2015-06-05 14:57:31 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| |
| 1) THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF |
| THE 5TH EDITION OF FLORIDA FIRE PREVENTION CODE |
| INCLUDING THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND |
| ALL OTHER APPLICABLE CODES OR STANDARDS. |
| FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS |
| OF NFPA 13, 2010 EDITION. |
| FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| NFPA 72, 2010 EDITION. |
| |
| 2) ADD AN EXIT SIGN AT THE REAR DOOR LEADING THE EXIT |
| STAIR. THIS EXIT DOOR IS INDICATED IN THE TRAVEL PATH |
| ON THE LIFE SAFETY PLAN. |
| |
| 3) THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF |
| THE FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE |
| AND COMPLIANCE. ANY REMOVAL AND/OR CONSTRUCTION OF |
| WALLS REQUIRES AN EVALUATION. |
| THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE |
| SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE |
| CONSTRUCTION PERIOD. |
| ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER |
| SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND |
| BY CERTIFIED LIFE SAFETY CONTRACTORS. |
| ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS, |
| SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE |
| WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL |
| AND COMPLETE PROTECTION IS RETURNED. |
| |
| |
| |
| |