Plan Review Details - Permit 15060568
Plan Review Stops For Permit 15060568
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-08-07 Cont ID  
Sent By jwitmer Date 2015-08-07 Time 12:33 Rev Time 0.00
Received By jwitmer Date 2015-08-07 Time 12:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-06-27 Cont ID  
Sent By jwitmer Date 2015-06-27 Time 14:15 Rev Time  
Received By jwitmer Date 2015-06-27 Time   Sent To  
Notes
2015-06-27 14:10:28BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15060568
 ADD: 400 N. FLSGLER DR. SUITE 2102
 CONT: MARYJULI CONSTRUCTION
 TEL: (561)386-6032
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. JUNE 27/2015
 ACTION: DENIED
  
 1) THE PLANS DO NOT HAVE ANY DESIGN CRITERIA TO WHAT
 CODE HAS THE PLANS BEEN DRAWN, UNDER THE EXISTING
 BUILDING CODE THE DESIGNER OF RECORD NEEDS TO INDICATE
 ON THE PLANS THE COMPLIANCE METHOD FOR THIS DESIGN.
 2010 EXST. BLDG. CODE 101.5.
  
 2) THE PLANS DO NOT INDICATE THE BUILDING TYPE NOR THE
 RESTRICTIONS ON TYPE I TYPE II CONSTRUCTION. 2010 FBC-B
 603..1 ALLOWABLE MATERIALS.
  
 3) THE PLANS INDICATE THERE IS TO BE RAISED CEILINGS IN
 THE MASTER BATH, NO DETAILS AS TO HOW THE EXISTING
 CEILING/ SOFFIT IS HUNG NOR HOW THE NEW RAISED CEILINGS
 ARE TO BE BUILT. 107.3.5.1.1 MINIMUM PLAN REVIEW
 CRITERIA FOR COMMERCIAL BUILDINGS. TYPE OF MATERIALS
 FOR FRAMING MEMBERS, SIZE OF FRAMING MEMBERS, GAUGE,
 SPACING, IF STIFF BACKS ARE REQUIRED TYPE OF FINISH
 MATERIAL AND THICKNESS. PLEASE PROVIDE THE FINISH
 ELEVATION ABOVE THE FINISH FLOOR.
  
 4) THE PERMIT APPLICATION INDICATES TO RENOVATE
 BATHROOMS, IF THE FLOORING IS BEING REMOVED PLEASE
 PROVIDE COMPLIANCE WITH:
  
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION
  
 4A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 4B) FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 4C) FLAME SPREAD- FBC-B 2010 603.1.2 EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 5) THE PLANS INDICATE A NEW SHOWER STALL PLEASE PROVIDE
 THE TYPE OF BACKING TO BE REPLACED FOR THE PLACEMENT OF
 TILE. 2010 FBC-B
 2509.2 BASE FOR TILE SURFACES.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-08-14 Cont ID  
Sent By skennedy Date 2015-08-14 Time 15:11 Rev Time 0.00
Received By skennedy Date 2015-08-14 Time 15:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-07-22 Cont ID  
Sent By dhayes Date 2015-07-22 Time 11:39 Rev Time 0.00
Received By dhayes Date 2015-07-22 Time 11:39 Sent To  
Notes
2015-07-22 11:52:087/22/2015
 PROJECT: RULMAN 400 N FLAGLER #2102
 PERMIT#:15060568
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC,
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER ONE,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 THE DESCRIPTION OF WORK ON THE PERMIT APPLICATION
 APPEARS TO READ "REMOVE EXISTING BATHROOM AND REDO 4
 NEW ONES, MASTER & GUEST BATHROOM" BUT THE PLANS ONLY
 SHOW AN EXTREMELY VAGUE SCOPE OF WORK IN ONE BATH.
 CLARIFY WPB AMEND. TO 2010 FBC SEC. 107.2.1.
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) PROVIDE A FIXTURE SCHEDULE FOR LIGHTING FIXTURES TO
 BE INSTALLED INDICATING COMPLIANCE WITH THE NEC
 110.3(B), 410.10(D) AND FBC-ENERGY 502.3.8
  
 2) AT LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED IN
 BATHROOMS WITHIN (3 FT) OF THE OUTSIDE EDGE OF EACH
 BASIN. 210.52 (D) BATHROOMS. INDICATE THE REQUIRED
 RECEPTACLE IN THE BATHROOM BY THE SINK.
 RECEPTACLES INSTALLED IN THE LOCATIONS SPECIFIED IN (1)
 THROUGH (8) SHALL HAVE GROUND-FAULT CIRCUIT-INTERRUPTER
 PROTECTION FOR PERSONNEL. (1) BATHROOMS
  
