Notes
2015-06-27 12:39:07 
 BUILDING PLAN REVIEW
 W. P. B. PERMIT:15061254
 MASTER: 15011018
 ADD: 2020 PALM BEACH LAKES
 CONT: MORTON ROOFING
 TEL: (954)783-5883
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. JUNE 27/ 2015
 ACTION: DENIED
  
 1) THE SUBMITTED NOA 14-0611.01 GAF RUBEROID MODIFIED
 BITUMEN ROOF SYSTEM IS FOR A FLAT ROOF. S201 SUBMITTED
 DATED 01/26/14 AND REVISION DATED 03/11/15 AND THE
 LATEST REVISION DATED 06/02/15 ALL SHOW A GABLE STYLE
 ROOF WITH PARAPET AROUND THE PERIMETER.
  
 2) THE SUBMITTED NOA 14-0611.01 PAGE 26 OF 29 MAXIMUM
 DESIGN PRESSURES ARE -75 LITH LIMITATION # 7 WHICH
 REQUIRES A DESIGN PROFESSIONAL TO CALCULATE THE
 FASTENING TO RAS 117.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  