Plan Review Details - Permit 15060579
Plan Review Stops For Permit 15060579
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-06-22 Cont ID  
Sent By skennedy Date 2015-06-22 Time 10:29 Rev Time 0.00
Received By skennedy Date 2015-06-22 Time 10:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-06-12 Cont ID  
Sent By skennedy Date 2015-06-12 Time 13:45 Rev Time 0.00
Received By skennedy Date 2015-06-12 Time 13:45 Sent To Z
Notes
2015-06-12 14:54:08BUILDING PLAN REVIEW
  
 2010 FLORIDA BUILDING CODE W?
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DENIED
  
 1) IS THIS APPLICATION FOR THE TEMPORARY INSTALLATION
 OF A CONSTRUCTION MODULAR BUILDING OR SALES TRAILER FOR
 6 MONTHS, OR LONGER?
  
 THE 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, 102.2 BUILDING. THE FOLLOWING
 BUILDINGS, STRUCTURES AND FACILITIES ARE EXEMPT FROM
 THE FLORIDA BUILDING CODE AS PROVIDED BY LAW, AND ANY
 FURTHER EXEMPTIONS SHALL BE AS DETERMINED BY THE
 LEGISLATURE AND PROVIDED BY LAW:
  
 (E) MOBILE OR MODULAR STRUCTURES USED AS TEMPORARY
 OFFICES, EXCEPT THAT THE PROVISIONS OF PART V (SECTION
 553.501-553.513, FLORIDA STATUTES) RELATING TO
 ACCESSIBILITY BY PERSONS WITH DISABILITIES, AND PERMITS
 SHALL BE REQUIRED FOR STRUCTURAL SUPPORT AND TIE DOWN,
 ELECTRICAL SUPPLY, AND ALL UTILITY CONNECTIONS TO SUCH
 MOBILE OR MODULAR STRUCTURES.
  
 2) NO PLANS WERE SUBMITTED FOR THE ACCESSIBLE PARKING
 SPACE, ACCESS AISLE, ACCESSIBLE ROUTE TO THE OFFICE,
 RAMP, STAIRS, LANDING, GAURDRAIL/ HANDRAIL SYSTEM.
 SEE ACC CODE, 405.1-10.
  
 3) INADEQUATE PLANS WERE SUBMITTED SUCH THAT
 DETERMINATION OF THE INTENDED STRUCTURE AS APPROVED BY
 AN OUTSIDE AGENCY COULD BE MADE.
  
 4) IT IS PRESUMED A LOCALLY ENGINEERED FOUNDATION PLAN
 MAY BE REQUIRED.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2015-06-12 Cont ID  
Sent By skennedy Date 2015-06-12 Time 13:44 Rev Time 0.00
Received By skennedy Date 2015-06-12 Time 13:44 Sent To  
Notes
2015-06-12 13:45:24BY SEPARATE PERMIT.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-06-12 Cont ID  
Sent By wjolin Date 2015-06-12 Time 10:39 Rev Time 0.00
Received By wjolin Date 2015-06-12 Time 10:37 Sent To  
Notes
2015-06-12 10:39:35NEED A #131 FIRE INSPECTION BEFORE OCCUPYING
 TRAILER/MODULAR BUILDING.
  
 TEMPORARY BUILDING NEEDS TO BE RELOCATED PER NFPA 241
 PRIOR TO ANY CONSTRUCTION ON THE APARTMENT BUILDING.
  
 WESLEY JOLIN
 WPB FIRE RESCUE
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-06-22 Cont ID  
Sent By skennedy Date 2015-06-22 Time 10:29 Rev Time 0.00
Received By skennedy Date 2015-06-18 Time 10:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-06-16 Cont ID  
Sent By skennedy Date 2015-06-16 Time 14:31 Rev Time 0.00
Received By skennedy Date 2015-06-12 Time 13:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-06-15 Cont ID  
Sent By tklarge Date 2015-06-15 Time 09:12 Rev Time 0.00
Received By tklarge Date 2015-06-15 Time 09:12 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2015-06-16 Cont ID  
Sent By aaponte Date 2015-06-16 Time 14:43 Rev Time 0.00
Received By aaponte Date 2015-06-16 Time 14:43 Sent To  
Notes
***NONE***