Plan Review Details - Permit 15060526
Plan Review Stops For Permit 15060526
Review Stop P PLUMBING
Rev No 2 Status P Date 2015-06-17 Cont ID  
Sent By swurafti Date 2015-06-15 Time 11:30 Rev Time 0.00
Received By swurafti Date 2015-06-15 Time 11:30 Sent To  
Notes
2015-06-17 11:31:18NOTE ON FRONT SCREEN SHOWS APPROVED BY TLARGE

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-06-14 Cont ID  
Sent By tklarge Date 2015-06-14 Time 05:20 Rev Time 0.00
Received By tklarge Date 2015-06-14 Time 05:17 Sent To  
Notes
2015-06-14 05:20:371) INDICATE ON THE PLANS WHAT TYPE OF OPERATIONS THE
 HAND SINK & THREE COMPARTMENT SINK WILL SERVE. THE
 THREE COMPARTMENT SINK MAY BE REQUIRED TO DISCHARGE
 THROUGH A GREASE REMOVAL DEVICE OR A GREASE INTERCEPTOR
 / GREASE REMOVAL DEVICE..
 2010 FPC SEC. 1003.3.1, WPB AMEND. TO 2010 FBC SEC.
 107.2.1.
 2) IS THE FLOOR SINK & HAND SINK EXISTING? INDICATE ON
 PLAN.
 3) SUBMIT A FLOOR PLAN SHOWING THE LAYOUT & LOCATION OF
 THESE FIXTURES.
 4) SHOW THE PIPING FOR THE TANKLESS WATER HEATER ON THE
 PLANS. IS IT GAS OR ELECTRIC? SUBMIT MANUFACTURER'S
 SPECIFICATION SHEETS FOR THE TANKLESS WATER HEATER. A
 SEPARATE ELECTRIC PERMIT WILL ALSO BE REQUIRED. IF GAS,
 SUBMIT A GAS DRAWING FOR REVIEW.
 5) CITY RECORDS DO NOT SHOW ANY PREVIOUS PERMITS FOR A
 HAND SINK, THREE COMPARTMENT SINK.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved