Plan Review Details - Permit 15060144
Plan Review Stops For Permit 15060144
Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status P Date 2016-04-20 Cont ID  
Sent By shill Date 2016-04-20 Time 14:48 Rev Time 0.00
Received By shill Date 2016-04-20 Time 14:48 Sent To  
Notes
2016-04-20 14:49:04RECEIVED EMAIL FROM SYBILLE WELTER; ROUTED TO RECORDS
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2015-10-30 Cont ID  
Sent By shill Date 2015-10-30 Time 14:42 Rev Time 0.00
Received By shill Date 2015-10-30 Time 14:42 Sent To  
Notes
2015-10-27 08:45:50***PROVISOS***
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. SEPARATE PERMITS (APPLICATION, PLANS, AND FEES BASED
 ON VALUE) ARE REQUIRED FOR FENCES, SIGNS, MONUMENT
 SIGNS, PARKING LOT, SITE LIGHTING, ROOFTOP ALUMINUM
 CANOPY.
  
 2. PRODUCT APPROVALS (AND FLOOR HATCH SPEC SHEETS) ARE
 TO BE SUBMITTED AND REVIEWED **PRIOR TO PRODUCT
 INSTALLATION**. ALL SUBMITTALS ARE TO BE REVIEWED BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL TO THE BUILDING
 DIVISION, FBC 107.
 PRODUCTS TO COMPLY WITH THE FOLLOWING DESIGN PRESSURES
 (SEE S7.5):
  
 ZONE 1: +16 / -57.8
 ZONE 2 : +16 / -93
 ZONE 3: +16 / -93
 ZONE 4: +41.8 / -44
 ZONE 5: +41.8 / -71
  
 PROVIDE FIRE RESISTANCE RATING INFORMATION WITH PRODUCT
 APPROVALS, IF APPLICABLE.
  
 PROVIDE ROOF/FLOOR HATCH SPECS WITH FIRE RESISTANCE
 RATING INFORMATION
  
 3. FBC 2010 603.1, PROVIDE INFORMATION REGARDING THE
 THE VINYL COVERED FENCE. THIS SECTION LISTS THE
 COMBUSTIBLES PERMITTED IN TYPE I AND II BUILDINGS.
 COMPLIANCE NOT CLEAR. THIS IS REQUIRED AS A SUBMITTAL
 PRIOR TO INSTALLATION.
  
 4. THREE SETS OF ALL DOCUMENTS REQUIRED FOR ALL
 REVISIONS AND SUBMITTALS.
  
 5. SPEC BOOK HAS NOT BEEN REVIEWED. A COPY MAY BE
 RETAINED AS A PART OF THE PERMIT FILE BUT IS NOT TO BE
 USED IN LIEU OF PLANS TO DEMONSTRATE CODE COMPLIANCE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-10-26 Cont ID  
Sent By shill Date 2015-10-26 Time 13:44 Rev Time 0.00
Received By shill Date 2015-10-26 Time 13:44 Sent To  
Notes
2015-10-26 13:46:46SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FROM PROVISO LIST:
  
 ***REQUIRED PRIOR TO PERMIT ISSUANCE***
  
 11. SEE SHEETS SA1 THROUGH 6D AND OTHER SHEETS AS
 APPLICABLE, AS000, THE THRESHOLD STATEMENTS ARE NOT
 CONSISTENT WITH FLORIDA STATUTE 553.79(7)(D). PLEASE
 REVISE OR CLARIFY.
  
 THE LANGUAGE IN FS 553.79:
  
 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED TO BE
 SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF
 RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE
 ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM
 BUILDING CODES AND THE APPLICABLE FIRESAFETY STANDARDS
 AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS CHAPTER AND CHAPTER 633.
  
 STATEMENT ON STRUCTURAL SHEETS:
  
 TO THE BEST OF THE ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM
 BUILDING CODES AND THE LOCAL AUTHORITY IN ACCORDANCE
 WITH THIS SECTION AND 633 FLORIDA STATUTES.
  
 (NOTE THAT LANGUAGE NOT CONSISTENT WITH STATUTE.)
  
 ***************************************************
 ***PROVISO***
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. INFORMATIONAL ONLY; SEPARATE PERMITS REQUIRED FOR
 FENCES, SIGNS, MONUMENT SIGNS, PARKING LOT, SITE
 LIGHTING.
  
 2. INFORMATIONAL ONLY, PRODUCT APPROVALS ARE TO BE
 SUBMITTED AND REVIEWED PRIOR TO PRODUCT INSTALLATION.
 ALL SUBMITTALS ARE TO BE REVIEWED BY DESIGNER OF RECORD
 PRIOR TO SUBMITTAL TO THE BUILDING DIVISION, FBC 107.
 PRODUCTS TO COMPLY WITH THE FOLLOWING DESIGN PRESSURES
 (SEE S7.5):
  
 ZONE 1: +16 / -57.8
 ZONE 2 : +16 / -93
 ZONE 3: +16 / -93
 ZONE 4: +41.8 / -44
 ZONE 5: +41.8 / -71
  
 3. PROVISO, FBC 2010 ACCESSIBILITY 502.5, HEIGHT
 RESTRICTION SIGNAGE REQUIRED FOR ACCESSIBLE VANS. PER
 ARCHITECT, THIS IS INCLUDED ON SHEET SW129 (SEE INDEX,
 THIS SHEET NOT SUBMITTED FOR REVIEW).
  
 4. PROVISO, FBC 2010 603.1, PROVIDE INFORMATION
 REGARDING THE THE VINYL COVERED FENCE. THIS SECTION
 LISTS THE COMBUSTIBLES PERMITTED IN TYPE I AND II
 BUILDINGS. COMPLIANCE NOT CLEAR. THIS IS REQUIRED AS A
 SUBMITTAL PRIOR TO INSTALLATION.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-10-15 Cont ID  
Sent By shill Date 2015-10-15 Time 12:01 Rev Time 0.00
Received By shill Date 2015-10-07 Time 07:42 Sent To  
Notes
2015-10-10 15:20:37***PROVISO***
 ***ISSUED AT CONTRACTOR'S RISK***
 ***REVISION REQUIRED***
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. INFORMATIONAL ONLY; SEPARATE PERMITS REQUIRED FOR
 FENCES, SIGNS, MONUMENT SIGNS, PARKING LOT, SITE
 LIGHTING.
  
