Plan Review Details - Permit 15061003
Plan Review Stops For Permit 15061003
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2015-07-13 Cont ID  
Sent By jgomez Date 2015-07-13 Time 14:45 Rev Time 0.00
Received By jgomez Date 2015-07-13 Time 14:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status   Date 2015-07-10 Cont ID  
Sent By jgomez Date 2015-07-10 Time 15:10 Rev Time 0.00
Received By jgomez Date 2015-07-10 Time 15:10 Sent To  
Notes
2015-07-10 15:19:32REVISED RAS 117 CALCULATIONS ARE OK. NEED TO SUBMIT
 CALCULATIONS WITH ORIGINAL ENGINEER'S SEAL AND
 SIGNATURE AS REQUIRED BY CHAPTER 471 FL. ST.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-07-06 Cont ID  
Sent By jgomez Date 2015-07-06 Time 18:46 Rev Time 0.00
Received By jgomez Date 2015-07-06 Time 18:45 Sent To  
Notes
2015-07-06 19:01:33RESIDENTIAL (R3) RE-ROOF SECOND BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC-RESIDENTIAL
  
 1- ENGINEER TO REVISE THE RAS 117 CALCULATIONS
 SUBMITTED:
 A) THIS BUILDING IS LOCATED IN EXPOSURE "D" NO "C".
 REVISE CALCULATIONS AS REQUIRED. SEC. R301.2.1.4.3 OF
 2010 FBC-RESIDENTIAL.
  
 B) HEIGHT OF THE BUILDING IS INCORRECT. THIS IS A TWO
 STORY BUILDING. 14' HEIGHT IS NOT CORRECT. REVISE
 CALCULATIONS AS REQUIRED. SEC. R301.1 OF 2010
 FBC-RESIDENTIAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-06-24 Cont ID  
Sent By jgomez Date 2015-06-24 Time 14:10 Rev Time 0.00
Received By jgomez Date 2015-06-24 Time 13:44 Sent To  
Notes
2015-06-24 14:32:01RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC-RESIDENTIAL
  
 1- FLAT ROOF FLORIDA PRODUCT APPROVAL FL2533-R12:
 SELECTED ASSEMBLY W-69 DOESN'T MEET THE DESIGN
 PRESSURES FOR THE CORNER AREAS OF THIS BUILDING. SELECT
 ANOTHER ASSEMBLY THAT MEETS THE DESIGN PRESSURES OR
 PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR BASE
 SHEET NAIL ENHANCEMENT. NOTE: THIS BUILDING IS LOCATED
 IN EXPOSURE "D". SEC R301.2.1.4.3 OF 2010
 FBC-RESIDENTIAL.
  
 2- TU PLUS ROOF TILE UNDERLAYMENT FL5259-R22:
 SELF-ADHERING UNDERLAYMENTS NEED TO COMPLY WITH THE
 DESIGN PRESSURES OF ALL ROOF ZONES. CLEARLY IDENTIFY
 WHICH MAXIMUM DESIGN PRESSURES FROM SEC. 5.6.4 OF
 FLORIDA PRODUCT APPROVAL IS GOING TO BE INSTALLED TO
 VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 R301 OF 2010 FBC-RESIDENTIAL.
  
 3- VALUATION WAS UPDATED TO $22,296 AS REQUIRED BY SEC.
 109.3 CITY AMENDMENTS. THE PERMIT FEE BALANCE IS
 $512.58.
  
 IF YOU HAVE ANY QUESTION, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
 .

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-07-10 Cont ID  
Sent By jgomez Date 2015-07-10 Time 15:19 Rev Time 0.00
Received By jgomez Date 2015-07-10 Time 15:19 Sent To  
Notes
2015-07-10 15:20:28REVISED RAS 117 CALCULATIONS WERE E-MAILED.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-07-10 Cont ID  
Sent By jgomez Date 2015-07-10 Time 15:10 Rev Time 0.00
Received By jgomez Date 2015-07-10 Time 15:09 Sent To  
Notes
***NONE***