Plan Review Details - Permit 15060319
Plan Review Stops For Permit 15060319
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-10-29 Cont ID  
Sent By eschneid Date 2015-10-29 Time 14:57 Rev Time 0.00
Received By jwitmer Date 2015-10-29 Time 06:26 Sent To  
Notes
2015-10-29 06:50:25BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15060319
 ADD: 400 N. FLAGLER DR.
 CONT:MURRAY LOGAN CONSTRUCTION
 TEL: (561)686-3948
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: THURS. OCT29/ 2015
  
 ACTION: BUILDING PROVISO
 BUILDING APPROVED WITH EXCEPTION!
  
  
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 THE HOLDER OF SUCH PERMIT FOR FLOATING DOCK & PILING
 ARE PROCEDING AT THEIR OWN RISK. 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION, 107.3.3.
  
 NEITHER YOUR THREE PLAN SHEETS NOR THE SUBMITTED
 MARINETEK DRAWINGS PROVIDE NOTES OR DETAILS DESCRIBING
 THE PROPOSED MATERIAL, OR MATERIAL THICKNESS, FOR THE
 20 INCH DIA. PILES, OR DETAILS OF THE INTERNAL PILE
 GUIDES FOR THE PILES, OR DETAILS OF THE "STEEL
 CONNECTOR BRACKET" REFERENCED ON SHEET 0127GL01 FOR
 ATTACHMENT OF THE ANGLED FINGER PONTOON (NEAREST TO THE
 SEAWALL). YOUR DRAWING SHEET # 2, SEEMS TO SHOW A PILE
 AT EACH OF THE TWO NEW TRANSFORMER LOCATIONS. PLEASE
 PROVIDE A DETAIL OF THE PILE GUIDE AT THESE LOCATIONS.
 FOR US TO ISSUE A PERMIT WITH PROVISOS / CONDITIONS
 YOUR LETTER SHALL ALSO ACKNOWLEDGE THAT YOU WILL BE
 REQUIRED TO REVISE YOUR PLANS IMMEDIATELY TO
 INCORPORATE DETAILS FOR THESE FOUR ITEMS AND SUBMIT THE
 REVISED PLANS FOR OUR REVIEW AND STAMP BEFORE
 INSPECTION.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-10-27 Cont ID  
Sent By jwitmer Date 2015-10-27 Time 15:44 Rev Time 0.00
Received By jwitmer Date 2015-10-27 Time 11:59 Sent To  
Notes
2015-10-27 15:44:20BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15060319
 ADD: 400 N. FLAGLER DR.
 CONT:MURRAY LOGAN CONSTRUCTION
 TEL: (561)686-3948
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. OCT27/ 2015
 ACTION: DENIED
  
 1) THE STRUCTURAL DESIGN FOR THE FLOATING DOCK AND
 FINGER PIERS APPERA TO BE PRELIMINARY PLANS. SEE THE
 FOLLOWING SHEETS ARE NOT SIGNED NOR SEALED.
 1A) THEORETICAL FREEBOARD (NOMINAL) AT DEAD LOAD
 WITHOUT UTILITIES
 1B) DOCK E EXTENSION
 1C) FIXING SET INSTALATION SY
 1D) CONNECTION DETAIL (DET1)
 1E) SUPER YAUCHT BOLLARD 7.5 TN
 1F) MEGA YAUCHT BOLLARD 10 TN
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. FL ADMIN
 CODE 61G15-23.002 ENGINEERS
  
 SUBMITTED ALSO 1 BOOKLET OF CALCULATIONS BY CLE
 ENGINEERING. PLEASE NOTE THIS BOOK IS 1 1/2 INCHES
 THICK OF VARIOUS CALCULATIONS AND DOCUMENTS. PLEASE
 PROVIDE EITHER 2 OF THESE BOOKS SIGNED AND
 SEALEDCOMPLYING WITH: 61G15-23.002(2) FL. ADMIN. CODE.
 A COVER SHEET OR INDEX SHEET FOR ENGINEERING
 SPECIFICATIONS MAY BE USED AND THAT SHEET MUST BE
 SIGNED IN RESPONSIBLE CHARGE OF THE PRODUCTION &
 PREPARATION OF EACH SECTION OF THE ENGINEERING
 SPECIFICATION WITH SUFFICIENT INFORMATION ON THE COVER
 SHEET OR INDEX LISTING HOW MANY PAGES ARE COVERED UNDER
 THE COVER SHEET OR INDEX SHEET. .
  