 2. INFORMATIONAL ONLY, PRODUCT APPROVALS ARE TO BE
 SUBMITTED AND REVIEWED PRIOR TO PRODUCT INSTALLATION.
 ALL SUBMITTALS ARE TO BE REVIEWED BY DESIGNER OF RECORD
 PRIOR TO SUBMITTAL TO THE BUILDING DIVISION, FBC 107.
  
 3. PROVIDE MORE INFORMATION REGARDING COST BREAKDOWN,
 FBC 109. IT IS NOT CLEAR HOW THE COST OF THE JOB
 DECREASED SIGNFICANTLY, ESPECIALLY IN LIGHT OF THE FACT
 THE CONSTRUCTION COSTS HAVE INCREASED SINCE
 APPLICATION. PROVIDE A COPY OF THE CONTRACT, FBC 109.
 PRIOR TO PAYMENT OF THIS PERMIT, FEES SHOULD BE
 RESOLVED AND APPLIED TO OTHER PERMITS AS APPLICABLE.
  
 4. AS000, REVISE SITE PLAN TO SHOW COMPLIANCE WITH FBC
 705.8, FBC 705.3 (ASSUMED PROPERTY LINE, DISTANCE OF
 EACH BUILDING TO THE ASSUMED PROPERTY LINE).
 INCORPORATE ANY EXCEPTIONS UTILIZED INTO THE PLAN.
 (THIS SHOULD BE CONSISTENT WITH THE CHANGES ALREADY
 MADE TO THE FOUNDATION PERMIT PLAN.)
  
 2ND REVIEW, THE PLAN SUBMITTED (AS000 DATED 9/4/15)
 DOES NOT INCLUDE FOUNDATION REVISION NUMBER 3 DATED
 6/9/15. THE PLAN SUBMITTED, ALTHOUGH THIS REVISION IS
 INCLUDED IN THE REVISION BLOCK, DOES NOT SHOW THE
 ASSUMED PROPERTY LINE CORRECTLY AND DOES NOT MATCH THE
 ISSUED FOUNDATION PERMIT. ALSO, THIS SHEET WAS REDLINED
 TO INCORPORATE EXCEPTIONS WHICH WERE INCLUDED IN THE
 RESPONSE LETTER BUT NOT INCLUDED ON THE PLAN.
  
 PROVIDE A PLAN CONSISTENT WITH THE ISSUED FOUNDATION
 PERMIT. IT IS UNCLEAR WHY THIS REVISION WOULD BE
 REMOVED FROM THIS SHEET. PLEASE CONFIRM THAT NO OTHER
 REVISIONS WERE REMOVED FROM THIS PLAN. A RE-REVIEW
 TYPICALLY TAKES LESS TIME AS ONLY NEW ITEMS ARE
 REVIEWED. IF REVISIONS WHICH WERE REQUIRED TO SHOW CODE
 COMPLIANCE ARE REMOVED FROM THE PLAN, A COMPLETE REVIEW
 OF THE ENTIRE PLAN IS REQUIRED AND TAKES SIGNIFICANTLY
 MORE TIME.
  
 4A. SEE FOUNDATION PERMIT, REVISION 15090442 SHEET
 AS000 AND ISSUED SHEET AS000. IT APPEARS THAT, ALTHOUGH
 THE DIMENSIONS DEMONSTRATING CODE COMPLIANCE FBC 705.8,
 705.3 WAS REMOVED, THAT CHANGE TO THE PLAN (REMOVAL OF
 REQUIRED DIMENSIONS) WAS NOT CLOUDED AND THEREFORE NOT
 REVIEWED. REVISE THIS SHEET AND SUBMIT AS A REVISION TO
 THE FOUNDATION PERMIT, INCORPORATING REDLINES WHICH
 INCLUDED THE EXCEPTIONS REFERRED TO IN THE RESPONSE
 LETTER (NOT A PART OF THE PERMIT RECORD). PLEASE SEE
 FOUNDATION COMMENT WHICH REQUESTED THAT ALL EXCEPTIONS
 UTILIZED BE INCORPORATED INTO THE PLAN (IN ORDER TO
 AVOID FIELD ISSUES AND TO CLEARLY DEMONSTRATE CODE
 COMPLIANCE).
  
 4B. TWO SHEETS WERE ENTIRELY NEW SHEETS SUBMITTED AS A
 REVISION TO THE FOUNDATION PERMIT (S8.2, S9.4) BUT WERE
 NOT INDICATED AS NEW SHEETS AND THEREFORE ONLY CLOUDED
 REVISIONS WERE REVIEWED. SUBMIT A NEW INDEX AS A
 REVISION TO THE FOUNDATION PERMIT INDICATING THE NEW
 SHEETS. CONFIRM THAT ALL CHANGES IN THAT REVISION WERE
 CLOUDED. IN ADDITION TO THE CHANGE ON AS000, SEE
 F-PP110D; THIS SHEET INCLUDES A CHANGE WHICH WAS NOT
 CLOUDED. OTHER CHANGES WERE MADE TO THE STRUCTURAL
 SHEETS WHICH WERE NOT CLOUDED. PLEASE CONFIRM THAT ALL
 REVISIONS TO THE ISSUED FOUNDATION PERMIT WERE PROPERLY
 CLOUDED AND, IF ANY CHANGES WERE NOT, PLEASE CLOUD AT
 THIS TIME AND SUBMIT WITH THE REVISION SO THOSE ITEMS
 CAN BE REVIEWED. DISCREPANCIES WERE FOUND ON TWO S
 SHEETS, BUT A THOROUGH REVIEW WAS NOT DONE, ONLY A SPOT
 CHECK.
  
 SHEET AS000 TO BE CORRECTED AND SUBMITTED AS A
 REVISION.
  
 5. PROVISO, FBC 1008, PER ARCHITECT, BOTH MEANS OF
 EGRESS GATES WILL INCLUDE PANIC HARDWARE.
  
 6. PROVISO, FBC 2010 ACCESSIBILITY 502.5, HEIGHT
 RESTRICTION SIGNAGE REQUIRED FOR ACCESSIBLE VANS.
  
 7. PROVISO, PROVIDE CALCULATIONS AND MORE INFORMATION
 TO DOCUMENT THE PERCENTAGES (OPEN PARKING GARAGE) SHOWN
 ON AE201 AND AE202. CALCULATIONS AND REPORT PREPARED BY
 SARAH MAMAN PE, FIRE PROTECTION ENGINEER, HAS BEEN
 RECEIVED VIA EMAIL; SIGNED, SEALED, DATED ORIGINALS
 REQUIRED. SUBMIT AS A "SUBMITTAL" (NO FEE).
  
