2015-06-12 06:32:28 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT : 15060482 |
| MASTER PERMIT: 14050151 |
| ADD: 1950 GOLDEN LAKES BLVD. |
| CONT: AMBATT ROOFING |
| TEL: (561)792-1826 |
| E-MAIL: [email protected] |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: FRI. JUNE 12/ 2015 |
| ACTION: DENIED |
| |
| 1) PLEASE NOTE THIS IS A REVISION AND FEES WILL BE |
| ASSESSED AS SUCH. UNDER THE MATER PERMIT 14050151 THE |
| DESIGNER OF RECORD HAD APPROVED THE USE OF FLORIDA |
| APPROVAL # 5680-R12 TRINITY ERD GAF MODIFIED BITUMEN |
| ROOF SYSTEM SYSTEM NO. SC-172 W/ -150 PSF. |
| |
| 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE |
| CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND |
| DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS, |
| FASTENING REQUIREMENTS, FLASHING REQUIREMENTS AND WIND |
| RESISTANCE RATING THAT ARE REQUIRED TO BE INSTALLED. |
| PRODUCT EVALUATION AND INSTALLATION SHALL INDICATE |
| COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR THE |
| SPECIFIC SITE OR A STATEMENT BY AN ARCHITECT OR |
| ENGINEER FOR THE SPECIFIC SITE MUST BE SUBMITTED WITH |
| THE CONSTRUCTION DOCUMENTS. |
| |
| 2) PLEASE NOTE THE SUBMITTED NOA 13-1217.06 SUB-SYSTEM |
| SELECTED PAGE 15 OF 26 SBS/APP DECK TYPE 21: STEEL |
| INSULATED HAS A MAXIMUM DESIGN PRESSURE OF -82.5 W/ |
| GENERAL LIMITATION #7. GENERAL LIMITATATION # 7 DOES |
| ALLOW FOR ENHANCED FASTENING BY FLORIDA ARCHITECT OR |
| FLORIDA ENGINEER IN COMPLIANCE WITH RAS 117. SHEET S1.2 |
| DOES HAVE THE ROOFING PRESSURES IN VULT MULTIPLY BY 0.6 |
| TO OBTAIN THE PRESSURES IN VASD. PRESSURES ARE TO HIGH |
| IN ZONE (3) WHERE THERE IS NO 3 FOOT PARAPET. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| DEVELOPMENT SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |
| MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| |
| |
| |
| |
| |