Plan Review Details - Permit 15061003
Plan Review Stops For Permit 15061003 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2015-07-13 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2015-07-13 |
Time |
14:45 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2015-07-13 |
Time |
14:37 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
|
Date |
2015-07-10 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2015-07-10 |
Time |
15:10 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2015-07-10 |
Time |
15:10 |
Sent To |
|
|
Notes |
2015-07-10 15:19:32 | REVISED RAS 117 CALCULATIONS ARE OK. NEED TO SUBMIT | | CALCULATIONS WITH ORIGINAL ENGINEER'S SEAL AND | | SIGNATURE AS REQUIRED BY CHAPTER 471 FL. ST. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2015-07-06 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2015-07-06 |
Time |
18:46 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2015-07-06 |
Time |
18:45 |
Sent To |
|
|
Notes |
2015-07-06 19:01:33 | RESIDENTIAL (R3) RE-ROOF SECOND BUILDING REVIEW | | COMMENTS. | | CODE: 2010 FBC-RESIDENTIAL | | | | 1- ENGINEER TO REVISE THE RAS 117 CALCULATIONS | | SUBMITTED: | | A) THIS BUILDING IS LOCATED IN EXPOSURE "D" NO "C". | | REVISE CALCULATIONS AS REQUIRED. SEC. R301.2.1.4.3 OF | | 2010 FBC-RESIDENTIAL. | | | | B) HEIGHT OF THE BUILDING IS INCORRECT. THIS IS A TWO | | STORY BUILDING. 14' HEIGHT IS NOT CORRECT. REVISE | | CALCULATIONS AS REQUIRED. SEC. R301.1 OF 2010 | | FBC-RESIDENTIAL. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | (561)805-6712 | | [email protected] |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2015-06-24 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2015-06-24 |
Time |
14:10 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2015-06-24 |
Time |
13:44 |
Sent To |
|
|
Notes |
2015-06-24 14:32:01 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS. | | CODE: 2010 FBC-RESIDENTIAL | | | | 1- FLAT ROOF FLORIDA PRODUCT APPROVAL FL2533-R12: | | SELECTED ASSEMBLY W-69 DOESN'T MEET THE DESIGN | | PRESSURES FOR THE CORNER AREAS OF THIS BUILDING. SELECT | | ANOTHER ASSEMBLY THAT MEETS THE DESIGN PRESSURES OR | | PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR BASE | | SHEET NAIL ENHANCEMENT. NOTE: THIS BUILDING IS LOCATED | | IN EXPOSURE "D". SEC R301.2.1.4.3 OF 2010 | | FBC-RESIDENTIAL. | | | | 2- TU PLUS ROOF TILE UNDERLAYMENT FL5259-R22: | | SELF-ADHERING UNDERLAYMENTS NEED TO COMPLY WITH THE | | DESIGN PRESSURES OF ALL ROOF ZONES. CLEARLY IDENTIFY | | WHICH MAXIMUM DESIGN PRESSURES FROM SEC. 5.6.4 OF | | FLORIDA PRODUCT APPROVAL IS GOING TO BE INSTALLED TO | | VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. | | R301 OF 2010 FBC-RESIDENTIAL. | | | | 3- VALUATION WAS UPDATED TO $22,296 AS REQUIRED BY SEC. | | 109.3 CITY AMENDMENTS. THE PERMIT FEE BALANCE IS | | $512.58. | | | | IF YOU HAVE ANY QUESTION, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | (561)805-6712 | | [email protected] | | . |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2015-07-10 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2015-07-10 |
Time |
15:19 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2015-07-10 |
Time |
15:19 |
Sent To |
|
|
Notes |
2015-07-10 15:20:28 | REVISED RAS 117 CALCULATIONS WERE E-MAILED. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2015-07-10 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2015-07-10 |
Time |
15:10 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2015-07-10 |
Time |
15:09 |
Sent To |
|
|
Notes |
|
|
|