 8. PROVISO, PROVIDE ARCHITECT'S EXHIBIT "C" (ADDITIONAL
 DOCUMENTATION FOR "OPEN" CLASSIFICATION) FULL SIZE
 SHEETS, SIGNED AND SEALED (SUBMITTAL, NO FEE).
  
 9. PROVISO, FBC 2010 ACCESSIBILITY 209.4, 503, REVISE
 PLAN TO SHOW THE VEHICULAR PULL UP SPACE AND ACCESS
 AISLE. SUBMIT AS A REVISION. (RESPONSE LETTER STATES
 THAT THIS IS SHOWN ON AE172 AND REVISED CIVIL DRAWINGS.
 SEE SECTION 503.3.3, THE ACCESS AISLE IS TO BE MARKED.
 IT IS NOT CLEAR ON AE172 WHERE THE LOADING ZONE IS
 LOCATED AND I WAS UNABLE TO FIND THE MARKED ACCESS
 AISLE, PLEASE REVISE PLAN. PLEASE REVISE PLANS TO SHOW
 DIMENSIONS OF FBC 2010 ACCESSIBILITY 503.2, THE PULL UP
 SPACE, AND 503.3, THE MARKED ACCESS AISLE. AN
 ACCESSIBLE PASSENGER LOADING ZONE COMPLIANT WITH 503 IS
 REQUIRED. RESPONSE APPEARS TO INDICATE AGREEMENT FROM
 THE DESIGNER, BUT IT IS NOT CLEAR HOW THIS HAS BEEN
 ADDRESSED.)
  
 10. PROVISO, FBC 2010 603.1, PROVIDE INFORMATION
 REGARDING THE THE VINYL COVERED FENCE. THIS SECTION
 LISTS THE COMBUSTIBLES PERMITTED IN TYPE I AND II
 BUILDINGS. COMPLIANCE NOT CLEAR. THIS IS REQUIRED AS A
 SUBMITTAL PRIOR TO INSTALLATION.
  
 ***REQUIRED PRIOR TO PERMIT ISSUANCE***
  
 11. SEE SHEETS SA1 THROUGH 6D AND OTHER SHEETS AS
 APPLICABLE, AS000, THE THRESHOLD STATEMENTS ARE NOT
 CONSISTENT WITH FLORIDA STATUTE 553.79(7)(D). PLEASE
 REVISE OR CLARIFY.
  
 THE LANGUAGE IN FS 553.79:
  
 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED TO BE
 SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF
 RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE
 ARCHITECT?S OR ENGINEER?S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM
 BUILDING CODES AND THE APPLICABLE FIRESAFETY STANDARDS
 AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS CHAPTER AND CHAPTER 633.
  
 STATEMENT ON STRUCTURAL SHEETS:
  
 TO THE BEST OF THE ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM
 BUILDING CODES AND THE LOCAL AUTHORITY IN ACCORDANCE
 WITH THIS SECTION AND 633 FLORIDA STATUTES.
  
 (NOTE THAT LANGUAGE NOT CONSISTENT WITH STATUTE.)
  
 STATEMENT ON AS000:
  
 TO THE BEST OF ARCHITECT?S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE FIRE SAFETY
 STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE.
  
 (NOTE THAT MINIMUM BUILDING CODES WAS OMITTED.)
  
 PLEASE EITHER REVISE THE STATEMENT TO BE CONSISTENT
 WITH THE STATUTE OR EMAIL RATIONALE FOR LANGUAGE WHICH
 DEVIATES FROM THE STATUTE.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-07-16 Cont ID  
Sent By shill Date 2015-07-16 Time 18:19 Rev Time 0.00
Received By shill Date 2015-06-05 Time 07:56 Sent To  
Notes
2015-07-16 18:20:34****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. INFORMATIONAL ONLY; SEPARATE PERMITS REQUIRED FOR
 FENCES, SIGNS, MONUMENT SIGNS, PARKING LOT, SITE
 LIGHTING.
  
 2. PROVIDE A COST BREAKDOWN FOR THE PROJECT. SOME ITEMS
 WILL REQUIRE SEPARATE PERMITS (SUCH AS THE PARKING LOT
 AND LANDSCAPING) AND SHOULD NOT BE INCLUDED IN THE
 BUILDING PERMIT VALUE.
  
 3. INFORMATIONAL ONLY, PRODUCT APPROVALS ARE TO BE
 SUBMITTED AND REVIEWED PRIOR TO PRODUCT INSTALLATION.
 ALL SUBMITTALS ARE TO BE REVIEWED BY DESIGNER OF RECORD
 PRIOR TO SUBMITTAL TO THE BUILDING DIVISION, FBC 107.
  
 4. AS000, REVISE SITE PLAN TO SHOW COMPLIANCE WITH FBC
 705.8, FBC 705.3 (ASSUMED PROPERTY LINE, DISTANCE OF
 EACH BUILDING TO THE ASSUMED PROPERTY LINE).
 INCORPORATE ANY EXCEPTIONS UTILIZED INTO THE PLAN.
 (THIS SHOULD BE CONSISTENT WITH THE CHANGES ALREADY
 MADE TO THE FOUNDATION PERMIT PLAN.)
  
 5. LS110 AND C2.00, FBC 1008.2, PROVIDE A DETAIL FOR
 THE GATES AND GATE HARDWARE FOR THE PEDESTRIAN GATES
 ADJACENT TO THE FIRE LANE. THE GATES ARE TO MEET ALL OF
 THE REQUIREMENTS AS DOORS AS THEY ARE IN THE EXIT
 DISCHARGE FOR SEVERAL EXITS.
  
