Plan Review Details - Permit 15060170
Plan Review Stops For Permit 15060170
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-09-04 Cont ID  
Sent By rmcdouga Date 2015-09-04 Time 10:26 Rev Time 0.00
Received By rmcdouga Date 2015-09-03 Time 17:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-07-29 Cont ID  
Sent By rmcdouga Date 2015-07-29 Time 14:05 Rev Time 0.00
Received By rmcdouga Date 2015-07-28 Time 07:12 Sent To  
Notes
2015-07-28 13:36:50PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PLANS SPECIFY THAT THE EXISTING ASPHALT SHINGLE
 ROOF ON THE MAIN HOUSE IS TO BE REPLACED WITH A
 CONCRETE TILE ROOF. THE EXISTING ROOF IS REQUIRED TO BE
 EVALUATED BY A FLORIDA LICENSED STRUCTURAL ENGINEER TO
 DETERMINE THAT IT IS CAPABLE OF SAFELY SUPPORTING ALL
 LOADS, INCLUDING DEAD LOADS, LIVE LOADS AND WINDS
 LOADS. FBC - R301.1
  
 2) THE ROOF NOTES FOR THE PROPOSED DETACHED GARAGE ON
 A-3 INCORRECTLY STATE REPLACE ASPHALT SHINGLES WITH
 TILE. PLEASE CORRECT. FBC 107.2.1
  
 3) THE WORK THAT IS BEING DONE TO THE EXISTING BUILDING
 INVOLVES RECONFIGURING SPACE AND THE WORK AREA EXCEEDS
 50 PERCENT OF THE BUILDING AREA. THIS CLASSIFIES IT AS
 LEVEL 3 ALTERATION PER FBC EXISTING BUILDING CHAPTER 4.
 THE DESIGN PROFESSIONAL IS REQUIRED TO NOTE THE LEVEL
 OF ALTERATION ON THE PLANS PER SECTION 401.4.
  
 4) THE VALUE OF THE ALTERATION WORK EXCEEDS 30 PERCENT
 OF THE ASSESSED VALUE OF THE STRUCTURE AND IS
 CONSIDERED A RENOVATED BUILDING BY THE 2010 FBC ENERGY
 CONSERVATION. SUBMIT TWO SETS OF ENERGY CALCULATIONS
 SHOWING THAT THE RENOVATED BUILDING COMPLIES WITH THE
 ENERGY CODE. FBC ENERGY CONSERVATION 401.2
  
 5) THE PLANS SPECIFY A 4 PLY 2 X 12 WOOD BEAM AT THE
 OPENING FROM THE DINING ROOM TO THE FAMILY ROOM THAT
 WILL SUPPORT THE ALTERED ROOF TRUSSES. SPECIFY THE
 FOOTING SIZES AND REINFORCEMENT THAT WILL BE REQUIRED
 AT THE LOAD BEARING ENDS OF THIS BEAM. FBC-R301.1
  
 6) THE PRODUCT APPROVAL THAT WAS SUBMITTED HAS THE TWO
 #8 SCREW MECHANICAL ATTACHMENT MARKED. THE PLANS
 SPECIFY A FOAM-ON TILE APPLICATION AND A PRODUCT
 APPROVAL FOR AH-160 FOAM ROOF TILE ADHESIVE WAS
 SUBMITTED. PLEASE CLARIFY THE INSTALLATION THAT WILL BE
 USED.
  
 7) SHOW COMPLIANCE WITH TERMITE PROTECTION AT THE
 PROPOSED GARAGE. FBC - R 318
  
 8) IN DETAIL B ON S-2 THE INTERIOR FOOTING REINFORCING
 BARS ARE REQUIRED TO BE LAPPED AT THE CORNERS LIKE THE
 OUTSIDE BARS IN ORDER TO BE CONTINUOUS.
  
 9) ON SHEET S-2 THE GARAGE FOOTING IS SPECIFIED AS 20"
 X 16" IN THE SCHEDULE AND AT SECTION C IT IS 16" X 16"
 ,AS WELL AS, 1' 4" (16") X 1' 10" (22"). PLEASE CORRECT
 SUCH THAT THE FOOTING SIZES ARE CONSISTENT. FBC 107.2.1
  
 10) SPECIFY THE MAXIMUM SPACING OF THE VERTICALLY
 REINFORCED FILLED CELLS IN THE EXTERIOR WALLS OF THE
 PROPOSED GARAGE. FBC - R 609.3.3
  
