Plan Review Details - Permit 15060333
Plan Review Stops For Permit 15060333
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-08-03 Cont ID  
Sent By rmcdouga Date 2015-08-03 Time 15:07 Rev Time 0.00
Received By rmcdouga Date 2015-08-03 Time 15:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-06-12 Cont ID  
Sent By rmcdouga Date 2015-06-12 Time 10:35 Rev Time 0.00
Received By rmcdouga Date 2015-06-12 Time 10:35 Sent To  
Notes
2015-06-12 10:41:59PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO COPIES OF A SURVEY. FBC 107.2.1
  
 2) SHOW COMPLIANCE WITH FBC R4101.17 RESIDENTIAL
 SWIMMING POOL BARRIER REQUIREMENTS.
  
 3) SPECIFY THE DECK MATERIAL AND THE DIMENSIONS OF THE
 DECK ON THE PLANS. FBC 107.2.1
  
 4) A POOL PERMIT WILL NOT BE ISSUED UNTIL THE POOL
 PLUMBING AND ELECTRICAL SUB-PERMITS ARE SUBMITTED.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2015-06-09 Cont ID  
Sent By spalmer Date 2015-06-09 Time 08:17 Rev Time 0.00
Received By spalmer Date 2015-06-09 Time 08:17 Sent To  
Notes
2015-06-09 08:17:21ROUTED TO ZONING

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-08-03 Cont ID  
Sent By rmcdouga Date 2015-08-03 Time 17:34 Rev Time 0.00
Received By rmcdouga Date 2015-08-03 Time 17:34 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-06-12 Cont ID  
Sent By rmcdouga Date 2015-06-12 Time 11:01 Rev Time 0.00
Received By rmcdouga Date 2015-06-12 Time 11:01 Sent To  
Notes
2015-06-12 11:01:31PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010 & NEC 2008
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY ELECTRICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PROVIDE TWO SETS OF ELECTICAL PLANS FOR THE POOL
 WITH THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE
 FOR THE DESIGN. SPECIFY ALL CONDUIT AND WIRE SIZES ON
 THE PLANS. FBC 107.2.1
  
 2) SHOW COMPLIANCE WITH NEC 680.26 FOR EQUIPOTENTIAL
 BONDING.
  
 3) SHOW COMPLIANCE WITH NEC 680.8 AND 680.10 FOR
 OVERHEAD CONDUCTOR CLEARANCES AND UNDERGROUND WIRING
 LOCATIONS.
  
 4) SHOW COMPLIANCE WITH NEC 680.22 FOR AREA LIGHTING,
 RECEPTACLES AND EQUIPMENT.
  
 5) SHOW COMPLIANCE WITH FBC ENERGY CONSERVATION SECTION
 403.9.2 TIME SWITCHES.
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2015-06-12 Cont ID  
Sent By tklarge Date 2015-06-12 Time 08:12 Rev Time 0.00
Received By tklarge Date 2015-06-12 Time 08:10 Sent To  
Notes
2015-06-12 08:14:17A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS AND GAS RISER THAT REFLECTS THE
 ENTIRE SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC
 SEC. 107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-08-11 Cont ID  
Sent By tklarge Date 2015-08-11 Time 10:46 Rev Time 0.00
Received By tklarge Date 2015-08-11 Time 10:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-08-04 Cont ID  
Sent By tklarge Date 2015-08-04 Time 06:54 Rev Time 0.00
Received By tklarge Date 2015-08-03 Time 13:40 Sent To  
Notes
2015-08-03 13:40:19SGRAHAM DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-06-12 Cont ID  
Sent By rmcdouga Date 2015-06-12 Time 11:01 Rev Time 0.00
Received By rmcdouga Date 2015-06-09 Time 08:18 Sent To  
Notes
2015-06-12 08:33:46ONE SET OF PLANS IS BEING RETAINED BY THE BUILDING
 DIVISION FOR ENGINEERING BOARD REVIEW. T.LARGE
2015-06-09 08:18:12ROUTED TO ZONING

