2015-06-23 10:35:02 | 6/23/2015 |
| PROJECT: GLUE PRODUCTS |
| PERMIT#: 15041010 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| 2ND ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| BELOW IS THE LIST OF ITEMS REQUESTED ON THE FIRST |
| REVIEW ALONG WITH THE ITEMS PROVIDED ON YOUR |
| RE-SUBMITTAL. AS NOTED, THERE IS A DEFICIENCIES AND NOT |
| UNTIL ALL ITEMS ARE PROVIDED WILL THIS PERMIT BE |
| APPROVED. THE RISER DIAGRAM YOU PROVIDED DOES NOT MATCH |
| THE ONE ON THE PLANS. IF THE ONE ON THE PLANS IS |
| INCORRECT, PLEASE CROSS IT OUT. PER NEC REQUIREMENTS |
| YOU SHALL PROVIDE A LOAD CALC OF THE4 EXISTING TO |
| ASCERTAIN THAT THE SERVICE WILL ABSORB THE ADDED LOAD |
| PROPERLY. |
| |
| |
| MISSING 1. PROVIDE THE CIRCUITRY ON THE FLOOR PLAN TO |
| COINCIDE WITH THE REQUIRED PANEL SCHEDULE AS WELL AS A |
| RISER DIAGRAM AND LOAD CALCULATION. FBC 107.3.5 |
| ELECTRICAL |
| |
| MISSING 2. PROVIDE COMPLETE CIRCUIT DIRECTORIES FOR |
| ELECTRICAL PANELS. EVERY CIRCUIT SHALL BE LEGIBLY |
| IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC |
| PURPOSE OR USE. NEC 408.4 |
| |
| MISSING 3. INDICATE THE REQUIRED LIGHTING CONTROLS FOR |
| INTERIOR AND EXTERIOR ILLUMINATION. LIGHTING SYSTEMS |
| SHALL BE PROVIDED WITH CONTROLS AS REQUIRED IN |
| FBC-ENERGY CONSERVATION SECTIONS 505 ELECTRICAL POWER & |
| LIGHTING SYSTEMS (MANDATORY). |
| |
| MISSING 4. INDICATE THE REQUIRED LIGHTING ABOUT |
| ELECTRICAL EQUIPMENT. ILLUMINATION SHALL BE PROVIDED |
| FOR ALL WORKING SPACES ABOUT ELECTRICAL PANELS AND |
| EQUIPMENT. NEC 110.26 (D) |
| |
| MISSING 5. VERIFY SAFETY LABELING FOR ARC FLASH |
| PROTECTION FOR THE PANEL BOARDS AND MAIN DISCONNECTING |
| MEANS. NEC 110.16 |
| |
| MISSING 6. INDICATE ALL REQUIRED EMERGENCY |
| ILLUMINATION. EMERGENCY ILLUMINATION SHALL INCLUDE ALL |
| REQUIRED MEANS OF EGRESS LIGHTING, ILLUMINATED EXIT |
| SIGNS, AND ALL OTHER LIGHTS SPECIFIED AS NECESSARY TO |
| PROVIDE REQUIRED ILLUMINATION. NEC 700.16(F) |
| |
| INCOMPLETE 7. PROVIDE THE LOCATION OF ALL MECHANICAL |
| EQUIPMENT WITH ASSOCIATED REQUIRED DISCONNECTS AND GFI |
| OUTLETS. NEC 210.63, 210.8(A)(3), NEC 440.14, THE FIRE |
| PLAN DOES HAVE AN INDICATION OF THE LOCATION, BUT IT |
| DOES NOT COMPLY WITH THE ELECTRICAL REQUIREMENTS. |
| |
| MAY NOT BE NECESSARY AS ONLY THE MIX ROOMS ARE BEING |
| ADDED TO THE EXISTING LOCATION 8. INDICATE PROVISIONS |
| FOR THE REQUIRED SIGN CIRCUIT AND SHOW WINDOW LIGHTING. |
| NEC 210.62, 600.5(A) |
| |
| COMPLETE (15060821) 9. SEPARATE ELECTRICAL PERMIT |
| ACCOMPANIED BY MANUFACTURER?S EQUIPMENT SUBMITTAL |
| REQUIRED, FOR ELECTRICAL WORK |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| REVIEW. |
| |