Plan Review Details - Permit 15060482
Plan Review Stops For Permit 15060482
Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2015-06-22 Cont ID  
Sent By jwitmer Date 2015-06-22 Time 14:59 Rev Time 0.00
Received By jwitmer Date 2015-06-22 Time 14:59 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2015-06-12 Cont ID  
Sent By jwitmer Date 2015-06-12 Time 08:59 Rev Time 0.00
Received By jwitmer Date 2015-06-12 Time 05:56 Sent To  
Notes
2015-06-12 06:32:28BUILDING PLAN REVIEW
 W. P. B. PERMIT : 15060482
 MASTER PERMIT: 14050151
 ADD: 1950 GOLDEN LAKES BLVD.
 CONT: AMBATT ROOFING
 TEL: (561)792-1826
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. JUNE 12/ 2015
 ACTION: DENIED
  
 1) PLEASE NOTE THIS IS A REVISION AND FEES WILL BE
 ASSESSED AS SUCH. UNDER THE MATER PERMIT 14050151 THE
 DESIGNER OF RECORD HAD APPROVED THE USE OF FLORIDA
 APPROVAL # 5680-R12 TRINITY ERD GAF MODIFIED BITUMEN
 ROOF SYSTEM SYSTEM NO. SC-172 W/ -150 PSF.
  
 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE
 CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND
 DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS,
 FASTENING REQUIREMENTS, FLASHING REQUIREMENTS AND WIND
 RESISTANCE RATING THAT ARE REQUIRED TO BE INSTALLED.
 PRODUCT EVALUATION AND INSTALLATION SHALL INDICATE
 COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR THE
 SPECIFIC SITE OR A STATEMENT BY AN ARCHITECT OR
 ENGINEER FOR THE SPECIFIC SITE MUST BE SUBMITTED WITH
 THE CONSTRUCTION DOCUMENTS.
  
 2) PLEASE NOTE THE SUBMITTED NOA 13-1217.06 SUB-SYSTEM
 SELECTED PAGE 15 OF 26 SBS/APP DECK TYPE 21: STEEL
 INSULATED HAS A MAXIMUM DESIGN PRESSURE OF -82.5 W/
 GENERAL LIMITATION #7. GENERAL LIMITATATION # 7 DOES
 ALLOW FOR ENHANCED FASTENING BY FLORIDA ARCHITECT OR
 FLORIDA ENGINEER IN COMPLIANCE WITH RAS 117. SHEET S1.2
 DOES HAVE THE ROOFING PRESSURES IN VULT MULTIPLY BY 0.6
 TO OBTAIN THE PRESSURES IN VASD. PRESSURES ARE TO HIGH
 IN ZONE (3) WHERE THERE IS NO 3 FOOT PARAPET.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  