Plan Review Details - Permit 15060261
Plan Review Stops For Permit 15060261
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2015-06-29 Cont ID  
Sent By skennedy Date 2015-06-29 Time 14:41 Rev Time 0.00
Received By skennedy Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-06-11 Cont ID  
Sent By skennedy Date 2015-06-29 Time 14:41 Rev Time 0.00
Received By dhayes Date 2015-06-11 Time 10:53 Sent To B
Notes
2015-06-11 11:03:14APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN APPROVED
 PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION
 FEE(S).
  
 1) 505.2.4 EXTERIOR LIGHTING CONTROLS.
 LIGHTING FOR ALL EXTERIOR APPLICATIONS NOT EXEMPTED IN
 SECTION 505.1 SHALL HAVE AUTOMATIC CONTROLS CAPABLE OF
 TURNING OFF EXTERIOR LIGHTING WHEN SUFFICIENT DAYLIGHT
 IS AVAILABLE OR WHEN THE LIGHTING IS NOT REQUIRED
 DURING NIGHTTIME HOURS. LIGHTING NOT DESIGNATED FOR
 DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY EITHER A
 COMBINATION OF A PHOTOSENSOR AND A TIME SWITCH, OR AN
 ASTRONOMICAL TIME SWITCH.
  
 2) 2010 FBC-BUILDING SECTION 1609
 PROVIDE WIND LOAD CALCULATIONS FOR ALL LIGHT POLES
 INCLUDING LUMINAIRE IN COMPLIANCE WITH THE FBC 1609
  
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-06-29 Cont ID  
Sent By dhayes Date 2015-06-29 Time 14:41 Rev Time  
Received By skennedy Date 2015-06-05 Time   Sent To E
Notes
2015-06-19 10:09:05ROUTED TO MISC2 FOR BUILDING REVIEW

Review Stop Z ZONING
Rev No 1 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***