Plan Review Details - Permit 15060603
Plan Review Stops For Permit 15060603
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-08-15 Cont ID  
Sent By tklarge Date 2015-08-15 Time 05:28 Rev Time 0.00
Received By tklarge Date 2015-08-13 Time 13:43 Sent To  
Notes
2015-08-13 13:43:55RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-08-15 Cont ID  
Sent By ccole Date 2015-06-19 Time 10:30 Rev Time 0.00
Received By tklarge Date 2015-06-19 Time 09:37 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-08-15 Cont ID  
Sent By tklarge Date 2015-08-15 Time 05:14 Rev Time 0.00
Received By tklarge Date 2015-08-15 Time 05:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-08-15 Cont ID  
Sent By tklarge Date 2015-06-19 Time 10:30 Rev Time 0.00
Received By tklarge Date 2015-06-19 Time 10:01 Sent To  
Notes
2015-06-19 10:29:071) SUBMIT A ROOF PLAN SHOWING THE LOCATION OF THE ROOF
 DRAINS AND SHOW THE SQUARE FOOTAGE OF THE ROOF THAT IS
 BEING DRAINED INTO EACH DRAIN.WPB AMEND. TO 2010 FBC
 SEC. 107.2.1.
 2) THE SIZING OF THE ROOF DRAINS AND ALL VERTICAL AND
 HORIZONTAL PIPING SHALL BE SIZED IN ACCORDANCE WITH
 TABLES 1106.2 (1) & 1106.3 FOR A RAINFALL RATE OF 5
 INCHES PER HOUR.
 3) INDICATE TYPE OF PIPING TO INSTALLED. IF PVC, IT
 SHALL BE SUPPORTED AT 4 FT.INTERVALS HORIZONTALLY AND
 10 FT. INTERVALS VERTICALLY. INDICATE ON THE PLANS HOW
 THE PIPE WILL BE SUPPORTED.
 4) SUBMIT DETAILS FOR SECONDARY (EMERGENCY) DRAINAGE
 PER 2010 FPC SEC.1107.1.
 5) INDICATE IF THERE IS A PARAPET WALL ON THIS PROJECT.
 IF SO, ONE-HALF THE AREA OF ANY VERTICAL WALL THAT
 DIVERTS RAINWATER TO THE ROOF SHALL BE ADDED TO THE
 PROJECTED ROOF AREA PER 2010 FPC SEC.1106.4.
 6) SHOW THE TERMINATION POINT OF EACH DRAIN. THE
 VERTICAL LEADERS/CONDUCTORS SHALL DISCHARGE A MINIMUM
 OF ONE (1) FOOT FROM THE STRUCTURE SIDEWALL PER THE
 2010 FBC SEC.1503.7. SUBMIT A PLAN SHOWING THE
 TERMINATION/DISCHARGE POINTS OF THE LEADERS/CONDUCTORS.
 WPB AMEND. TO 2010 FBC SEC. 107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
2015-06-19 09:38:14ROUTED TO PLUMBING/CC