Plan Review Details - Permit 15060473
Plan Review Stops For Permit 15060473
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-09-23 Cont ID  
Sent By jwitmer Date 2015-09-23 Time 06:30 Rev Time 0.00
Received By jwitmer Date 2015-09-23 Time 06:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-08-21 Cont ID  
Sent By jwitmer Date 2015-08-21 Time 14:07 Rev Time 0.00
Received By jwitmer Date 2015-08-21 Time 13:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-06-19 Cont ID  
Sent By jwitmer Date 2015-06-19 Time 09:01 Rev Time 0.00
Received By jwitmer Date 2015-06-19 Time 07:16 Sent To  
Notes
2015-06-19 07:59:55BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15060473
 ADD: 525 S. FLAGLER DR. 5TH FLOOR WELLNESS AREA
 CONT: URBAN BUILDING CONCEPTS
 TEL: ( 561)727-8343
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. JUNE 19/ 2015
 ACTION: DENIED
  
 1) SHEET S1-1 DETAIL # 1 INDICATES THE USE OF HU410 OR
 HUC410 BUCKETS TO TO SECURED TO THE CONCRETE SLAB .
 THERE ARE (2) ISSUES:
 1A) THE USE OF OR CAN NOT BE USED. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS. . SUCH DRAWINGS AND
 SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION.
  
 1B) SHEET A1-1 DETAIL # 1 INDICATES THE USE OF UL
 LISTING G556 A UNRESTRAINED FLOOR / CEILING ASSEMBLY.
 REQUIREMENT NOTE # 2 DEALS WITH THE METAL JOIST AND
 CLIP ASSEMBLIES. THE HANGER BUCKETS ARE NOT PART OF
 THIS ASSEMBLY. PLEASE IDENTIFY WHICH PARTS OF THIS
 ASSEMBLY ARE GOING TO BE INSTALLED. WITHAPPROPRIATE RIM
 JOIST OR IF THE CLIP ANGLES ARE GOING TO BE INSTALLED.
 IF STIFFNER FLANGES ARE REQUIRED, IF SO MINIMUM LENGTH,
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 1C) ALSO FOUND IN THE SAME FLOOR INFILL, BRIDING
 REQUIREMENTS FOUND UNDER REQUIREMENT # 3 OF UL G556.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 1D) THE PLANS FOR THE INFILL FLOOR ASSEMBLY SHOW THE
 USE OF A RESILIENT CHANNEL RC-1 OR EQUAVALENT 107.2.1
 CAN NOT USE OR THE PLANS HAVE TO BE SPECIFIC.
  
 1E) THE PLANS FOR THE INFILL FLOOR ASSEMBLY SHOW THE
 USE OF A RESILIENT CHANNEL DOES NOT SHOW THE CENTER TO
 CENTER OF THE CHANNELS NOR TYPE OF FASTENER.
  
 2) THE COVERSHEET ALSO INDICATES UPDATING THE CORRIDOR
 WALL WITH STOREFRONT WINDOW AND DOOR SYSTEMS, BUT DOES
 NOT PROVIDE ANY INFORMATION AS TO DESIGN FOR LIFE
 SAFETY FOR THIS FLOOR, NO LIFE SAFETY PLAN WAS
 INCLUDED. WHAT FACTORS ARE IN PLACE THAT WILL ALLOW
 THIS FLOOR TO BE A NON-FIRE RATED EXIT ACCESS COORIDOR
 (FBC-B TABLE 1015.1 & TABLE 1016.1 )? HOW FAR FROM THE
 FURTHEST POINT ON THE FLOOR TO AN EXIT TABLE 1016.1?AND
 SINCE THERE ARE ELEVATORS, WHY NO ELEVATOR LOBBIES
 (708.14.1 IN PLACE OR EXCEPTIONS)? NO OCCUPANCY
 CLASSIFICATION FOR THIS FLOOR HAS BEEN DECLARED, IS
 THIS A MIXED OCCUPANCY? ARE OCCUPANCY SEPARATION WALLS
 REQUIRED AND WHERE? FBC-B 508.2.4.
  
