2015-08-26 09:53:02BUILDING PLAN REVIEW
 PERMIT: 15060911
 ADD: 1220 ORTEGA RD
 CONT: WILBUR HOBGOOD CONST.
 TEL: (561)691-9686
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS,
 AND SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SUN. JUNE 28/ 2015
 ACTION: BUILDING PROVISO
  
 A SEPARATE ROOFING PERMIT & REVIEW REQUIRED.
 ROOFING PRODUCT APPROVAL : 13-0529.14
 JOHN MANVILLE MODIFIED BITUMEN OVER WOOD DECK
 NO SUB-SYSTEM WAS IDENTIFIED, WILL NEED TO SELECT A
 SUB-SYSTEM BETWEEN
 PAGES 10-26. NOTE PRESSURES ARE GOOD FOR ZONE # 1 BUT
 WILL REQUIRE
 ENHANCED FASTENING IN ZONES 2 & 3. SEE IF LIMITATION 7
 OR 9 APPLIES.
  
 PAGE 27 LIMITATION # 7 REQUIRES RAS 117 CALCULATIONS TO
 BE COMPLETED BY
 EITHER AN ARCHITECT OR ENGINEER REGISTERED WITH THE
 STATE OF FLORIDA.
  
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2015-06-28 Cont ID  
Sent By jwitmer Date 2015-06-28 Time 07:01 Rev Time 0.00
Received By jwitmer Date 2015-06-28 Time 06:22 Sent To  
Notes
2015-06-28 06:42:41BUILDING PLAN REVIEW
 PERMIT: 15060911
 ADD: 1220 ORTEGA RD
 CONT: WILBUR HOBGOOD CONST.
 TEL: (561)691-9686
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS,
 AND SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SUN. JUNE 28/ 2015
 ACTION: BUILDING PROVISO
  
 A SEPARATE ROOFING PERMIT & REVIEW REQUIRED.
 ROOFING PRODUCT APPROVAL : 13-0529.14
 JOHN MANVILLE MODIFIED BITUMEN OVER WOOD DECK
 NO SUB-SYSTEM WAS IDENTIFIED, WILL NEED TO SELECT A
 SUB-SYSTEM BETWEEN
 PAGES 10-26. NOTE PRESSURES ARE GOOD FOR ZONE # 1 BUT
 WILL REQUIRE
 ENHANCED FASTENING IN ZONES 2 & 3. SEE IF LIMITATION 7
 OR 9 APPLIES.
  
 PAGE 27 LIMITATION # 7 REQUIRES RAS 117 CALCULATIONS TO
 BE COMPLETED BY
 EITHER AN ARCHITECT OR ENGINEER REGISTERED WITH THE
 STATE OF FLORIDA.
  
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-07-23 Cont ID  
Sent By albarran Date 2015-07-23 Time 11:16 Rev Time 0.00
Received By albarran Date 2015-07-23 Time 09:43 Sent To I
Notes
2015-07-23 11:18:39APPROVED W/PROVISO: THERE ARE A COUPLE OF ITEMS WHICH
 ARE MISSING FROM THE DRAWINGS THAT HAVE BEEN MARKED AND
 MENTIONED ON THE APPROVED PLANS. WHICH SHALL BE
 ADDRESSED FOR INSPECTION.
 1. NEC 600.5(A) REQUIRED BRANCH CIRCUIT. EACH
 COMMERCIAL BUILDING AND EACH COMMERCIAL OCCUPANCY
 ACCESSIBLE TO PEDESTRIANS SHALL BE PROVIDED WITH AT
 LEAST ONE OUTLET IN AN ACCESSIBLE LOCATION AT EACH
 ENTRANCE TO EACH TENANT SPACE FOR SIGN OR OUTLINE
 LIGHTING SYSTEM USE. THE OUTLET(S) SHALL BE SUPPLIED BY
 A BRANCH CIRCUIT RATED AT LEAST 20 AMPERES THAT
 SUPPLIES NO OTHER LOAD. SERVICE HALLWAYS OR CORRIDORS
 SHALL NOT BE CONSIDERED ACCESSIBLE TO PEDESTRIANS.
 2. FBC-B 1006.3 EXITS SHALL BE MARKED BY AN APPROVED
 SIGN READILY VISIBLE FROM ANY DIRECTION OF EXIT ACCESS.
 EVERY EXIT SHALL BE SUITABLY ILLUMINATED BY A RELIABLE
 LIGHT SOURCE. EXTERNALLY & INTERNALLY ILLUMINATED SIGNS
 SHALL BE VISIBLE IN BOTH NORMAL & EMERGENCY LIGHTING.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2015-07-02 Cont ID  
Sent By cranford Date 2015-07-02 Time 10:38 Rev Time 0.00
Received By cranford Date 2015-07-02 Time 10:33 Sent To  
Notes
2015-07-02 10:38:22SEE E12030009 FOR ENGINEERING DEVELOPMENT APPROVAL.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-08-19 Cont ID  
Sent By pleduc Date 2015-08-19 Time   Rev Time 0.00
Received By pleduc Date 2015-08-19 Time 09:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-06-23 Cont ID  
Sent By pleduc Date 2015-06-23 Time   Rev Time 0.00
Received By pleduc Date 2015-06-23 Time 14:56 Sent To  
Notes
2015-06-23 15:34:14THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET A 1 - THERE IS AN INCORRECT REFERNECE TO THE
 FIRE CODE.
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
  
