Plan Review Details - Permit 15060821
Plan Review Stops For Permit 15060821
Review Stop E ELECTRICAL
Rev No 2 Status N Date 2015-08-06 Cont ID  
Sent By skennedy Date 2015-08-06 Time 09:47 Rev Time 0.00
Received By skennedy Date 2015-08-06 Time 09:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-06-23 Cont ID  
Sent By albarran Date 2015-06-23 Time 09:57 Rev Time 0.00
Received By albarran Date 2015-06-23 Time 09:57 Sent To I
Notes
2015-06-23 10:35:026/23/2015
 PROJECT: GLUE PRODUCTS
 PERMIT#: 15041010
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 BELOW IS THE LIST OF ITEMS REQUESTED ON THE FIRST
 REVIEW ALONG WITH THE ITEMS PROVIDED ON YOUR
 RE-SUBMITTAL. AS NOTED, THERE IS A DEFICIENCIES AND NOT
 UNTIL ALL ITEMS ARE PROVIDED WILL THIS PERMIT BE
 APPROVED. THE RISER DIAGRAM YOU PROVIDED DOES NOT MATCH
 THE ONE ON THE PLANS. IF THE ONE ON THE PLANS IS
 INCORRECT, PLEASE CROSS IT OUT. PER NEC REQUIREMENTS
 YOU SHALL PROVIDE A LOAD CALC OF THE4 EXISTING TO
 ASCERTAIN THAT THE SERVICE WILL ABSORB THE ADDED LOAD
 PROPERLY.
  
  
 MISSING 1. PROVIDE THE CIRCUITRY ON THE FLOOR PLAN TO
 COINCIDE WITH THE REQUIRED PANEL SCHEDULE AS WELL AS A
 RISER DIAGRAM AND LOAD CALCULATION. FBC 107.3.5
 ELECTRICAL
  
 MISSING 2. PROVIDE COMPLETE CIRCUIT DIRECTORIES FOR
 ELECTRICAL PANELS. EVERY CIRCUIT SHALL BE LEGIBLY
 IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC
 PURPOSE OR USE. NEC 408.4
  
 MISSING 3. INDICATE THE REQUIRED LIGHTING CONTROLS FOR
 INTERIOR AND EXTERIOR ILLUMINATION. LIGHTING SYSTEMS
 SHALL BE PROVIDED WITH CONTROLS AS REQUIRED IN
 FBC-ENERGY CONSERVATION SECTIONS 505 ELECTRICAL POWER &
 LIGHTING SYSTEMS (MANDATORY).
  
 MISSING 4. INDICATE THE REQUIRED LIGHTING ABOUT
 ELECTRICAL EQUIPMENT. ILLUMINATION SHALL BE PROVIDED
 FOR ALL WORKING SPACES ABOUT ELECTRICAL PANELS AND
 EQUIPMENT. NEC 110.26 (D)
  
 MISSING 5. VERIFY SAFETY LABELING FOR ARC FLASH
 PROTECTION FOR THE PANEL BOARDS AND MAIN DISCONNECTING
 MEANS. NEC 110.16
  
 MISSING 6. INDICATE ALL REQUIRED EMERGENCY
 ILLUMINATION. EMERGENCY ILLUMINATION SHALL INCLUDE ALL
 REQUIRED MEANS OF EGRESS LIGHTING, ILLUMINATED EXIT
 SIGNS, AND ALL OTHER LIGHTS SPECIFIED AS NECESSARY TO
 PROVIDE REQUIRED ILLUMINATION. NEC 700.16(F)
  
 INCOMPLETE 7. PROVIDE THE LOCATION OF ALL MECHANICAL
 EQUIPMENT WITH ASSOCIATED REQUIRED DISCONNECTS AND GFI
 OUTLETS. NEC 210.63, 210.8(A)(3), NEC 440.14, THE FIRE
 PLAN DOES HAVE AN INDICATION OF THE LOCATION, BUT IT
 DOES NOT COMPLY WITH THE ELECTRICAL REQUIREMENTS.
  
 MAY NOT BE NECESSARY AS ONLY THE MIX ROOMS ARE BEING
 ADDED TO THE EXISTING LOCATION 8. INDICATE PROVISIONS
 FOR THE REQUIRED SIGN CIRCUIT AND SHOW WINDOW LIGHTING.
 NEC 210.62, 600.5(A)
  
 COMPLETE (15060821) 9. SEPARATE ELECTRICAL PERMIT
 ACCOMPANIED BY MANUFACTURER?S EQUIPMENT SUBMITTAL
 REQUIRED, FOR ELECTRICAL WORK
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353,
 561-805-7943 OR [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-08-06 Cont ID  
Sent By skennedy Date 2015-08-06 Time 09:47 Rev Time 0.00
Received By skennedy Date 2015-07-09 Time 12:56 Sent To  
Notes
2015-08-06 09:47:56SEE 15041010
2015-07-09 12:56:48ON ALBARRAN DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-06-23 Cont ID  
Sent By albarran Date 2015-06-23 Time 10:18 Rev Time 0.00
Received By albarran Date 2015-06-18 Time   Sent To  
Notes
2015-06-23 10:21:07THIS IS PART OF A THREE PERMIT PACK. I WAS GOING TO
 ISSUE THE PERMIT W/AN ELECTRICAL HOLD BUT REALIZED THAT
 THERE ARE STILL PENDING ZONING MATTERS, THEREFORE I
 RETURNED THIS TO SMALL DENIED "F", UNTIL SUCH TIME AS
 THE OTHER SUBMITTAL ARE COMPLETE. I SPOKE W/THE EC TO
 DISCUSS THIS SUBMITTAL; HE WILL COMPLETE AS DISCUSSED.
2015-06-22 10:35:24PULLED FROM THE ELECTRICAL BOX AND ROUTED TO
 M.ALBARRAN'S DESK FOR ELECTRICAL REVIEW UNDER THE
 MASTER 15041010.
2015-06-18 15:43:15INCOMING SENT TO ELECTRICAL BOX <$5K.