 PLEASE ALSO NOTE PAGE (1) OF THIS BOOK IS SIGNED AND
 SEALED THE LAST PARAGRAPH READS: ONCE THE PACKAGE HAS
 BEEN REVIEWED, WE WILL PROVIDE A FULL PRINTED AND
 SEALED FINAL PACKAGE. PLEASE PROVIDE.
  
  
 2) PROVIDE WIND DESIGN CRITERIA 2010 FBC-B 1603.1.4.
  
 3) PLEASE PROVIDE THE STRUCTURAL DESIGN IN COMPLIANCE
 WITH ASCE 7-10. 1604.1 & 1604.2.
  
 4) NO INFORMATION WAS PROVIDED FOR THE PILING THAT WILL
 HOLD THE DOCK IN PLACE AND KEEP IT FROM SLIPPING
 LATERALLY BY EITHER WIND AND OR WATER. 2010 FBC-B
 1803.5.5 DEEP FOUNDATIONS.
  
 5) REFERS BACK TO COMMENT # 1. STRUCTURAL PLANS WILL BE
 REQUIRED TO BE DESIGNED BY A FLORIDA REGISTERED
 ENGINEER. PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND BEING
 FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE
 DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
 EFFECTIVE DATE 05/06/2009
 (2)(A) EVERY SHEET OF PLANS AND PRINTS WHICH MUST BE
 SEALED UNDER THE PROVISIONS OF CHAPTER 471, F.S., SHALL
 BE SEALED, SIGNED AND DATED BY THE PROFESSIONAL
 ENGINEER IN RESPONSIBLE CHARGE.
  
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-06-25 Cont ID  
Sent By jwitmer Date 2015-06-25 Time 10:03 Rev Time  
Received By jwitmer Date 2015-06-25 Time   Sent To  
Notes
2015-06-25 10:17:50BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15060319
 ADD: 400 N. FLAGLER DR.
 CONT:MURRAY LOGAN CONSTRUCTION
 TEL: (561)686-3948
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. OCT27/ 2015
 ACTION: DENIED
  
 1) THE STRUCTURAL DESIGN FOR THE FLOATING DOCK AND
 FINGER PIERS APPERA TO BE PRELIMINARY PLANS. SEE THE
 FOLLOWING SHEETS ARE NOT SIGNED NOR SEALED.
 1A) THEORETICAL FREEBOARD (NOMINAL) AT DEAD LOAD
 WITHOUT UTILITIES
 1B) DOCK E EXTENSION
 1C) FIXING SET INSTALATION SY
 1D) CONNECTION DETAIL (DET1)
 1E) SUPER YAUCHT BOLLARD 7.5 TN
 1F) MEGA YAUCHT BOLLARD 10 TN
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. FL ADMIN
 CODE 61G15-23.002 ENGINEERS
  
 SUBMITTED ALSO 1 BOOKLET OF CALCULATIONS BY CLE
 ENGINEERING. PLEASE NOTE THIS BOOK IS 1 1/2 INCHES
 THICK OF VARIOUS CALCULATIONS AND DOCUMENTS. PLEASE
 PROVIDE EITHER 2 OF THESE BOOKS SIGNED AND
 SEALEDCOMPLYING WITH: 61G15-23.002(2) FL. ADMIN. CODE.
 A COVER SHEET OR INDEX SHEET FOR ENGINEERING
 SPECIFICATIONS MAY BE USED AND THAT SHEET MUST BE
 SIGNED IN RESPONSIBLE CHARGE OF THE PRODUCTION &
 PREPARATION OF EACH SECTION OF THE ENGINEERING
 SPECIFICATION WITH SUFFICIENT INFORMATION ON THE COVER
 SHEET OR INDEX LISTING HOW MANY PAGES ARE COVERED UNDER
 THE COVER SHEET OR INDEX SHEET. .
  
