Plan Review Details - Permit 15060508
Plan Review Stops For Permit 15060508
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-07-16 Cont ID  
Sent By albarran Date 2015-07-16 Time 15:02 Rev Time 0.00
Received By albarran Date 2015-07-16 Time 14:38 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-07-08 Cont ID  
Sent By albarran Date 2015-07-08 Time 16:08 Rev Time 0.00
Received By albarran Date 2015-07-08 Time 16:01 Sent To I
Notes
2015-07-08 16:14:35PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE CORRECTIONS NOTED..
  
 THE FOLLOWING ITEMS SHALL BE CORRECTED AND THE PLANS
 RESUBMITTED FOR A SECOND REVIEW:
 1. PROVIDE AN EASIER TO UNDERSTAND RISER DIAGRAM. THIS
 DIAGRAM SHALL INDICATE LINE SIDE OF METER WHETHER
 OVERHEAD OR UNDERGROUND.
 2. YOU SHALL PROVIDE LOAD CALCS FOR THE COMPLETE
 RESIDENCE, NOT JUST THE GENERATOR LOAD.
 3. FROM THE SUBMITTED RISER, IT APPEARS THAT BOTH
 PANELS ARE ON THE LOAD SIDE OF THE ATS.
 4. PER NEC ALL CONDUCTORS INSIDE AN UNDERGROUND RACEWAY
 SHALL BE LISTED FOR WET LOCATION AND THHN IS NOT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
  
2015-06-18 11:17:32SENT TO GENERATOR BIN

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-07-16 Cont ID  
Sent By albarran Date 2015-07-16 Time 15:05 Rev Time 0.00
Received By albarran Date 2015-07-16 Time 12:43 Sent To  
Notes
2015-07-16 15:11:037/16/15 - PASSED ELECTRICAL REVIEW. CONTRACTOR NOTIFIED
 VIA EMAIL. SENT TO SMALL READY BIN "A". MA
2015-07-16 12:43:49RESUB ROUTED TO MA

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-07-08 Cont ID  
Sent By albarran Date 2015-07-08 Time 16:17 Rev Time 0.00
Received By albarran Date 2015-06-11 Time 14:05 Sent To  
Notes
2015-07-08 16:18:577/8/15 - FAILED ELECTRICAL REVIEW. CONTRACTOR NOTIFIED
 VIA EMAIL. SENT TO SMALL DENIED BIN "A". MA
2015-06-11 14:14:58ROUTED TO R04

Review Stop Z ZONING
Rev No 1 Status P Date 2015-06-18 Cont ID  
Sent By sgraham Date 2015-06-18 Time 15:39 Rev Time 0.00
Received By sgraham Date 2015-06-18 Time 15:39 Sent To B
Notes
***NONE***