2015-08-20 18:50:48PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SHOW COMPLIANCE WITH FBC EXISTING BUILDING 604.1 FOR
 EGRESS WINDOWS IN THE SECOND FLOOR BEDROOM. THE
 EXISTING 30" X 36" BEDROOM WINDOWS WERE JALOSIE WINDOWS
 WHICH WOULD ALLOW THE SLATS TO BE REMOVED OR EASILY
 BROKEN OUT IN AN EMERGENCY. THE PROPOSED IMPACT RATED
 SINGLE HUNG WINDOWS WILL NOT PROVIDE A LARGE ENOUGH
 CLEAR OPENING AND WOULD BE VERY DIFFICULT TO BREAK. I
 WOULD SUGGEST THAT YOU CONSIDER INSTALLING A CASEMENT
 WINDOW IN THE BEDROOM.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-09-08 Cont ID  
Sent By rmcdouga Date 2015-09-08 Time 14:51 Rev Time 0.00
Received By rmcdouga Date 2015-09-08 Time 14:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-08-20 Cont ID  
Sent By rmcdouga Date 2015-08-20 Time 17:02 Rev Time 0.00
Received By rmcdouga Date 2015-08-20 Time 17:02 Sent To  
Notes
2015-08-20 17:26:29PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY ELECTRICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) NEC 250.52 & 210.70 - PROVIDE AN ELECTRICAL FLOOR
 PLAN SHOWING THE LOCATION OF ALL REQUIRED LIGHTING AND
 RECEPTACLE OUTLETS AND SHOW CIRCUITS.
  
 2) NEC 220.40 - SUBMIT ELECTRICAL LOAD CALCULATIONS.
  
 3) FBC 107.3.5.3 - SUBMIT PANEL SCHEDULES.
  
 4) NEC 240.24(A) & (B) PANELS SHALL BE READILY
 ACCESSIBLE AND EACH OCCUPANT SHALL HAVE READY ACCESS.
 SPECIFY THE LOCATIONS OF THE PANELS ON THE ELECTRICAL
 FLOOR PLAN.
  
 5) FBC- 107.3.5.3 - PROVIDE AN ELECTRIC SERVICE RISER
 WITH WIRE SIZES, CONDUIT DETAIL AND GROUNDING DETAIL.
  
 6) NEC 110.9 - SPECIFY THE A.I.C. RATING OF THE
 ELECTRICAL EQUIPMENT ON THE PLANS.
  
 7) NEC 210.70 (A) (2) - PROVIDE AT LEAST ONE WALL
 SWITCH CONTROLLED LIGHTING OUTLET TO PROVIDE
 ILLUMINATION ON THE EXTERIOR SIDE OF OUTDOOR ENTRANCES
 OR EXISTS WITH GRADE LEVEL ACCESS.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-09-08 Cont ID  
Sent By rmcdouga Date 2015-09-08 Time 14:51 Rev Time 0.00
Received By rmcdouga Date 2015-08-31 Time 15:20 Sent To  
Notes
2015-08-31 15:21:26MCDOUGAL'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-08-20 Cont ID  
Sent By rmcdouga Date 2015-08-20 Time 18:50 Rev Time 0.00
Received By rmcdouga Date 2015-06-22 Time 09:43 Sent To  
Notes
2015-06-22 09:44:08SENT TO R6 SHELF FOR REVIEW. JG.

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-09-08 Cont ID  
Sent By tklarge Date 2015-09-08 Time 14:55 Rev Time 0.00
Received By tklarge Date 2015-09-08 Time 14:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-07-20 Cont ID  
Sent By tklarge Date 2015-07-20 Time 09:10 Rev Time 0.00
Received By tklarge Date 2015-07-20 Time 09:04 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2015-06-30 Cont ID  
Sent By sgraham Date 2015-06-30 Time 15:27 Rev Time 0.00
Received By sgraham Date 2015-06-30 Time 15:27 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved