Plan Review Stops For Permit 15060346 |
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2015-06-23 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2015-06-23 |
Time |
11:26 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2015-06-23 |
Time |
10:58 |
Sent To |
I |
|
Notes |
2015-06-23 11:26:39 | THOUGH YOUR SUBMITTED PLANS FOR PERMITTING DO NOT | | COMPLY WITH THE MINIMUM DIMENSIONING REQUIREMENTS OF | | THE FBC, I WILL ACCEPT THEM AS THIS IS ONLY FOR THE | | DEMO OF ALREADY EXISTING APPARATUS. WHAT YOU FAIL TO | | INDICATE ON THE DRAWINGS IS WHAT WILL BE DONE WITH THE | | ELECTRICAL FEEDING THIS EQUIPMENT. THEREFORE AS PER MY | | TELEPHONE CONVERSATION WITH MR. BRIAN PERALTO OF CSI | | COMMUNICATIONS, ALL THE FEEDERS WILL BE REMOVED BACK TO | | THEIR ORIGIN AND CAPPED OFF THERE. ALL UNUSED OPENINGS | | SHALL BE CAPPED AS REQUIRED BY THE 2008 EDITION OF THE | | NEC. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2015-06-23 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2015-06-23 |
Time |
11:26 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2015-06-09 |
Time |
10:21 |
Sent To |
|
|
Notes |
2015-06-23 11:27:14 | SMALL READY "C" | 2015-06-09 10:22:07 | <5000 ELEC |
|
|
|