 PLEASE ALSO NOTE PAGE (1) OF THIS BOOK IS SIGNED AND
 SEALED THE LAST PARAGRAPH READS: ONCE THE PACKAGE HAS
 BEEN REVIEWED, WE WILL PROVIDE A FULL PRINTED AND
 SEALED FINAL PACKAGE. PLEASE PROVIDE.
  
  
 2) PROVIDE WIND DESIGN CRITERIA 2010 FBC-B 1603.1.4.
  
 3) PLEASE PROVIDE THE STRUCTURAL DESIGN IN COMPLIANCE
 WITH ASCE 7-10. 1604.1 & 1604.2.
  
 4) NO INFORMATION WAS PROVIDED FOR THE PILING THAT WILL
 HOLD THE DOCK IN PLACE AND KEEP IT FROM SLIPPING
 LATERALLY BY EITHER WIND AND OR WATER. 2010 FBC-B
 1803.5.5 DEEP FOUNDATIONS.
  
 5) REFERS BACK TO COMMENT # 1. STRUCTURAL PLANS WILL BE
 REQUIRED TO BE DESIGNED BY A FLORIDA REGISTERED
 ENGINEER. PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND BEING
 FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE
 DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
 EFFECTIVE DATE 05/06/2009
 (2)(A) EVERY SHEET OF PLANS AND PRINTS WHICH MUST BE
 SEALED UNDER THE PROVISIONS OF CHAPTER 471, F.S., SHALL
 BE SEALED, SIGNED AND DATED BY THE PROFESSIONAL
 ENGINEER IN RESPONSIBLE CHARGE.
  
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-10-27 Cont ID  
Sent By dharvey Date 2015-10-27 Time 10:06 Rev Time 0.00
Received By dharvey Date 2015-10-27 Time 08:12 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-08-21 Cont ID  
Sent By dharvey Date 2015-08-21 Time 12:07 Rev Time 0.00
Received By dharvey Date 2015-08-20 Time 13:02 Sent To  
Notes
2015-08-21 12:07:29REVIEWED BY DOUG HARVEY UNDER 15070489.
2015-08-20 15:33:51DEFERRED REVIEW TO DISCUSS MULTIPLE PERMITS W/DOUG
 HARVEY

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2015-10-28 Cont ID  
Sent By cranford Date 2015-10-28 Time 15:17 Rev Time 0.00
Received By cranford Date 2015-10-28 Time 15:02 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2015-07-06 Cont ID  
Sent By cranford Date 2015-07-06 Time 09:43 Rev Time 0.00
Received By cranford Date 2015-07-02 Time 14:51 Sent To  
Notes
2015-07-06 08:41:191. THE SUBMITTED DESIGN PLANS WERE NOT SIGNED OR SEALED
 BY A LICENSED PROFESSIONAL (ARCHITECT OR PROFESSIONAL
 ENGINEER. PLEASE SUBMIT SIGNED AND SEALED PLANS. (FAC
 61G15-23.002, FS 481.221 AND 481.321)
  
 2. PLEASE SUBMIT A COPY OF THE CONSENT OF EASEMENT FROM
 THE ARMY CORPS OF ENGINEERS. (SPECIAL CONDITION 5 OF
 SAJ-2002-03636)
  
 3. SHOW THE SUBMERGED LAND LEASE BOUNDARY OF THE FINGER
 DOCK PLANS.
  
 4. PLEASE SHOW THE LOCATION OF THE CITY'S NORTHERN DOCK
 ON THE CONSTRUCTION PLANS.
  
 5. SHEET 4 OF THE SAJ PERMIT EXHIBITS INDICATES THAT
 THE CITY'S NORTHERN PUBLIC DOCK WILL BE REMOVED AND
 RELOCATED. WHEN IS THE CITY DOCK PROPOSED TO BE
 REMOVED?
  
