Plan Review Details - Permit 15060940
Plan Review Stops For Permit 15060940
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-09-14 Cont ID  
Sent By jgomez Date 2015-09-14 Time 13:27 Rev Time 0.00
Received By jgomez Date 2015-09-14 Time 13:27 Sent To  
Notes
2015-09-14 13:28:46PER PHONE CONVERSATION WITH PETER NUNEZ, THE SCOPE OF
 WORK IS KITCHEN CABINETS REPLACEMENT. JG.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2015-08-21 Cont ID  
Sent By jgomez Date 2015-08-21 Time 11:07 Rev Time 0.00
Received By jgomez Date 2015-08-21 Time 11:07 Sent To  
Notes
2015-08-21 11:08:36NO WORK SHOWN ON PLANS. ONLY MEP WORK. JG.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-08-21 Cont ID  
Sent By skennedy Date 2015-08-21 Time 12:14 Rev Time 0.00
Received By skennedy Date 2015-08-21 Time 12:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-09-14 Cont ID  
Sent By jgomez Date 2015-09-14 Time 14:27 Rev Time 0.00
Received By jgomez Date 2015-09-09 Time 08:55 Sent To  
Notes
2015-09-10 08:55:33RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-08-21 Cont ID  
Sent By skennedy Date 2015-08-21 Time 12:14 Rev Time 0.00
Received By skennedy Date 2015-06-22 Time 18:52 Sent To  
Notes
2015-06-22 18:53:23SENT TO R22 SHELF FOR REVIEW. JG.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2015-09-14 Cont ID  
Sent By jgomez Date 2015-09-14 Time 13:28 Rev Time 0.00
Received By jgomez Date 2015-09-14 Time 13:28 Sent To  
Notes
2015-09-14 13:30:49PER PHONE CONVERSATION WITH PETER NUNEZ, THE MECHANICAL
 CONTRACTOR WILL SUBMIT PLANS AND EQUIPMENT SIZING
 CALCULATIONS UNDER A SEPARATE PERMIT. JG.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-08-21 Cont ID  
Sent By jgomez Date 2015-08-21 Time 11:08 Rev Time 0.00
Received By jgomez Date 2015-08-21 Time 11:08 Sent To  
Notes
2015-08-21 11:18:49RESIDENTIAL (R3) MECHANICAL REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- EQUIPMENT SIZING CALCULATIONS SUBMITTED ARE DONE FOR
 THE WRONG LOCATION. THIS IS CITY OF WEST PALM BEACH NOT
 FORT LAUDERDALE. ENGINEER DOING THE CALCULATIONS TO
 REVISE AS REQUIRED. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 2- ENERGY CALCULATIONS SUBMITTED NEED TO HAVE THE
 OWNER/AGENT SIGNATURE AS REQUIRED BY SEC. 103.2.3.2 OF
 2010 FBC-ENERGY CONSERVATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-07-20 Cont ID  
Sent By gjohnson Date 2015-07-20 Time 13:09 Rev Time 0.00
Received By gjohnson Date 2015-07-20 Time 13:08 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2015-06-30 Cont ID  
Sent By sgraham Date 2015-06-30 Time 15:57 Rev Time 0.00
Received By sgraham Date 2015-06-30 Time 15:57 Sent To  
Notes
***NONE***