 3) SHEET A1.1 SHOWS VARIOUS GYMS ON THIS FLOOR PLEASE
 PROVIDE THE SQUARE FOOTAGE OF EACH AREA AND OCCUPANT
 LOAD AT 15 SQ.FT./ OCCUPANT SINCE THERE IS NO
 EQUIPMENT. NOTE WHEN THERE IS OVER 49 OCCUPANTS IN A
 ROOM FBC-B TABLE 1015.1 REQUIRES A 2ND MEANS OF EGRESS
 OUT OF THE ROOM.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-06-23 Cont ID  
Sent By rlecky Date 2015-06-23 Time 13:03 Rev Time 0.00
Received By rlecky Date 2015-06-23 Time 12:59 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2015-09-21 Cont ID  
Sent By pleduc Date 2015-09-21 Time   Rev Time 0.00
Received By pleduc Date 2015-09-18 Time 14:51 Sent To B
Notes
2015-09-21 12:55:16THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THE SPRINKLER DESIGN SHALL PROVIDE PROTECTION FOR EACH
 WINDOW PANE PER NFPA 13.
  
 SEPARATE SHOP DRAWINGS SHALL BE SUBMITTED.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-08-17 Cont ID  
Sent By pleduc Date 2015-08-17 Time   Rev Time 0.00
Received By pleduc Date 2015-08-17 Time 15:08 Sent To  
Notes
2015-08-20 10:26:13JWITMER'S DESK
2015-08-17 15:10:28THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF THE
 FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE AND
 COMPLIANCE. ANY REMOVAL AND/OR CONSTRUCTION OF WALLS
 REQUIRES AN EVALUATION.
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-06-12 Cont ID  
Sent By pleduc Date 2015-06-12 Time   Rev Time 0.00
Received By pleduc Date 2015-06-12 Time 14:17 Sent To  
Notes
2015-06-12 14:50:36THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THE REPLACEMENT GLAZING AND DOORS OF THE ELEVATOR
 LOBBY CORRIDOR WALL SHALL BE FIRE RATED AND EQUAL TO
 THE PROTECTION OF THE EXISTING CORRIDOR WALLS AND
 ELEVATOR LOBBY.
  
 2) THE FINSIHED FLOOR PLAN OF THE CABANA LEVEL IS NOT
 CLEARLY INDCATED IN THE DRAWINGS.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-09-23 Cont ID  
Sent By jwitmer Date 2015-09-23 Time 06:30 Rev Time 0.00
Received By jwitmer Date 2015-09-17 Time 11:51 Sent To  
Notes
2015-09-22 07:18:499/22 TO JW DESK
  
  
2015-09-17 11:51:36RESUB ROUTED TO FIRE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-08-21 Cont ID  
Sent By jwitmer Date 2015-08-21 Time 14:08 Rev Time 0.00
Received By jwitmer Date 2015-08-13 Time 15:23 Sent To  
Notes
2015-08-13 15:23:43B12

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-08-13 Cont ID  
Sent By lmarchan Date 2015-07-06 Time 15:22 Rev Time  
Received By lmarchan Date 2015-06-10 Time   Sent To  
Notes
2015-06-11 09:56:02B-02.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2015-06-19 Cont ID  
Sent By jwitmer Date 2015-06-19 Time 09:01 Rev Time 0.00
Received By jwitmer Date 2015-06-19 Time 09:01 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2015-08-20 Cont ID  
Sent By ccole Date 2015-08-20 Time 07:28 Rev Time 0.00
Received By ccole Date 2015-08-20 Time 07:14 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-07-06 Cont ID  
Sent By ccole Date 2015-07-06 Time 07:54 Rev Time 0.00
Received By ccole Date 2015-07-06 Time 07:54 Sent To  
Notes
2015-07-06 08:03:501ST REVIEW: FBC 2010 MECHANICAL
  
 1) REFERENCE TABLE 403.3 MINIMUM VENTILATION RATES:
 PROVIDE VENTILATION CALCULATIONS FOR THE NEW EXERCISE
 ROOMS. INDICATE ON THE PLAN THE REQUIRED O/A CFM'S PER
 THE TABLE AND THE AMOUNT OF CFM'S PROVIDED BY THE
 EXISTING SYSTEM. PROVIDE DRAWINGS AND DETAILS FOR ANY
 REQUIRED MODIFICATIONS TO THE EXISTING SYSTEM.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2015-07-01 Cont ID  
Sent By tklarge Date 2015-07-01 Time 06:36 Rev Time 0.00
Received By tklarge Date 2015-07-01 Time 06:28 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2015-06-22 Cont ID  
Sent By ajones Date 2015-06-22 Time 14:58 Rev Time 0.00
Received By ajones Date 2015-06-22 Time 14:57 Sent To  
Notes
***NONE***