 6. C3.05, LEGEND DOES NOT INCLUDE THE GRAPHIC FOR THE
 FIRE LANE. ON OTHER SHEETS, THE FIRE LANE IS NOTED AS
 STABILIZED GRADE. LS110, THE SIDEWALK WHICH LEADS TO
 THE TWO GATES APPEAR TO BE BLOCKED BY STAIRS (FOR
 EXAMPLE, SEE STAIR 3 AND DOOR 105). IN OTHER AREAS (SE
 STAIR TO BASEMENT, SE CORNER OF BUILDING) SIDEWALK
 WIDTH IS NOT CLEAR. SEE FBC 1003.1, 1005.1, 1003.4,
 1003.5. ARE OCCUPANTS TO WALK AROUND THE STAIRS, ON THE
 FIRE LANE, WHICH APPEARS UNPAVED?
  
 7. LS110 AND C2.00, THE EXIT AT THE SOUTH (AND OTHER
 EXITS) APPEAR TO BE OBSTRUCTED BY OTHER STAIRS
 (SIDEWALK NOT CONTINUOUS). SEE FBC 1003.6, MEANS OF
 EGRESS CONTINUITY. REVISE THE LIFE SAFETY PLAN TO SHOW
 EXIT DISCHARGE, ROUTE TO THE PUBLIC WAY, WITH MORE
 INFORMATION REGARDING THE FIRE EXIT LANE (SHOWN AS
 "STABLILIZED" RATHER THAN PAVED) AS IT APPEARS THAT
 OCCUPANTS WILL BE FORCED TO WALK ACROSS THE FIRE LANE,
 AROUND THE STAIRS, AS A PART OF THE EXIT DISCHARGE.
  
 8. LS120, FBC 2010 ACCESSIBILITY 208.3, 103, AND TITLE
 II ADA (STATE AND LOCAL GOVERNMENT REQUIREMENTS), THERE
 ARE SEVERAL ELECTRICAL VEHICLE SPACES BUT IT DOES NOT
 APPEAR THAT ANY OF THEM ARE USABLE BY AN INDIVIDUAL WHO
 REQUIRES AN ACCESSIBLE SPACE. AT LEAST ONE OF THE
 SPACES IS REQUIRED TO BE ACCESSIBLE (MEETING THE
 PARKING SPACE DIMENSION REQUIREMENTS, ACCESS AISLE). IT
 IS RECOMMENDED THAT AN EMAIL ADVISING HOW THIS WILL BE
 ADDRESSED IS SUBMITTED PRIOR TO PLAN RESUBMITTAL FOR A
 COURTESY REVIEW TO AVOID REPEAT COMMENTS.
  
 9. LS SHEETS, SEE FBC 1007, FBC 2010 ACCESSIBILITY 207,
 PLEASE IDENTIFY METHOD OF COMPLAINCE AND NOTE
 ACCESSIBLE EXITS ON THE PLAN. A REVIEW OF THIS ITEM HAS
 NOT BEEN DONE AS METHOD SELECTED (IBC 2001 OR IBC 2003)
 HAS NOT BEEN DETERMINED. PLEASE NOTE THAT, SINCE THE
 BUILDING IS NOT SPRINKLERED AT THIS TIME, IT APPEARS
 THAT AREA OF REFUGE WILL BE REQUIRED.
  
 TO AVOID POSSIBLE COMMENTS ON THIS ITEM, A COURTESY
 REVIEW CAN BE REQUESTED PRIOR TO RESUBMITTAL.
  
 10. LS120, FBC 2010 ACCESSIBILITY 502.5, HEIGHT
 RESTRICTION SIGNAGE REQUIRED FOR ACCESSIBLE VANS.
  
 11. LS110, ALLOWABLE AREA IS SHOWN USING FBC TABLE
 406.3.5 FOR OPEN PARKING GARAGES. SEE FIRE COMMENTS. IF
 THIS BUILDING IS DETERMINED TO BE AN ENCLOSED PARKING
 GARAGE, PLEASE CONTACT ME TO DISCUSS HOW TO PROCEED.
  
 12. PROVIDE CALCULATIONS AND MORE INFORMATION TO
 DOCUMENT THE PERCENTAGES (OPEN PARKING GARAGE) SHOWN ON
 AE201 AND AE202, ESPECIALLY THE GROUND LEVEL (SHOWN AS
 20.5%; 20% REQUIRED). AS THIS ISSUE IS CRUCIAL TO THE
 ENTIRE REVIEW AND BUILDING DESIGN, THIS INFORMATION CAN
 BE SENT VIA EMAIL FOR PRELIMINARY REVIEW PRIOR TO
 RESUBMITTAL OF THE PLAN.
  
 THIS REVIEW IS BEING PERFORMED TREATING THE BUILDING AS
 AN OPEN PARKING GARAGE. PLEASE NOTE THAT, SUBJECT TO
 REVIEW OF CALCULATIONS FOR THE OPENINGS REQUIRED, IF
 ADDITIONAL ITEMS ARE ADDED WHICH EXCEED CODE COMPLIANCE
 FOR AN OPEN PARKING GARAGE, THE ADDITIONAL SYSTEMS WILL
 NOT AFFECT THE DESIGNATION OF OPEN PARKING GARAGE. THE
 CLASSIFICATION OF OPEN PARKING GARAGE WILL BE BASED ON
 OPENING CALCULATIONS AND THE DEFINITION IN THE FBC.
  
 **7/17/15 - CALCULATIONS AND REPORT PREPARED BY SARAH
 MAMAN PE, FIRE PROTECTION ENGINEER, HAS BEEN RECEIVED
 VIA EMAIL (PENDING REVIEW AND MEETING)**
  
 13. FBC 2010 ACCESSIBILITY 209.4, 503, REVISE PLAN TO
 SHOW THE VEHICULAR PULL UP SPACE AND ACCESS AISLE.
  
 14. LS110, 0 FIRE RATING SHOWN FOR THE ROOF; FBC TABLE
 601 REQUIRES 1 HOUR, FOOTNOTE B APPLIES IF THE ROOF IS
 OVER 20FT ABOVE THE FLOOR BELOW. PLEASE REVISE OR
 INCORPORATE APPLICABLE EXCEPTION INTO THE PLAN FOR 0 HR
 FIRE RATING.
  
 15. LS110, BUILDING HEIGHT AND AREA ADDRESSES ONLY THE
 S2 OCCUPANCY. PLEASE REVISE TO INCLUDE THE BUSINESS
 OCCUPANCY. IS THIS AREA BEING TREATED AS AN ACCESSORY
 OR MIXED USE? SEE FBC 508. NO FIRE RATED SEPARATIONS
 SHOWN BETWEEN BUSINESS AND S2.
  