 3) PROVIDE A PANEL SCHEDULE INDICATING COMPLIANCE WITH
 THE NEC 210.11(C)(3) AND 408.4
  
 4) VERIFY OR INDICATE COMPLIANCE WITH THE FBC REGARDING
 THE EXISTIANCE OR INSTALLATION OF INTERCONNECTED SMOKE
 DETECTORS. WHEN ALTERATIONS, REPAIRS, OR ADDITIONS
 REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE
 INDIVIDUAL DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE
 ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS.
 FBC-RESIDENTIAL 314 AND 315
  
 5) INDICATE HOW THE LIGHTING WILL BE CONTROLLLED AND
 THE LOCATION OF SWITCHES. INDICATE WHETHER SWITCHES ARE
 NEW OR EXISTING.
  
 6) INDICATE COMPLIANCE WITH THE NEC. ALL NEW GENERAL
 PURPOSE OUTLETS MUST BE TAMPER RESISTANT AND AFCI
 PROTECTED. NEC 210.12, 406.11
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-08-04 Cont ID  
Sent By pleduc Date 2015-08-04 Time   Rev Time 0.00
Received By pleduc Date 2015-08-04 Time 13:20 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-06-29 Cont ID  
Sent By pleduc Date 2015-06-29 Time   Rev Time 0.00
Received By pleduc Date 2015-06-29 Time 11:35 Sent To  
Notes
2015-06-29 11:43:36THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THE EXTENT OF THE REMODEL OR REVISION IS UNCLEAR AND
 DOES NOT INDICATE SUFFICIENT DETAIL TO ADDRESS LIFE
 SAFETY CONCERNS OF THE PROPOSED PROJECT.
  
 2) WITH THE PROPOSED CEILING WORK, INDICATED IF THE THE
 AREA IS SPRINKLERED OR HAS FIRE ALARM DEVICES
  
 3) INDICATED THAT ANY SPRINKLER AND/OR FIRE ALARM WORK
 SHALL BE SUBMITTED UNDER SEPARATE SHOP DRAWINGS. THE
 LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE SPRINKLER
 SHALL REMAIN ACTIVE THROUGHOUT THE CONSTRUCTION PERIOD.
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
 4) INDICATED THAT THE PROPOSED PROJECT SHALL MEET THE
 REQUIREMENTS OF THE 5TH EDITION OF FLORIDA FIRE
 PREVENTION CODE INCLUDING THE 2012 EDITION OF NFPA 1
 AND NFPA 101 AND ALL OTHER APPLICABLE CODES OR
 STANDARDS.
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-08-14 Cont ID  
Sent By skennedy Date 2015-08-14 Time 15:11 Rev Time 0.00
Received By skennedy Date 2015-07-30 Time 11:57 Sent To  
Notes
2015-07-30 11:57:26B01 - EXPEDITE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-07-22 Cont ID  
Sent By dhayes Date 2015-07-22 Time 11:52 Rev Time 0.00
Received By dhayes Date 2015-06-12 Time 07:05 Sent To  
Notes
2015-06-12 07:08:20ROUTED TO B03/CC

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-08-08 Cont ID  
Sent By tklarge Date 2015-08-08 Time 03:15 Rev Time 0.00
Received By tklarge Date 2015-08-08 Time 03:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-07-11 Cont ID  
Sent By tklarge Date 2015-07-11 Time 08:01 Rev Time 0.00
Received By tklarge Date 2015-07-11 Time 07:48 Sent To  
Notes
2015-07-11 08:01:26THE DESCRIPTION OF WORK ON THE PERMIT APPLICATION
 APPEARS TO READ " REMOVE EXISTING BATHROOM AND REDO 4
 NEW ONES, MASTER & GUEST BATHROOM BUT THE PLANS ONLY
 SHOW AN EXTREMELY VAGUE SCOPE OF WORK IN ONE BATH.
 CLARIFY.
 2) SUBMIT 2 COPIES OF A SET OF PLANS THAT SHOWS THE
 EXISTING PLAN AND THE PROPOSED PLAN AND ALSO REFLECTS
 THE ENTIRE SCOPE OF WORK TO BE DONE, WPB AMEND. TO 2010
 FBC SEC. 107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  