Plan Review Details - Permit 15060608
Plan Review Stops For Permit 15060608
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-07-20 Cont ID  
Sent By rmcdouga Date 2015-07-20 Time 18:01 Rev Time 0.00
Received By rmcdouga Date 2015-07-20 Time 18:01 Sent To P
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-06-17 Cont ID  
Sent By rmcdouga Date 2015-06-17 Time 17:06 Rev Time 0.00
Received By rmcdouga Date 2015-06-17 Time 17:06 Sent To  
Notes
2015-06-17 17:22:14PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PAPER PLANS ARE REQUIRED TO HAVE THE ENGINEER'S
 ORIGINAL HANDWRITTEN SIGNATURE ON THEM. DIGITAL
 SIGNATURES ARE ONLY VALID FOR ELECTRONICALLY SUBMITTED
 DOCUMENTS. FS 471 & FS 668.50

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-07-21 Cont ID  
Sent By skennedy Date 2015-07-21 Time 14:55 Rev Time 0.00
Received By skennedy Date 2015-07-21 Time 14:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-06-17 Cont ID  
Sent By Pool Bin Date 2015-06-17 Time 16:37 Rev Time 0.00
Received By dhayes Date 2015-06-17 Time 16:37 Sent To B
Notes
2015-06-17 16:46:196/17/2015
 PROJECT: SWIMMING POOL
 PERMIT#: 15060608
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) PROVIDE A REFFERENCE FOR THE LOAD CALCULATION
 SUBMITTED. THE DEMAND LOAD SUBMITTED IS RAZOR CLOSE TO
 100% OF THE MAIN OCPD. PROVIDE SUPPORTING DOCUMENTATION
 FOR THE TOTAL DEMAND LOAD ARRIVED AT IN THE
 CALCULATION. WPB AMENDMENTS TO THE FBC 107.2.1
  
 2) PROVIDE A PANEL SCHEDULE THAT INCLUDES THE OCPD AND
 WIRE SIZES FOR ALL NEW CIRCUITS. NEC 408.4
  
 3) PROVIDE MANUFACTURER SPECS FOR NEW POOL PANEL, TIME
 CLOCK, TRANSFORMER, DECK BOX AND POOL LIGHTS. NEC
 680.24, 110.3
  
 4) ALL DESIGN DOCUMENTS TO BE SIGNED BY THE DESIGNER
 RESPONSIBLE FOR THE DESIGN. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. FBC, WPB AMENDMENTS 107.2.1
 4A) THE SUBMITTED PLANS ARE PHOTOCOPIED PLANS OF AN
 ORIGINAL SIGNED AND SEALED PLAN. PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC RECORD SHALL
 HAVE THE SIGNATURE AND SEAL OF THE DESIGN PROFESSIONAL
 AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2015-06-17 Cont ID  
Sent By tklarge Date 2015-06-17 Time 11:08 Rev Time 0.00
Received By tklarge Date 2015-06-17 Time 11:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-07-21 Cont ID  
Sent By skennedy Date 2015-07-21 Time 14:55 Rev Time 0.00
Received By skennedy Date 2015-07-14 Time 15:56 Sent To  
Notes
2015-07-14 15:57:20IN POOL BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-06-17 Cont ID  
Sent By rmcdouga Date 2015-06-17 Time 17:06 Rev Time 0.00
Received By rmcdouga Date 2015-06-12 Time 18:54 Sent To  
Notes
2015-06-12 18:54:39SENT TO ZONING SHELF FOR REVIEW. JG.

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-07-21 Cont ID  
Sent By skennedy Date 2015-07-21 Time 14:47 Rev Time 0.00
Received By skennedy Date 2015-07-21 Time 14:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-06-17 Cont ID  
Sent By tklarge Date 2015-06-17 Time 11:09 Rev Time 0.00
Received By tklarge Date 2015-06-17 Time 11:09 Sent To  
Notes
2015-06-17 11:44:211) THE PAPER PLANS STATE THAT THEY HAVE BEEN DIGITALLY
 SIGNED BY WAYNE BENNETT, P.E. THE PLANS SHALL BE
 SUBMITTED ELECTRONICALLY FOR THE DIGITAL SIGNATURE TO
 BE VALID PER FL. STATUTE 471.025.
 2) THE SUBMITTAL OF DIGITALLY SIGNED PLANS SHALL COMPLY
 WITH FL. ADMIN.CODE RULE 61G15-23.003.
 3) IF THE INTENT IS TO SUBMIT PAPER PLANS FOR
 PERMITTING, BOTH SETS SHALL BE SIGNED AND SEALED PER
 THE THE FL. ADMIN. CODE 61G15-23.002.
  
 PLEASE CONTACT CAROLINE PUELL, PERMIT LIBRARIAN, AT
 561-805-6659 FOR SUBMITTING PLANS ELECTRONICALLY.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2015-06-16 Cont ID  
Sent By sgraham Date 2015-06-16 Time 10:26 Rev Time 0.00
Received By sgraham Date 2015-06-16 Time 10:26 Sent To B
Notes
***NONE***