Plan Review Details - Permit 15060833
Plan Review Stops For Permit 15060833
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-06-18 Cont ID  
Sent By dhayes Date 2015-06-18 Time 15:00 Rev Time 0.00
Received By dhayes Date 2015-06-18 Time 15:00 Sent To  
Notes
2015-06-18 15:14:59APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN APPROVED
 PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION
 FEE(S).
  
 1) WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL
 314 AND 315.
  
 2) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER
 RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11
  
 3) IN ADDITION TO THE NUMBER OF BRANCH CIRCUITS
 REQUIRED BY OTHER PARTS OF THIS SECTION, AT LEAST ONE
 20-AMPERE BRANCH CIRCUIT SHALL BE PROVIDED TO SUPPLY
 BATHROOM RECEPTACLE OUTLET(S). SUCH CIRCUITS SHALL HAVE
 NO OTHER OUTLETS. NEC 210.11(C)(3)
  
 4) ALL 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE
 RECEPTACLES INSTALLED IN THE LOCATIONS SPECIFIED IN (1)
 THROUGH (8) SHALL HAVE GROUND-FAULT CIRCUIT-INTERRUPTER
 PROTECTION FOR PERSONNEL. NEC 210.8 (1) BATHROOMS
  
 5) IN DWELLING UNITS, AT LEAST ONE RECEPTACLE OUTLET
 SHALL BE INSTALLED IN BATHROOMS WITHIN (3 FT) OF THE
 OUTSIDE EDGE OF EACH BASIN. NEC 210.52 (D)
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-06-18 Cont ID  
Sent By dhayes Date 2015-06-18 Time 15:01 Rev Time 0.00
Received By dhayes Date 2015-06-18 Time 15:00 Sent To  
Notes
***NONE***