 2) SHEET A 5 - THE NEW EXIT DOORS SHALL SWING IN THE
 DIRECTION OF EGRESS. PLEASE REVIEW THE FOLLOWING:
 NFPA 101 CHAPTER 7, MEANS OF EGRESS
 7.2.1.4.3 DOOR LEAF ENCROACHMENT
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE
 REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY,
 OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT
 MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A
 CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN,
 UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS
 PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED
 WIDTH OF THE STAIR LANDING WHEN THE DOOR LEAF IS FULLY
 OPEN.
  
 3) NO EXIT DOOR SHALL BE LOCKED FROM THE EGRESS SIDE.
 ANY AND ALL LOCKING MECHANISMS SHALL BE COMPLAINT WITH
 CHAPTER 7 OF THE FLORIDA FIRE PREVENTION CODE. PROVIDE
 A DOOR SCHEDULE INCLUDING EXIT AND LATCH HARDWARE.
  
 4) SHEET E 2.01 - PROVIDE AND EXIT SIGN AT THE SIDE
 EXIT DOOR.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-08-26 Cont ID  
Sent By jwitmer Date 2015-08-26 Time 09:53 Rev Time 0.00
Received By jwitmer Date 2015-08-07 Time 14:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-07-23 Cont ID  
Sent By albarran Date 2015-07-23 Time 11:19 Rev Time 0.00
Received By albarran Date 2015-06-19 Time 17:26 Sent To  
Notes
2015-07-23 11:21:05CONTRACTOR NOTIFIED VIA EMAIL. RETURNED TO C11 DUE TO
 PIGGYBACK PERMIT 15060916 MISSING BLDG. REVIEW. MA
2015-06-19 17:34:49PLACED IN C11

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2015-08-26 Cont ID  
Sent By jwitmer Date 2015-08-26 Time 09:51 Rev Time 0.00
Received By jwitmer Date 2015-08-26 Time 09:51 Sent To  
Notes
2015-08-26 09:52:22JULY 22/2015
 MU-2015-18295
 598 SQ. FT.
 $954.34

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-06-28 Cont ID  
Sent By jwitmer Date 2015-06-28 Time 06:35 Rev Time 0.00
Received By jwitmer Date 2015-06-28 Time 06:34 Sent To  
Notes
2015-06-28 06:35:43BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-08-14 Cont ID  
Sent By ccole Date 2015-08-14 Time 15:25 Rev Time 0.00
Received By ccole Date 2015-08-14 Time 15:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-07-07 Cont ID  
Sent By ccole Date 2015-07-07 Time 10:51 Rev Time 0.00
Received By ccole Date 2015-07-07 Time 10:51 Sent To  
Notes
2015-07-07 11:26:581ST REVIEW: FBC 2010 MECHANICAL
  
 1) ENERGY COMPLIANCE FORM 506-2010: A) THE CONSTRUCTION
 MATERIALS LISTED FOR THE LOADING DOCK WALLS IN THE
 INPUT DATA REPORT SHOW SOLID WALLS WHICH DOES NOT MATCH
 THE PLAN WHICH SHOWS SEVEN INSULATED ROLL-UP DOORS. B)
 THE REPORT IS LISTING ONLY TWO MAN DOORS HOWEVER THERE
 ARE THREE SHOWN ON THE PLAN.
 2) THE AIR SYSTEM SIZING SUMMARIES INDICATE THE
 LOCATION OF THE PROJECT TO BE IN MIAMI. PLEASE REVISE
 THE CALCS TO INDICATE WEST PALM BEACH LOCATION, AND USE
 THE CORRECT DB/WB TEMPERATURES PER TABLE 1A MANUAL N.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-07-14 Cont ID  
Sent By tklarge Date 2015-07-14 Time 05:21 Rev Time 0.00
Received By tklarge Date 2015-07-14 Time 05:01 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2015-06-26 Cont ID  
Sent By sgraham Date 2015-06-26 Time 08:49 Rev Time 0.00
Received By sgraham Date 2015-06-26 Time 08:49 Sent To  
Notes
***NONE***