 16. LS110 AND OTHER SHEETS, FBC 708.14.1, ELEVATOR
 LOBBY WALL IS NOT SHOWN AS A FIRE PARTITION. EITHER
 REVISE PLAN TO INCLUDE REQUIRED FIRE RATING OR
 INCORPORATE AN APPLICABLE EXCEPTION INTO THE PLAN.
  
 17. LS110, FBC 509.3(5) STATES THAT THE GROUP S2
 ENCLOSED PARKING GARAGE IS FOR THE EXCLUSIVE USE OF
 PARKING, BUT ALLOWS AN OFFICE, WAITING ROOM AND TOILET
 ROOM NOT TO EXCEED 1000 SF, AND MECHANICAL EQUIPMENT
 ROOMS IN THE ENCLOSED PARKING GARAGE PORTION. THIS
 SHEET SHOWS THREE UTILITY SPACES, B004, B005 AND B006
 AND ONE UNIDENTIFIED SPACE (ADJACENT TO B004). IT DOES
 NOT APPEAR THAT THE CODE ALLOWS THE UTILITY SPACES, AND
 MORE INFORMATION IS REQUIRED FOR THE UNIDENTIFIED
 SPACE. PROVIDE SF AREA AND RATIONALE FOR THESE SPACES
 OR REVISE TO BE CONSISTENT WITH THE ALLOWABLE USES IN
 THE CODE.
  
 18. LS110, PLEASE CORRECT THE TYPO FBC 1022.1 EXCEPTION
 4 (PLAN STATES EXCEPTION 5 WHICH IS NOT APPLICABLE).
  
 19. LS110, PLEASE CORRECT THE APPARENT TYPO (OR
 CLARIFY) FBC 905.3.1, EXCEPTION 3 REFERS TO AREAS
 SUBJECT TO FREEZING.
  
 20. LS120, PROVIDE DIMENSIONS FOR THE FIRE COMMAND
 CENTER, FBC 403.4.5, 911.1.3.
  
 21. LS120, STAIRS 1 AND 2, WILL THERE BE SIGNAGE TO
 HELP TO PREVENT OCCUPANTS FROM ATTEMPTING TO ENTER THE
 BASEMENT DOOR RATHER THAN THE EXIT? NOT REQUIRED BUT
 RECOMMENDED.
  
 22. LS130 AND OTHER SHEETS, CLARIFY USE OF THE UTILITY
 SPACE AND INCLUDE THESE SPACES ON LS110 (SQUARE FOOT
 AREAS, OCCUPANCY CLASSIFICATION, HOW THEY ARE
 CLASSIFIED FBC 508).
  
 23. FBC 1009.6.2, IT APPEARS THAT THE SOME OF THE EXIT
 STAIRS WILL BE EXPOSED TO THE WEATHER. PROVIDE
 INFORMATION (CROSS SLOPE?) TO SHOW HOW WATER WILL BE
 PREVENTED FROM ACCUMULATING.
  
 24. AE160, SPECIFY DESIGN PRESSURES FOR THE PROPOSED
 ROOF HATCHES. IT APPEARS THAT THEY WILL BE IN ZONE 2.
  
 25. AE152, DETAILS 1 AND 5, IDENTIFY THE SQUARES WHICH
 APPEAR TO BE HATCHES.
  
 26. ENERGY CALCS REQUIRED, FBC 2010 ENERGY CONSERVATION
 103.
  
 27. FBC 2010 ENERGY CONSERVATION, CONFIRM THAT
 INFORMATION REQUIRED BY 103.2.2 IS INCLUDED IN THE
 PLAN.
  
 28. FBC 2010 603.1, PROVIDE INFORMATION REGARDING THE
 ACRYLIC FABRIC AND THE VINYL COVERED FENCE. THIS
 SECTION LISTS THE COMBUSTIBLES PERMITTED IN TYPE I AND
 II BUILDINGS. COMPLIANCE NOT CLEAR.
  
 29. 2 AE160 AND DETAILS, PENETRATIONS INTO A RATED
 STAIR SHOULD BE LIMITED TO THOSE REQUIRED FOR THE
 ENCLOSURE, FBC 1022.4; DRAINS ARE SHOWN.
  
 30. FBC 703, PROVIDE DETAILS FOR THE FIRE RATED
 STRUCTURAL ELEMENTS TO SHOW COMPLIANCE WITH TYPE 1B
 BUILDING PER TABLE 601.
  
 31. AE150A AND OTHER SHEETS, UPPER DECK UNDER AWNING
 PARKING INCLUDES NON ACCESSIBLE SPACES ONLY. SEE FBC
 2010 ACCESSIBILITY 103, EQUIVALENT FACILITATION. IT
 APPEARS THAT EITHER ACCESSIBLE SPACES SHOULD BE
 INCLUDED UNDER AWNING OR ACCESSIBLE SPACES MOVED TO A
 COVERED FLOOR.
  
 REVISED 8/28/15 - PER ROBERT BROWN, BUILDING OFFICIAL,
 AS DISCUSSED IN MEETING W/ARCHITECT, IT IS ACCEPTABLE
 FOR ACCESSIBLE PARKING TO REMAIN AS DESIGNED DUE TO THE
 NUMBER OF ACCESSIBLE SPACES UNDER COVER ON OTHER
 FLOORS.
  
 32. FBC 107, DUE TO THE SIZE OF THIS PLAN, IT IS
 SUGGESTED THAT EITHER THE PLAN BE SUBMITTED DIGITALLY
 OR THAT THE PLAN SETS BE SPLIT INTO TWO OR THREE ROLLS
 (ARCH, STRUCTURAL, MEP), FBC 107.
  
