 CHOICE THAN RUNNING FIRE SPRINKLER IN THERE.
 PG. FA-2.1.4, FA-2.1.5, FA-2.1.6, FA-2.1.7, FA-2.1.8,
 FA-2.1.9
 1. ALL ELECTRICAL AND/OR EQUIPMENT ROOMS ARE NOT
 IDENTIFIED AS REQUIRED BY FBC SECTION 907.1.2(1). SMOKE
 DETECTOR PROTECTION INSIDE THE ELECTRICAL AND/OR
 EQUIPMENT ROOMS AS REQUIRED BY FBC, SECTION 907.2.18.1
 AND IS A WISER CHOICE THAN RUNNING FIRE SPRINKLER IN
 THERE.
 PG. FA-3.1.1
 1. ACCORDING TO THIS RISER DIAGRAM THERE ARE SPEAKERS
 ON THE GRD. FLOOR. SYMBOL OF WHICH DOES NOT APPEAR ON
 THE LEGEND ON PG. FA-4.1.1
 2. NOT ALL SMOKE DETECTORS REFLECTED ON THE RISER
 DIAGRAM APPEAR ON THE GRD FLOOR PLAN
 PG. FA-4.1.1
 1. CONFLICTING SYMBOL IDENTIFIERS PLEASE CORRECT OR
 CLARIFY.
 2. IN THE INTEREST OF CONSISTENCY, PLEASE REVISE THE WP
 INDICATORS TO BE TYPICAL THROUGHOUT THE PLANS.
 3. THIS SHOULD READ, "COVERED TO PROTECT"
  
 IN ADDITION TO ALL OF THE ABOVE YOU SHALL PROVIDE THE
 REQUIRED VOLTAGE DROP CALCULATIONS FOR ALL WIRING ALONG
 WITH BATTERY CALCS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
  
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2015-10-14 Cont ID  
Sent By albarran Date 2015-10-14 Time 17:51 Rev Time 0.00
Received By albarran Date 2015-10-14 Time 16:39 Sent To  
Notes
2015-10-14 17:51:04AT A MEETING THIS AFTERNOON WITH REPRESENTATIVES FROM
 KAST, THE ELECTRICAL CONTRACTOR, THE ARCHITECT THE
 OWNER AND MYSELF WE DISCUSSED THE REQUIRED CORRECTIONS
 AS INDICATED BY MY REVIEW NOTES. I WAS FALSELY LED TO
 BELIEVE THAT THERE HAD BEEN A RE-SUBMITTAL ADDRESSING
 ALL THE CORRECTIONS ACCOMPANIED BY A NARRATIVE WHICH
 WESLEY JOLIN APPROVED. AFTER OUR MEETING I TRIED TO GO
 INTO PROJECTDOX TO STRAIGHTEN OUT THE SUPPOSEDLY
 INCORRECT VERSIONING AND REALIZED THAT IT WAS ALL
 FALSE, THERE HAS NOT BEEN A RE-SUBMITTAL AND WES HAS
 NOT SEEN A REVISED SET OF DRAWINGS. AS HE STATED IN
 COMMUNITY PLUS, HE APPROVED BASED ONLY ON THE
 ENGINEER'S LETTER. THESE FOLKS HAVE BEEN REMINDED
 NUMEROUS TIMES TO GET THEIR CORRECTED SUBMITTAL IN FOR
 REVIEW AND THEY HAVE NOT DONE SO. IRRESPONSIBILITY ON
 THEIR PART DOES NOT CONSTITUTE AN EMERGENCY ON MINE.
 ON THE OTHER HAND, THIS STRUCTURE BEING GREATER THAN
 75' IN HEIGHT SHALL BE CONSIDERED PER FBC-BUILDING A
 HIGH-RISE AND THEREFORE SHALL COMPLY WITH THE FIRE
 ALARM REQUIREMENTS AS INDICATED IN THE 5TH EDITION OF
 THE FBC-B 2014 SECTION 907.2.13