 6. PLEASE SUBMIT SIGNED COPIES OF THE SAJ AND DEP
 PERMITS.
  
  
 KELLY CRANFORD, P.E.
 LAND DEVELOPMENT ENGINEER
 PUBLIC WORKS DEPARTMENT
 CITY OF WEST PALM BEACH
 [email protected]
 561-494-1098 (OFFICE)
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-06-22 Cont ID  
Sent By pleduc Date 2015-06-22 Time   Rev Time 0.00
Received By pleduc Date 2015-06-12 Time 09:09 Sent To  
Notes
2015-06-22 13:34:10THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THE CONSTRUCTION PROJECT SHALL COMPLY WITH THE
 APPROPRIATE PROVISIONS OF NFPA 303, FIRE PROTECTION
 STANDARD FOR MARINAS AND BOATYARDS, 2011 EDITION.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-10-28 Cont ID  
Sent By skennedy Date 2015-10-28 Time 16:00 Rev Time 0.00
Received By skennedy Date 2015-10-14 Time 12:45 Sent To  
Notes
2015-10-14 12:47:23C36

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-10-14 Cont ID  
Sent By cpuell Date 2015-07-21 Time 12:45 Rev Time 0.00
Received By cpuell Date 2015-06-09 Time 15:33 Sent To  
Notes
2015-06-09 15:33:49C10

Review Stop Z ZONING
Rev No 2 Status P Date 2015-10-29 Cont ID  
Sent By eschneid Date 2015-10-28 Time 15:27 Rev Time 0.50
Received By eschneid Date 2015-10-28 Time 15:27 Sent To B
Notes
2015-10-28 15:52:10CONDITIONAL PASS - CONTRACTOR PROCEEDS AT OWN RISK
 UNTIL CONDITIONS SUFFICIENTLY ADDRESSED.
  
 THE FOLLOWING ITEMS SHALL BE CORRECTED/ADDRESSED AS
 PART OF A PERMIT REVISION PRIOR TO THE FINAL INSPECTION
 (104) APPROVAL.
  
 1) THE DOCK INSTALLATION PLANS SHALL CLEARLY DESIGNATE
 THE NEW SOUTHERN BOUNDARY OF THE LEASE LINE. THE PIERS,
 NOR ANY BOATS DOCKED AT THE PIERS MAY EXTEND PAST THE
 LEASE LINE.
  
 2) THE DEP PERMIT AND THE SITE PLAN APPROVED PLANS SHOW
 PIERS THAT ARE 160 FEET LONG (MAXIMUM), WHILE THE
 MARINETEK PLANS SHOW THE LONGEST PIERS AT 160 FEET 5
 INCHES. PLEASE EXPLAIN.
  
 3) THE PROPOSED IMPROVEMENT PLAN BY BOLCHOZ MARINE
 ADVISOR'S, INC., SHOWS THE SOUTHERN MOST ANCHOR PILE AT
 THE END OF THE DOCK, YET THE MAINETEK PLANS SHOW THE
 PILE WITHIN THE DOCK. ALL PLANS SHALL SHOW THE SAME
 CONDITION.
  
 4) SHEET E-1 SHOWS A SLIP E200. THIS SLIP IS NOT
 APPROVED AS PART OF THE DEP APPROVAL AND SHALL BE
 REMOVED FROM THE PLANS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.

Review Stop Z ZONING
Rev No 1 Status F Date 2015-07-21 Cont ID  
Sent By eschneid Date 2015-07-21 Time 15:12 Rev Time 0.25
Received By eschneid Date 2015-07-21 Time 15:12 Sent To  
Notes
2015-08-20 09:31:51ON MALBERAN'S DESK
2015-07-21 15:34:57FAILED
  
 THE DOCK LAYOUT HAS NOT BEEN APPROVED THROUGH THE
 PLANNING DIVISION REVIEW PROCESS. UNTIL THE REVIEW HAS
 OCCURRED, AFTER AN APPLICATION TO THE PLANNING DIVISION
 HAS BEEN FILED, NO ZONING REVIEW WILL BEGIN ON THE DOCK
 PLANS.
  
 THIS DOES NOT COUNT AS ONE OF THE ZONING REVIEW CYCLES.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
  