 WHEN RESUBMITTING, IF THIS REMAINS A PAPER SUBMITTAL
 RATHER THAN DIGITAL, ALL OLD SHEETS ARE TO BE REMOVED
 FROM THE BOUND SET AND NEW SHEETS PUT IN THEIR PLACE.
 THE OLD SHEETS ARE TO BE RETAINED (ALL SETS) AND BOUND
 SEPARATELY FROM THE NEW SETS. PLEASE DO NOT REMOVE
 ANYTHING FROM THE DEPARTMENT AS SOMETIMES OLD SHEETS
 ARE USED TO AVOID RE-STAMPS BY TRADES WHICH HAVE PASSED
 OR PARTIALLY PASSED.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-11-18 Cont ID  
Sent By albarran Date 2015-11-18 Time 12:08 Rev Time 0.00
Received By albarran Date 2015-11-18 Time 11:30 Sent To E
Notes
2015-11-18 12:10:21PER THE PROVIDED RESPONSE LETTER AND REVISED SHEET
 EE405, THE REQUIRED EXIT LIGHTING HAS BEEN ADDED TO THE
 TOP LEVEL. NOW ALL THAT REMAINS IS FOR SOMEONE TO
 PROPERLY ASSEMBLE THE PLANS SET FOR STAMPING.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-10-01 Cont ID  
Sent By albarran Date 2015-10-01 Time 16:54 Rev Time 0.00
Received By albarran Date 2015-10-01 Time 15:50 Sent To  
Notes
2015-10-01 16:56:30I PUT A CALL OUT TO MR. FERNANDO DELDAGO TO DISCUSS
 WITH HIM THE STILL REMAINING DEFICIENCIES, WHICH ARE
 MISSING EXIT LIGHTS IN THE ROOF LEVEL OF THE GARAGE.
 RETURNED TO C35

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-08-31 Cont ID  
Sent By albarran Date 2015-08-31 Time 19:45 Rev Time 0.00
Received By albarran Date 2015-08-26 Time 09:26 Sent To I
Notes
2015-08-31 19:52:26PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
  
 1. THE EXIT LIGHT DEFICIENCY IS TYPICAL THROUGH OUT THE
 LEVELS. THERE SHALL BE AN EXIT LIGHT MID WAY IN EACH OF
 THE PARKING AISLES.
 2. THE DIRECTION OF THE FACE OF THE LIGHTS SHALL BE
 REVIEWED AS WELL.
 3. THE PANEL LABELS DO NOT MATCH THOSE INDICATED ON THE
 RISER DIAGRAM.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2015-11-23 Cont ID  
Sent By cranford Date 2015-11-23 Time 10:51 Rev Time 0.00
Received By cranford Date 2015-11-19 Time 09:12 Sent To  
Notes
2015-11-23 10:51:07ALSO SEE ENGINEERING DEVELOPMENT APPROVAL E15040015

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2015-06-22 Cont ID  
Sent By cranford Date 2015-06-22 Time 09:41 Rev Time 0.00
Received By cranford Date 2015-06-22 Time 09:37 Sent To  
Notes
2015-06-22 09:41:041. DISCREPANCIES BETWEEN PLUMBING PLAN VIEW,
 SCHEMATICS, AND DETAILS FOR SUMP DISCHARGE PUMP LINE
 DIAMETERS. ALSO, DISCREPANCY IN PIPE DIAMETER BETWEEN
 CIVIL PLANS AND PLUMBING PLANS.
  
 2. ON SHEET PP110A, SANITARY DISCHARGE PIPING IS
 LABELED AS DRAINAGE NEAR NORTHWEST CORNER OF PAGE.
  
 SEE ENGINEERING DEVELOPMENT APPLICATION E15040015 FOR
 CIVIL REVIEW COMMENTS.
  
 KELLY CRANFORD, PE
 LAND DEVELOPMENT ENGINEER
 (561)494-1098
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2015-10-30 Cont ID  
Sent By pleduc Date 2015-10-30 Time   Rev Time 0.00
Received By pleduc Date 2015-10-30 Time 13:14 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-09-22 Cont ID  
Sent By pleduc Date 2015-09-22 Time   Rev Time 0.00
Received By pleduc Date 2015-09-22 Time 15:38 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-06-10 Cont ID  
Sent By pleduc Date 2015-06-08 Time   Rev Time 0.00
Received By pleduc Date 2015-06-05 Time 11:00 Sent To  
Notes
2015-06-08 16:19:39THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET LS 110, THE PROPOSED PROJECT SHALL MEET THE
 REQUIREMENTS OF THE 5TH EDITION OF FLORIDA FIRE
 PREVENTION CODE INCLUDING THE 2012 EDITION OF NFPA 1
 AND NFPA 101 AND ALL OTHER APPLICABLE CODES OR
 STANDARDS. PLEASE MAKE CORRECTIONS TO THE DRAWING SET.
  
 2) SHEET LS110 EXIT #126 SE, LEADS TO AN AREA THAT HAS
 LOCKED GATES AND IS NOT LEADING TO A PUBLIC WAY. THE
 EXIT IS NONCONFORMING
  
 3) SHEET LS 120 EXITS # 105 S MIDDLE & 133.SE, LEAD TO
 AN AREA THAT HAS LOCKED GATES AND IS NOT LEADING TO A
 PUBLIC WAY. THESE EXITS ARE NONCONFORMING
  
 4) EXIT SIGNAGE DIRECTIONAL'S ON ALL FLOOR LEVELS SHALL
 BE REVIEWED AND ADJUSTED TO POINT IN THE DIRECTION OF
 THE EXIT.
  
 5) THE GATES ATEACH END OF THE FIRE LANE NOTE A KNOX
 BOX LOCATION. THE KNOX BOX CAN ONLY BE ACCESSED FROM
 ONE DIRECTON. GATE ACCESS SHALL BE FROM BOTH
 DIRECTIONS.
  
 6) THERE IS INSUFFICIENT INFORMATION PROVIDED TO
 DETERMINE THAT IT IS AN OPEN PARKING STRUCTURE. THE
 DEFINITION AND CONSTRUCTION OF THIS AS AN OPEN PARKING
 STRUCTURE IS NOT APPROVED. THE METAL FACADE STRUCTURE
 DOES NOT PROVIDE EACH PARKING LEVEL OPENINGS TO THE
 ATMOSPHERE. ADDITIONALLY, THE OPENINGS ARE NOT
 DISTRIBUTED OVER 40 PERCENT OF THE BUILDING PERIMETER
 OR UNIFORMLY OVER TWO OPPOSING SIDES. OPEN PARKING
 STRUCTURES PROVIDE FOR VENTILATION. WITH THE ADDITION
 OF THE METAL FACADE THE VENTILATION IS SIGNIFICANTLY
 REDUCED THAN IF THE THE AREAS WERE FULLY OPEN
  
 THE METAL FACADE IS A PERFORMANCE BASED OPTION OF AN
 OPEN PARKING STRUCTURE. PLEASE PROVIDE ADDITIONAL
 INFORMATION AS OUTLINED IN NFPA 1, CHAPTER 5
 PERFORMANCE BASED OPTION FOR REVIEW AND CONSIDERATION
 OF AN OPEN PARKING STRUCTURE.
  