 11) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT
 APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION
 INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR EACH OF
 THE SECTIONAL GARAGE DOOR.
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-09-04 Cont ID  
Sent By rmcdouga Date 2015-09-04 Time 08:10 Rev Time 0.00
Received By rmcdouga Date 2015-09-04 Time 07:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-07-27 Cont ID  
Sent By rmcdouga Date 2015-07-27 Time 19:06 Rev Time 0.00
Received By rmcdouga Date 2015-07-27 Time 19:06 Sent To  
Notes
2015-07-28 11:34:23PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010 / 2008 NEC
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY ELECTRICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THERE IS NO WALL SWITCH SHOWN FOR THE SIX HIGH HATS
 IN THE KITCHEN. FBC 107.2.1
  
 2) THE 2/0 CU FEEDERS SHOWN IN THE RISER DIAGRAM ON E-1
 ARE REQUIRED TO HAVE A #4 GROUNDING ELECTRODE
 CONDUCTOR. NEC 250.68
  
 3) ON SHEET E-1, FOUR (4) #12 CU CONDUCTORS ARE
 SPECIFIED ON THE RISER DIAGRAM FOR THE GARDEN SHED. THE
 PANEL SCHEDULE SHOWS ONE 20 AMP CIRCUIT FOR THE GARDEN
 SHED, WHICH REQUIRES TWO (2) #12 CU CONDUCTORS. PLEASE
 CLARIFY. FBC 107.2.1
  
 4) ON THE MAIN HOUSE FLOOR PLAN THERE IS A SWITCHED
 DUPLEX OUTLET SHOWN ON THE LIVING ROOM CEILING. IS THIS
 A TYPO? PLEASE CLARIFY. FBC 107.2.1
  
 5) THE LOAD CALCULATIONS FOR THE HOUSE PANEL APPEARS TO
 HAVE AN ERROR. THE TOTAL CALCULATED LOAD IS 36.5. THE
 FIRST 10 KW AT 100 PERCENT MAKES THE BALANCE 26.5 KW.
 FORTY PERCENT OF 26.5 KW IS 10.6 KW NOT 7.4 KW. PLEASE
 CORRECT. FBC 107.2.1
  
 6) NEC 250.94 - INTERSYSTEM BONDING TERMINATION SHALL
 BE PROVIDED.
  
 7) NEC 250.104(B) THE GAS PIPING IS REQUIRED TO BE
 BONDED.
  
 8) NEC 410.16 (A) - (C) - LUMINAIRES IN CLOTHES CLOSETS
 SHALL BE OF THE TYPE PERMITTED AND LOCATED AS REQUIRED.
  
 9) CLARIFY WHAT IS LOCATED BESIDE THE REFRIGERATOR ON
 THE FAMILY ROOM SIDE. IF IT IS COUNTER SPACE A GFCI
 RECEPTACLE OUTLET IS REQUIRED. NEC 210.52 (3) (C)
  
 10) BOXES USED AT LUMINAIRE OR LAMP HOLDER OUTLETS IN A
 CEILING SHALL BE DESIGNED FOR THE PURPOSE AND SHALL BE
 REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF
 23 KG (50 LB). BOXES USED AT LUMINAIRE OR LAMP HOLDER
 OUTLETS IN A WALL SHALL BE DESIGNED FOR THE PURPOSE AND
 SHALL BE MARKED TO INDICATE THE MAXIMUM WEIGHT OF THE
 LUMINAIRE THAT IS PERMITTED TO BE SUPPORTED BY THE BOX
 IN THE WALL, IF OTHER THAN 23 KG (50 LB). AT EVERY
 OUTLET USED EXCLUSIVELY FOR LIGHTING, THE BOX SHALL BE
 DESIGNED OR INSTALLED SO THAT A LUMINAIRE MAY BE
 ATTACHED. NEC 314.27(A)
  
