Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-07-01 Cont ID  
Sent By albarran Date 2015-07-01 Time 18:55 Rev Time 0.00
Received By albarran Date 2015-07-01 Time 18:12 Sent To I
Notes
2015-07-01 18:57:57IN ADDITION TO THE TAMPER-RESISTANT DEVICE REQUIREMENT
 OF NEC 406.11, THE FOLLOWING PROVISOS ARE ATTACHED TO
 THIS PERMIT.
 ELECTRICAL PROVISOS:
 1. PER FBC-R 315 YOU SHALL INSTALL A CO DETECTOR WITHIN
 10? OF THE DOORS TO EVERY SLEEPING ROOM.
 2. PER NFPA 72 SECTION 29.8.3.4(4) SMOKE DETECTORS
 MOUNTED WITHIN 10? OF A COOKING APPLIANCE SHALL BE
 RATED FOR SUCH; IF PHOTOELECTRIC WITHIN 20? SHALL BE
 EQUIPPED W/A SILENCING MEANS.
 3. PER NFPA 72 SECTION 29.8.3.4(6) SMOKE DETECTORS
 SHALL NOT BE INSTALLED WITHIN 3? FROM A DOOR TO A
 BATHROOM CONTAINING A SHOWER OR TUB UNLESS LISTED FOR
 SUCH.
 4. PER NEC 314.27 CEILING MOUNTED LUMINAIRE OUTLETS
 SHALL BE LISTED TO SUPPORT 50#
 5. PER NEC 314.20 BOXES IN NON-COMBUSTIBLE WALLS MAY
 SETBACK NO MORE THAN 1/8? FROM SURFACE AND FLUSH WITH
 COMBUSTIBLE SURFACES.
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-07-01 Cont ID  
Sent By albarran Date 2015-07-01 Time 18:58 Rev Time  
Received By albarran Date   Time   Sent To  
Notes
2015-07-01 19:02:107/1/15 - PASSED ELECTRICAL REVIEW W/PROVISOS.
 CONTRACTOR NOTIFIED VIA EMAIL. SENT TO SMALL READY BIN
 "R". MA
2015-06-25 13:25:14ROUTED TO ELECTRICAL LESS THAN $5000