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-08-26 Cont ID  
Sent By albarran Date 2015-08-26 Time 13:33 Rev Time 0.00
Received By albarran Date 2015-08-04 Time 13:37 Sent To  
Notes
2015-08-26 13:41:25THIS REVIEW WAS STARTED ON 7/17/15. ON 8/4/15 I WENT
 BACK TO IT AND TODAY 8/26/15 I COMPLETED THE REVIEW.
 THE APPLICATION/REVIEW FAILED ELECTRICAL AS NOTED
 BELOW:
 PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
  
 PAGE FA2.1.1
 1. THIS SHEET IS MISSING THE COMPLETE TITLE BLOCK
 2. THIS SHEET HAS NO F/A MARKINGS.
  
 PAGE FA2.1.2
 1. PER NFPA 72, SECTION 17.14.6, MANUAL PULL STATION
 REQUIRED WITHIN 5' OF EXIT.
 2. SAME AS CHANGE MARK 1 FOR VARIOUS LOCATIONS ON THIS
 PAGE.
 3. PER NFPA 72, SECTION 17.14.8, ADDITIONAL PULL
 STATIONS SHALL BE PROVIDED TO KEEP TRAVEL DISTANCE TO A
 PULL BOX UNDER 200FT.
 4. IDENTIFY/INCLUDE THE ?DD INSIDE THE SQUARE? SYMBOL
 ON YOUR LEGEND. DUCT DETECTOR?
  
 PAGE FA2.1.3 THROUGH FA2.1.8 APPEAR TO HAVE SIMILAR
 ISSUES. BASICALLY NO MANUAL INITIATION DEVICES APPEAR
 ON THE FLOOR PLANS.
 1. PER NFPA 72, SECTION 17.14.6, MANUAL PULL STATION
 REQUIRED WITHIN 5' OF EXIT.
 2. PER NFPA 72, SECTION 17.14.6, MANUAL PULL STATION
 REQUIRED WITHIN 5' OF EXIT.
 3. PER NFPA 72, SECTION 17.14.6, MANUAL PULL STATION
 REQUIRED WITHIN 5' OF EXIT.
 4. PER NFPA 72, SECTION 17.14.6, MANUAL PULL STATION
 REQUIRED WITHIN 5' OF EXIT.
 5. PER NFPA 72, SECTION 17.14.6, MANUAL PULL STATION
 REQUIRED WITHIN 5' OF EXIT.
 6. PER NFPA 72, SECTION 17.14.8, ADDITIONAL PULL
 STATIONS SHALL BE PROVIDED TO KEEP TRAVEL DISTANCE TO A
 PULL BOX UNDER 200FT.
 7. PER NFPA 72, SECTION 17.14.6, MANUAL PULL STATION
 REQUIRED WITHIN 5' OF EXIT.
 8. SMOKE DETECTOR INSIDE ELECTRICAL EQUIPMENT ROOM.
 9. SMOKE DETECTOR INSIDE ELECTRICAL EQUIPMENT ROOM.
  
 THERE APPEARS TO BE SMOKE BARRIER DOOR IN THE CORRIDORS
 W/O THE SMOKE DETECTORS AND OR DOOR HOLDER RELAYS. IF
 THE CORRIDORS ARE COMPARTMENTALIZED SHOW THE REQUIRED
 DEVICES.
  
 PAGES FA2.1.9 ROOF
 1. THIS PAGE IS LACKING THE MANUAL INITIATION DEVICES
 AS WELL.
 2. THERE ARE SYMBOLS NOT IDENTIFIED ON THE LEGEND.
  
