2015-06-19 07:59:55 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 15060473 |
| ADD: 525 S. FLAGLER DR. 5TH FLOOR WELLNESS AREA |
| CONT: URBAN BUILDING CONCEPTS |
| TEL: ( 561)727-8343 |
| E-MAIL: [email protected] |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: FRI. JUNE 19/ 2015 |
| ACTION: DENIED |
| |
| 1) SHEET S1-1 DETAIL # 1 INDICATES THE USE OF HU410 OR |
| HUC410 BUCKETS TO TO SECURED TO THE CONCRETE SLAB . |
| THERE ARE (2) ISSUES: |
| 1A) THE USE OF OR CAN NOT BE USED. 107.2.1 INFORMATION |
| ON CONSTRUCTION DOCUMENTS. . SUCH DRAWINGS AND |
| SPECIFICATIONS SHALL |
| CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, |
| AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS |
| ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH |
| INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES |
| SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE |
| TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE |
| FOR SPECIFIC INFORMATION. |
| |
| 1B) SHEET A1-1 DETAIL # 1 INDICATES THE USE OF UL |
| LISTING G556 A UNRESTRAINED FLOOR / CEILING ASSEMBLY. |
| REQUIREMENT NOTE # 2 DEALS WITH THE METAL JOIST AND |
| CLIP ASSEMBLIES. THE HANGER BUCKETS ARE NOT PART OF |
| THIS ASSEMBLY. PLEASE IDENTIFY WHICH PARTS OF THIS |
| ASSEMBLY ARE GOING TO BE INSTALLED. WITHAPPROPRIATE RIM |
| JOIST OR IF THE CLIP ANGLES ARE GOING TO BE INSTALLED. |
| IF STIFFNER FLANGES ARE REQUIRED, IF SO MINIMUM LENGTH, |
| 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 1C) ALSO FOUND IN THE SAME FLOOR INFILL, BRIDING |
| REQUIREMENTS FOUND UNDER REQUIREMENT # 3 OF UL G556. |
| 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 1D) THE PLANS FOR THE INFILL FLOOR ASSEMBLY SHOW THE |
| USE OF A RESILIENT CHANNEL RC-1 OR EQUAVALENT 107.2.1 |
| CAN NOT USE OR THE PLANS HAVE TO BE SPECIFIC. |
| |
| 1E) THE PLANS FOR THE INFILL FLOOR ASSEMBLY SHOW THE |
| USE OF A RESILIENT CHANNEL DOES NOT SHOW THE CENTER TO |
| CENTER OF THE CHANNELS NOR TYPE OF FASTENER. |
| |
| 2) THE COVERSHEET ALSO INDICATES UPDATING THE CORRIDOR |
| WALL WITH STOREFRONT WINDOW AND DOOR SYSTEMS, BUT DOES |
| NOT PROVIDE ANY INFORMATION AS TO DESIGN FOR LIFE |
| SAFETY FOR THIS FLOOR, NO LIFE SAFETY PLAN WAS |
| INCLUDED. WHAT FACTORS ARE IN PLACE THAT WILL ALLOW |
| THIS FLOOR TO BE A NON-FIRE RATED EXIT ACCESS COORIDOR |
| (FBC-B TABLE 1015.1 & TABLE 1016.1 )? HOW FAR FROM THE |
| FURTHEST POINT ON THE FLOOR TO AN EXIT TABLE 1016.1?AND |
| SINCE THERE ARE ELEVATORS, WHY NO ELEVATOR LOBBIES |
| (708.14.1 IN PLACE OR EXCEPTIONS)? NO OCCUPANCY |
| CLASSIFICATION FOR THIS FLOOR HAS BEEN DECLARED, IS |
| THIS A MIXED OCCUPANCY? ARE OCCUPANCY SEPARATION WALLS |
| REQUIRED AND WHERE? FBC-B 508.2.4. |
| |
| 3) SHEET A1.1 SHOWS VARIOUS GYMS ON THIS FLOOR PLEASE |
| PROVIDE THE SQUARE FOOTAGE OF EACH AREA AND OCCUPANT |
| LOAD AT 15 SQ.FT./ OCCUPANT SINCE THERE IS NO |
| EQUIPMENT. NOTE WHEN THERE IS OVER 49 OCCUPANTS IN A |
| ROOM FBC-B TABLE 1015.1 REQUIRES A 2ND MEANS OF EGRESS |
| OUT OF THE ROOM. |
| |
| 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |
| |