Plan Review Details - Permit 15061108
Plan Review Stops For Permit 15061108 |
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2015-08-06 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2015-08-06 |
Time |
15:09 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2015-08-06 |
Time |
14:35 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2015-08-04 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2015-08-04 |
Time |
19:48 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2015-08-04 |
Time |
19:36 |
Sent To |
|
|
Notes |
2015-08-04 20:03:39 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS | | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE | | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO | | THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE | | CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. | | | | 1. YOU SUBMITTED A SINGLE SHEET ADDRESSING THE | | ERRONEOUS CODE PREVIOUSLY QUOTED, BUT FAILED TO ADDRESS | | ANY OF THE OTHER MORE IMPORTANT ISSUES. | | 2. YOU FAILED TO PRODUCE A CORRECTED FLOOR PLAN WITH | | EACH ROOM PROPERLY LABELED AS INSTRUCTED. | | 3. YOU FAILED TO INDICATE THE CEILING HEIGHTS AS | | REQUIRED BY CODE. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE | | PREVIOUSLY REVIEWED SHEETS. | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | CONTACT ME DIRECTLY. | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2015-07-15 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2015-07-15 |
Time |
13:33 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2015-07-15 |
Time |
12:47 |
Sent To |
I |
|
Notes |
2015-07-15 13:52:58 | THE FOLLOWING ITEMS SHALL BE CORRECTED AND THE PLANS | | RESUBMITTED FOR ANOTHER REVIEW. | | 1. THE INCORRECT CODE IS QUOTED. YOU QUOTE NFPA 72 2002 | | EDITION IN ONE PLACE AND THEN THE 2007 EDITION ELSE | | WHERE. | | 2. PER NFPA 72 2007, SECTION 5.13.6, A PULL STATION IS | | REQUIRED WITHIN 5' OF AN EXIT AT EVERY FLOOR. THIS | | MEANS THE MEZZANINE LEVEL. | | 3. PER FBC EACH ROOM SHALL BE LABELED | | 4. PER FBC, DETAILS OF CEILING HEIGHT SHALL BE | | PROVIDED. | | 5. THOUGH THE VISUAL NOTIFICATION DEVICES APPEAR TO BE | | WELL PLACED, THIS CAN CHANGE WITH THE ARRANGEMENT OF | | SHELVING ETC. THIS SHALL BE DETERMINED AT THE FINAL | | INSPECTION. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2015-06-26 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2015-06-26 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2015-06-26 |
Time |
08:59 |
Sent To |
E |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2015-08-05 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2015-08-04 |
Time |
20:05 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2015-08-04 |
Time |
15:39 |
Sent To |
|
|
Notes |
2015-08-04 20:06:49 | FAILED TO PROPERLY ADDRESS PRIOR COMMENTS. CONTRACTOR | | NOTIFIED VIA EMAIL. SENT TO SMALL DENIED BIN "P". MA | 2015-08-04 15:39:33 | RESUB ROUTED TO MALBARRAN |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2015-07-15 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2015-08-06 |
Time |
15:11 |
Rev Time |
|
Received By |
albarran |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2015-08-06 15:11:41 | 8/6/15 - PASSED ELECTRICAL REVIEW WHILE CUSTOMER | | WAITED. SENT TO SUSAN PALMER. MA | 2015-07-15 13:55:27 | 7/15/15 - FAILED ELECTRICAL REVIEW. CONTRACTOR NOTIFIED | | VIA EMAIL. SENT TO SMALL DENIED BIN "P". MA | 2015-06-24 14:50:34 | ROUTED TO FIRE |
|
|
|