Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-08-06 Cont ID  
Sent By albarran Date 2015-08-06 Time 15:09 Rev Time 0.00
Received By albarran Date 2015-08-06 Time 14:35 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-08-04 Cont ID  
Sent By albarran Date 2015-08-04 Time 19:48 Rev Time 0.00
Received By albarran Date 2015-08-04 Time 19:36 Sent To  
Notes
2015-08-04 20:03:39PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
  
 1. YOU SUBMITTED A SINGLE SHEET ADDRESSING THE
 ERRONEOUS CODE PREVIOUSLY QUOTED, BUT FAILED TO ADDRESS
 ANY OF THE OTHER MORE IMPORTANT ISSUES.
 2. YOU FAILED TO PRODUCE A CORRECTED FLOOR PLAN WITH
 EACH ROOM PROPERLY LABELED AS INSTRUCTED.
 3. YOU FAILED TO INDICATE THE CEILING HEIGHTS AS
 REQUIRED BY CODE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-07-15 Cont ID  
Sent By albarran Date 2015-07-15 Time 13:33 Rev Time 0.00
Received By albarran Date 2015-07-15 Time 12:47 Sent To I
Notes
2015-07-15 13:52:58THE FOLLOWING ITEMS SHALL BE CORRECTED AND THE PLANS
 RESUBMITTED FOR ANOTHER REVIEW.
 1. THE INCORRECT CODE IS QUOTED. YOU QUOTE NFPA 72 2002
 EDITION IN ONE PLACE AND THEN THE 2007 EDITION ELSE
 WHERE.
 2. PER NFPA 72 2007, SECTION 5.13.6, A PULL STATION IS
 REQUIRED WITHIN 5' OF AN EXIT AT EVERY FLOOR. THIS
 MEANS THE MEZZANINE LEVEL.
 3. PER FBC EACH ROOM SHALL BE LABELED
 4. PER FBC, DETAILS OF CEILING HEIGHT SHALL BE
 PROVIDED.
 5. THOUGH THE VISUAL NOTIFICATION DEVICES APPEAR TO BE
 WELL PLACED, THIS CAN CHANGE WITH THE ARRANGEMENT OF
 SHELVING ETC. THIS SHALL BE DETERMINED AT THE FINAL
 INSPECTION.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-06-26 Cont ID  
Sent By pleduc Date 2015-06-26 Time   Rev Time 0.00
Received By pleduc Date 2015-06-26 Time 08:59 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-08-05 Cont ID  
Sent By albarran Date 2015-08-04 Time 20:05 Rev Time 0.00
Received By albarran Date 2015-08-04 Time 15:39 Sent To  
Notes
2015-08-04 20:06:49FAILED TO PROPERLY ADDRESS PRIOR COMMENTS. CONTRACTOR
 NOTIFIED VIA EMAIL. SENT TO SMALL DENIED BIN "P". MA
2015-08-04 15:39:33RESUB ROUTED TO MALBARRAN

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-07-15 Cont ID  
Sent By albarran Date 2015-08-06 Time 15:11 Rev Time  
Received By albarran Date   Time   Sent To  
Notes
2015-08-06 15:11:418/6/15 - PASSED ELECTRICAL REVIEW WHILE CUSTOMER
 WAITED. SENT TO SUSAN PALMER. MA
2015-07-15 13:55:277/15/15 - FAILED ELECTRICAL REVIEW. CONTRACTOR NOTIFIED
 VIA EMAIL. SENT TO SMALL DENIED BIN "P". MA
2015-06-24 14:50:34ROUTED TO FIRE