Review Stop P PLUMBING
Rev No 3 Status P Date 2015-08-11 Cont ID  
Sent By tklarge Date 2015-08-11 Time 10:45 Rev Time 0.00
Received By tklarge Date 2015-08-11 Time 10:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-08-10 Cont ID  
Sent By tklarge Date 2015-08-04 Time 06:53 Rev Time 0.00
Received By tklarge Date 2015-08-04 Time 05:50 Sent To  
Notes
2015-08-04 06:27:131) COMPLY WITH 2010 FBC-R R4101.6.3 FOR WATER VELOCITY.
 2) SUBMIT DETAILS FOR ENTRAPMENT PROTECTION. FBC-R
 SEC.R4101.6.6.
 3) WATER SUPPLY SHALL COMPLY WITH 2010 FBC-R SEC.
 R4101.9.
 4) COMPLY WITH 2010 FBC- R SEC.R4101.10.WHERE IS THE
 POOL DISCHARGE/WASTE LINE?
 5) THE GENERAL CONTRACTOR SHALL ONLY CONSTRUCT THE POOL
 SHELL PER F.S. 489.113 (3)(C).
 6) THE POOL PIPING PLAN SHOWS A "FLOOR DRAIN" BUT THERE
 IS NO PIPING TO IT. CLARIFY.
 7) THE POOL RETURN IS SHOWN AS 2 INCH ON THE PLUMBING
 SCHEDULE AND AS 1 1/2 INCH ON THE RETURN DETAIL. WHICH
 IS IT? CLARIFY.
 8) SUBMIT MANUF. SPECIFICATION SHEETS FOR THE MAIN
 DRAIN COVER.THE COVER SHALL COMPLY WITH ASME/ANSI
 A112.19.8 PER APSP 7 SEC.4.5.
 9) SUPPLY THE TOTAL DYNAMIC HEAD CALCULATIONS TO
 DETERMINE THE MAXIMUM FLOW RATE OF THE PUMP.APSP 7
 SEC.4.4.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-06-12 Cont ID  
Sent By tklarge Date 2015-06-12 Time 08:06 Rev Time 0.00
Received By tklarge Date 2015-06-12 Time 06:06 Sent To  
Notes
2015-06-12 08:06:111) THE SUBMITTED PLANS ARE SEVERELY DEFICIENT WITH THE
 REQUIRED CODE INFORMATION THAT A THOROUGH,
 COMPREHENSIVE PLUMBING REVIEW COULD NOT BE
 ACCOMPLISHED. THE DESIGN OF THE SWIMMING POOL SHALL
 COMPLY WITH THE FOLLOWING STANDARDS AND CODE SECTIONS:
 2010 FBC-R SECS.R4101.6.1,
 ANSI/NSPI3, ANSI/NSPI 4, ANSI/NSPA 5,ANSI/NSPI 6,
 ANSI/APSP-7.
 2) COMPLY WITH 2010 FBC-R R4101.6.3 FOR WATER VELOCITY.
 SUBMIT DETAILS.
 3) SUBMIT DETAILS FOR ENTRAPMENT PROTECTION. FBC-R
 SEC.R4101.6.6.
 4) SUBMIT DETAILS, MANUF. SPEC SHEETS & PUMP
 PERFORMANCE CURVE.2010 WPB AMEND. TO 2010 FBC SEC.
 107.2.1.
 5) COMPLY W/ 201 FBC-R SEC.R4101.7.1.
 6) COMPLY W/ 2010 FBC- R SEC.R4101.8.2.
 7) WATER SUPPLY SHALL COMPLY WITH 2010 FBC-R SEC.
 R4101.9.
 8) COMPLY WITH 2010 FBC- R SEC.R4101.10.
 9) COMPL WITH 2010 FBC-R SEC.R4101.20.
 10) COMPLY WITH 2010 FBC-R SEC.R4101.21.2.
 11) THE PLANS SHALL COMPLY WITH FL. ADMIN. CODE RULE
 61G15-23.002 (2)(B)(3).
 12) THE GENERAL CONTRACTOR SHALL ONLY CONSTRUCT THE
 POOL SHELL PER F.S. 489.113 (3)(C).
 13) IDENTIFY ALL THE RETURNS ON THE PIPING PLAN. 2010
 WPB AMEND. TO 2010 FBC SEC. 107.2.1.
  
 NOTE: ONE SET OF PLANS IS BEING RETAINED BY THE
 BUILDING DIVISION.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2015-08-03 Cont ID  
Sent By sgraham Date 2015-08-03 Time 14:35 Rev Time 0.00
Received By sgraham Date 2015-08-03 Time 14:35 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2015-06-11 Cont ID  
Sent By sgraham Date 2015-06-11 Time 11:22 Rev Time 0.00
Received By sgraham Date 2015-06-11 Time 11:22 Sent To B
Notes
2015-06-12 11:10:406/11/15 ZONING FAILED
  
 1. SUBMIT TWO UP TO DATE SURVEYS SHOWING LOCATION OF
 POOL