 THERE APPEARS TO BE NO WAY TO MEASURE OR TEST THAT THE
 PROPOSED WILL PROVIDE FOR VENTILATION.
  
 7) BASED ON # 6, THE PARKING STRUCTURE IS REQUIRED TO
 BE FULLY SPRINKLED WITH MECHANICAL VENTILATION.
  
 8) SHEET AE301, PROVIDE ADDITIONAL MORE DETAILED
 INFORMATION FOR THE STATEMENT, " VEHICLE RESTRAINT
 CABLE SYSTEM TYP. WITH WOVEN EXTERIOR ACRYLIC FABIC
 SCREEN WITH REINFORCED VINYL EDGES ONLY @ PERIMETER OF
 THE BUILDING."
 WHAT PURPOSE DOES IT SERVE? IS THIS FABRIC LFMAE
 RETARDENT? IS THIS FABRIC COVERING CALCULATED IN THE
 OPEN GARAGE FORMULA? THIS AREA WOULD NOT BE OPEN TO THE
 ATMOSPHERE AND SHOULD BE CLACULATED AS CLOSED.
  
 9) THE FIRE HYDRANT AND FDC ARE IN LOCATIONS THAT ARE
 NOT READILY ACCESSIBLE TO FIRE APPARATUS. THE HYDRANT
 AND FDC SHOULD BE MOVED OUT IN THE AREA OF THE FIRE
 COMMAND CENTER AND KNOX BOX.
  
 10) THERE APPEARS TO BE ONLY ONE WATER SUPPLY TO THE
 STRUCTURE, TWO ARE REQUIRED.
  
 11) SHEET FA 701, RISER LEGEND # 10, REMOTE GENERATOR
 STATUS PANEL SHALL INCLUDE AN ADDITIONAL STATEMENT OF
 "MANUAL START AND TRANSFER FEATURES"

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-11-24 Cont ID  
Sent By skennedy Date 2015-11-24 Time 09:32 Rev Time 0.00
Received By skennedy Date 2015-10-21 Time 09:53 Sent To  
Notes
2015-10-22 09:53:37RESUB ROUTED TO C28

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-10-22 Cont ID  
Sent By lmarchan Date 2015-10-22 Time 09:52 Rev Time 0.00
Received By lmarchan Date 2015-09-16 Time 11:06 Sent To  
Notes
2015-09-16 10:51:18C35

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-08-31 Cont ID  
Sent By albarran Date 2015-08-31 Time 19:52 Rev Time 0.00
Received By albarran Date 2015-06-03 Time 12:36 Sent To  
Notes
2015-08-31 19:54:498/31/15 - FAILED ELECTRICAL REVIEW. CONTRACTOR NOTIFIED
 VIA EMAIL. SENT TO LARGE DENIED BIN "W". MA
2015-06-05 08:03:49C25 & C26
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2015-06-11 Cont ID  
Sent By shill Date 2015-06-11 Time 14:48 Rev Time 0.00
Received By shill Date 2015-06-11 Time 14:48 Sent To  
Notes
2015-06-11 14:49:01NOT REQUIRED PER WILLIE SWOPE (COUNTY OWNED)
 SEE EMAIL IN FILE
  

Review Stop L LANDSCAPING
Rev No 1 Status N Date 2015-07-14 Cont ID  
Sent By eschneid Date 2015-07-14 Time 13:30 Rev Time 0.25
Received By eschneid Date 2015-07-14 Time 13:30 Sent To  
Notes
2015-08-20 09:57:11MALBERRAN'S DESK
2015-07-14 13:44:17SEPARATE LANDSCAPE PERMIT REQUIRED. PLEASE INCLUDE A
 COST ESTIMATE FOR THE VALUE OF THE LANDSCAPE
 INSTALLATION.
  
 SEPARATE IRRIGATION PERMIT REQUIRED.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2015-11-02 Cont ID  
Sent By ccole Date 2015-11-02 Time 14:01 Rev Time 0.00
Received By ccole Date 2015-11-02 Time 14:01 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-09-30 Cont ID  
Sent By ccole Date 2015-09-30 Time 08:52 Rev Time 0.00
Received By ccole Date 2015-09-29 Time 14:26 Sent To  
Notes
2015-09-30 10:14:162ND REVIEW: FBC 2010 MECHANICAL
 PERMIT #15060144
 9/30/15
  
 1) SHEET MM701: INDICATE THE DURATION OF OPERATION FOR
 THE PRESSURIZATION FANS SF-1 & 2 AFTER DETECTION OF A
 FIRE- REFER TO SECTION 909.4.6 FBC-10 BUILDING AND
 PROVIDE NOTES TO CLARIFY.
 2) MM110: INDICATE HOW THE BASEMENT LEVEL UTILITY ROOMS
 B005 & B006 ARE BEING VENTILATED. SHOW THE MEANS AND
 PROVIDE CALCULATIONS- SECTION 401 FBC-10 MECHANICAL.
 3) MM220: PROVIDE VENTILATION CALCULATIONS FOR THE
 UTILITY ROOM. PLEASE REFER TO SHEET AE140- THE UTILITY
 ROOM IS ALSO FOUND ON FLOOR LEVELS 2,3,4,6, & 8; AND ON
 FLOOR LEVELS 1,5, & 7 IT IS LABELED AS AN ELECTRICAL
 ROOM . PLEASE SHOW THE MEANS OF VENTILATION FOR ALL OF
 THESE ROOMS AND PROVIDE SIZING CALCULATIONS.
 4) MM220 & MM801: PROVIDE INSTALLATION AND SUPPORT
 DETAILS FOR THE SF-1 AND SF-2 PRESSURIZATION FANS.
 5) MM801, DETAIL 11: THE HEIGHT OF THE RECIRCULATING
 FANS ABOVE THE FINISH FLOORS SHALL BE MINIMUM 8' PER
 SECTION 304.6 FBC-10 MECHANICAL. PLEASE CORRECT THE
 DETAIL.
 6) MM802, DETAIL 3: THE DETAIL IS INCOMPLETE: PROVIDE
 FASTENING DETAILS FOR ATTACHING THE CONDENSERS TO THE
 BRACKET AND THE BRACKET TO THE WALL. DETAIL 4- PROVIDE
 THE TYPE, SIZE, AND DEPTH OF EMBEDMENT FOR THE
 CONDENSER TIE-DOWN ANCHOR BOLTS. PLEASE NOTE: SITE
 SPECIFICA WINDLOAD ENGINEERING IS REQUIRED FOR ALL
 EXTERIOR APPLIANCE INSTALLATIONS- SECTION 301.12
 /FBC-10 MECHANICAL.
 7) PROVIDE THE SEQUENCE OF OPERATION FOR THE
 RECIRCULATION FANS, AND ALL OF THE VARIOUS ROOM EXHAUST
 FANS.
 8) DUCTLESS SYSTEM 8 SHOWN IN THE SCHEDULE ON MM601 IS
 NOT SHOWN ON THE PLANS- PLEASE INDICATE THE SYSTEM
 LOCATION ON THE PLANS.
 9) AC CALCULATIONS WERE NOT PROVIDED FOR AC SYSTEMS 2,
 3, 6, 7, & 8- PLEASE PROVIDE THE CALCULATIONS.
 10) AC SYSTEMS 2, 3, 6, 7 & 8 ARE NOT LISTED IN THE
 ENERGY CALCULATION FORM 506-2010- PLEASE PROVIDE THE
 COMPLIANCE DATA.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-06-24 Cont ID  
Sent By ccole Date 2015-06-24 Time 13:45 Rev Time 0.00
Received By ccole Date 2015-06-24 Time 13:45 Sent To  
Notes
2015-06-24 14:57:211ST REVIEW: FBC 2010 MECHANICAL
  