 11) SMOKE ALARMS SHALL BE LOCATED PER MANUFACTURER'S
 INSTALLATION INSTRUCTIONS AND NFPA 72 SECTION 29.8.3.4.
 (4)*SMOKE ALARMS AND SMOKE DETECTORS SHALL NOT BE
 INSTALLED WITHIN AN AREA OF EXCLUSION DETERMINED BY A
 10 FT (3.0 M) RADIAL DISTANCE ALONG A HORIZONTAL FLOW
 PATH FROM A STATIONARY OR FIXED COOKING APPLIANCE,
 UNLESS LISTED FOR INSTALLATION IN CLOSE PROXIMITY TO
 COOKING APPLIANCES. SMOKE ALARMS AND SMOKE DETECTORS
 INSTALLED BETWEEN 10 FT (3.0 M) AND 20 FT (6.1 M) ALONG
 A HORIZONTAL FLOW PATH FROM A STATIONARY OR FIXED
 COOKING APPLIANCE SHALL BE EQUIPPED WITH AN
 ALARM-SILENCING MEANS OR USE PHOTOELECTRIC DETECTION.
 EXCEPTION: SMOKE ALARMS OR SMOKE DETECTORS THAT USE
 PHOTOELECTRIC DETECTION SHALL BE PERMITTED FOR
 INSTALLATION AT A RADIAL DISTANCE GREATER THAN 6 FT
 (1.8 M) FROM ANY STATIONARY OR FIXED COOKING APPLIANCE
 WHEN THE FOLLOWING CONDITIONS ARE MET:
 (A) THE KITCHEN OR COOKING AREA AND ADJACENT SPACES
 HAVE NO CLEAR INTERIOR PARTITIONS OR HEADERS AND
 (B) THE 10 FT (3.0 M) AREA OF EXCLUSION WOULD PROHIBIT
 THE PLACEMENT OF A SMOKE ALARM OR SMOKE DETECTOR
 REQUIRED BY OTHER SECTIONS OF THIS CODE.
 (5)*SMOKE ALARMS AND SMOKE DETECTORS SHALL NOT BE
 INSTALLED WITHIN A 36 IN. (910 MM) HORIZONTAL PATH FROM
 A DOOR TO A BATHROOM CONTAINING A SHOWER OR TUB.
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2015-07-08 Cont ID  
Sent By tklarge Date 2015-07-08 Time 05:00 Rev Time 0.00
Received By tklarge Date 2015-07-08 Time 04:58 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2015-07-21 Cont ID  
Sent By fmittner Date 2015-07-21 Time 09:58 Rev Time 0.00
Received By fmittner Date 2015-07-21 Time 09:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-09-11 Cont ID  
Sent By rmcdouga Date 2015-09-11 Time 13:39 Rev Time 0.00
Received By rmcdouga Date 2015-09-08 Time 12:55 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-09-04 Cont ID  
Sent By rmcdouga Date 2015-09-04 Time 10:26 Rev Time 0.00
Received By rmcdouga Date 2015-08-20 Time 12:54 Sent To  
Notes
2015-08-20 12:54:59RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-07-29 Cont ID  
Sent By rmcdouga Date 2015-07-29 Time 14:05 Rev Time 0.00
Received By rmcdouga Date 2015-06-03 Time 16:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2015-09-11 Cont ID  
Sent By rmcdouga Date 2015-09-11 Time 13:39 Rev Time 0.00
Received By rmcdouga Date 2015-09-11 Time 13:04 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-09-04 Cont ID  
Sent By rmcdouga Date 2015-09-04 Time 07:31 Rev Time 0.00
Received By rmcdouga Date 2015-09-03 Time 18:58 Sent To  
Notes
2015-09-03 18:58:18PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 2) THE SIZE OF THE SUPPLY DUCT TO BEDROOM #1 IS NOT
 SPECIFIED ON THE PLANS. FBC 107.2.1
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-07-27 Cont ID  
Sent By rmcdouga Date 2015-07-27 Time 10:38 Rev Time 0.00
Received By rmcdouga Date 2015-07-27 Time 10:38 Sent To  
Notes
2015-07-27 10:49:11PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC - 107.3.5.3 PLANS SHOW RELOCATED AIR HANDLER AND
 DIFFERENT ROOM LAYOUT. PROVIDE TWO SETS OF A MECHANICAL
 PLAN TO SHOW DUCT SYSTEM PER FBC-R M16 & BATH EXHAUST
 PER FBC-R M15.
  
 2) FBC-R - M 1602.4 PROVIDE BALANCED AIR RETURN AT
 BEDROOMS.
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-07-08 Cont ID  
Sent By tklarge Date 2015-07-08 Time 04:58 Rev Time 0.00
Received By tklarge Date 2015-07-08 Time 04:28 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2015-07-27 Cont ID  
Sent By rmcdouga Date 2015-07-27 Time 14:51 Rev Time 0.00
Received By rmcdouga Date 2015-07-27 Time 14:51 Sent To  
Notes
2015-07-27 13:44:03ROOFING MATERIALS
  
 - ENTEGRA CONCRETE ROOF TILE , FL7804
 - POLYGLASS POLYSTICK UNDERLAYMENT, NOA NO. 11-0601.10
 - 3M ROOF TILE ADHESIVE AH-160, NOA NO. 14-0805.01
  

Review Stop Z ZONING
Rev No 1 Status P Date 2015-07-21 Cont ID  
Sent By fmitner Date 2015-07-21 Time 09:59 Rev Time 0.00
Received By fmittner Date 2015-07-21 Time 09:58 Sent To  
Notes
***NONE***