 PAGES FA3.1.1.3.1.3 & FA3.1.1.3.1.5 RISER DIAGRAMS
 1. NOTHING SHOWN FOR THE GROUND FLOOR ON THE RISER
 DIAGRAM APPEARS ON THE CORRESPONDING PAGE.
 2. THE CONTINUATION OF THE RISER DIAGRAM, PROBABLY PAGE
 FA3.1.1.3.1.4 (THIRD TO FIFTH FLOORS) IS MISSING.
 3. THE CONTINUATION OF THE RISER DIAGRAM FOR THE
 SEVENTH FLOOR TO ROOF IS ALSO MISSING.
 4. THE ENTIRE RISER DIAGRAMS WILL HAVE TO BE RECREATED
 TO INCLUDE THE MISSING DEVICES ONCE ADDED TO PLANS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
  
2015-08-04 16:37:32REVIEW RESULTS PENDING RESPONSE FROM WES.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-08-26 Cont ID  
Sent By wjolin Date 2015-07-01 Time 12:54 Rev Time 0.00
Received By albarran Date 2015-07-14 Time 17:23 Sent To  
Notes
2015-07-14 17:41:077/17/15 - VERSIONS CONFLICT RESOLVED; RETURNED TO
 REVIEW
 7/14/15 - I BEGAN TO DO THE REVIEW BUT IT APPEARS THAT
 THIS IS VERSIONED INCORRECTLY. I ADVISED LEM AND
 WAITING FOR RESPONSE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2015-10-23 Cont ID  
Sent By wjolin Date 2015-10-23 Time 16:41 Rev Time 0.00
Received By wjolin Date 2015-10-23 Time 15:17 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-07-01 Cont ID  
Sent By wjolin Date 2015-07-01 Time 12:51 Rev Time 0.00
Received By wjolin Date 2015-07-01 Time 12:49 Sent To  
Notes
2015-07-01 12:51:32NOTE: PLANS WERE PREVIOUSLY SUBMITTED HARD-COPY UNDER
 PERMIT REVISION #15060302 AND HAS BEEN VOIDED. DIGITAL
 PLANS SUBMITTED UNDER THIS PERMIT REVISION #15061269.
  
 PLANS HAVE BEEN APPROVED BASED UPON THE ENGINEER OF
 RECORD'S EXPLANATION LETTER DETAILING THE PLAN CHANGES.
 REVISED PLAN (SHEET FA-2.1.1) FOR GROUND LEVEL ONLY
 SHOWS A FLOOR PLAN. NO FIRE ALARM DEVICES OR TITLEBLOCK
 COULD LOCATED. APPEARS DRAWING LAYERS HAVE BEEN FROZEN.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-07-01 Cont ID  
Sent By wjolin Date 2015-07-01 Time 12:49 Rev Time 0.00
Received By wjolin Date 2015-07-01 Time 12:48 Sent To  
Notes
2015-07-01 12:49:41705 NORTH OLIVE AVENUE
 REVISEDTRACKING #15061269
 TRACKING VOID #15060302
 MASTER #14030096
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NO ADDRESS INDICATED ON THE PLANS OR IN THE TITLEBLOCK.
  
 NO REVISION CLOUDS, DELTAS OR DETAILED SUMMARY PROVIDED
 INDICATED WHAT HAS CHANGED ON THE PLANS.
  
 PLANS WERE ORIGINALLY SUBMITTED DIGITALLY; REVISION WAS
 SUBMITTED AS HARD COPY. PLEASE RESUBMIT THE REVISED
 PLANS DIGITALLY.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-10-30 Cont ID  
Sent By cpuell Date 2015-10-30 Time 11:47 Rev Time 0.00
Received By cpuell Date 2015-10-26 Time 16:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-10-26 Cont ID  
Sent By lmarchan Date 2015-10-23 Time 11:03 Rev Time 0.00
Received By lmarchan Date 2015-10-16 Time 06:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-09-10 Cont ID  
Sent By lmarchan Date 2015-09-10 Time 11:55 Rev Time 0.00
Received By lmarchan Date 2015-07-01 Time 10:07 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2015-12-18 Cont ID  
Sent By skennedy Date 2015-12-18 Time 14:02 Rev Time 0.00
Received By skennedy Date 2015-12-18 Time 14:02 Sent To  
Notes
2015-12-16 13:21:39PEDDS GIVEN TO SKENNEDY