 1) PROVIDE AN EXHAUST VENTILATION CALCULATION FOR THE
 BASEMENT LEVEL PARKING GARAGE TO VERIFY EF-1, 2, & 3
 HAVE BEEN SIZED TO PROVIDE THE RATES REQUIRED BY TABLE
 403.3 AND SECTION 404 FBC-10 MECHANICAL.
 2) CLARIFY THE METHOD BY WHICH THE STAIR PRESSURIZATION
 FANS (EF-4, 5 AND SF-1,2) WERE SIZED: PROVIDE
 CALCULATIONS CONSISTENT WITH SECTION 909.6 INCLUSIVE
 FBC-10 BUILDING.
 3) PROVIDE EXHAUST VENTILATION CALCULATIONS FOR THE
 BOOSTER PUMP, STORAGE, AND FIRE PUMP ROOMS- ASHRAE
 62.1-07.
 4) PROVIDE AC LOAD CALCULATIONS FOR ALL CONDITIONED
 ROOMS AND SPACES IN ACCORDANCE WITH ACCA MANUAL N, OR
 ASHRAE/ACCA STANDARD 183- REFERENCE SECTION 503.2.1
 FBC-10 ENERGY CONSERVATION.
 5) PROVIDE ENERGY CALCULATIONS FOR THE PROPOSED PROJECT
 PER SECTION101 FBC-10 ENERGY: SUBMIT TWO COPIES OF
 EITHER FORM 502 OR 506 SIGNED BY THE DESIGN
 PROFESSIONAL OF RECORD.
 6) SHEET MM110: PROVIDE ADDITIONAL DETAILS OR NOTES
 INDICATING THE SPACING AND MOUNTING HEIGHT LOCATIONS OF
 THE C0 DETECTORS PER THE MANUFACTURER'S
 RECOMMENDATIONS. LIST THE MAKE AND MODEL NUMBERS OF THE
 DEVICES AND SUBMIT PRODUCT DATA SHEETS REVIEWED AND
 APPROVED BY THE DESIGN PROFESSIONAL OF RECORD.
 7) MM220: CU 3 & 6 SHOWN IN DETAIL 8 SHALL BE INSTALLED
 A MINIMUM OF 8 FT. ABOVE THE FLOOR PER SECTION 304.6
 FBC-10 MECH.
 8) MM230: THE BOTTOM OF THE EXHAUST LOUVERS FOR THE
 BASEMENT EXHAUST FANS AS SHOWN IN DETAIL 4 SHALL BE
 INSTALLED A MINIMUM OF 10 FT. ABOVE THE ADJOINING
 GRADE- SECTION 501.2.1(2) FBC-10 MECH.
 9) MM801: THE RECIRCULATING FANS SHOWN IN DETAIL 11
 SHALL BE INSTALLED AT LEAST 1FT. HIGHER THAN THE GARAGE
 DOOR PER SECTION 304.6.
 10) MM801: PROVIDE INSTALLATION DETAILS FOR THE
 FIRE/SMOKE DAMPERS, AND THE DUCT SMOKE DETECTORS.
 11) PROVIDE A SUBMITTAL PACKAGE PREPARED BY THE DESIGN
 PROFESSIONAL OF RECORD THAT INCLUDES: A) FLORIDA
 PRODUCT APPROVALS AND/OR MIAMI-DADE NOA'S FOR THE ROOF
 MOUNTED EXHAUST FANS, THE INTAKE AND EXHAUST LOUVERS,
 AND THE CONDENSER WALL MOUNT BRACKETS. B)
 MANUFACTURER'S SPECIFICATIONS FOR THE EXHAUST AND
 INTAKE FANS, THE AC UNITS, THE MOTORIZED INTAKE
 DAMPERS, THE C0 DETECTORS, THE RECIRCULATION FANS, THE
 FIRE/SMOKE DAMPERS, AND THE DUCT SMOKE DETECTORS. IN
 REGARD TO ALL EXTERIOR INSTALLATIONS SUBJECT TO WIND
 LOAD, THE DESIGN PROFESSIONAL OF RECORD SHALL CALCULATE
 DESIGN PRESSURES AND PROVIDE TIE-DOWN ENGINEERING, AND
 ALSO CIRCLE OR HIGHLIGHT ALL APPLICABLE NOTES AND
 DETAILS IN THE NOA'S AND PRODUCT APPROVALS.
 12) PLEASE NOTE THAT THE ABOVE REVIEW COMMENTS ARE
 BASED ON THE BUILDING BEING CLASSIFIED AS AN "OPEN
 PARKING GARAGE" BY THE DESIGN PROFESSIONAL OF RECORD.
 THIS CLASSIFICATION IS BEING CHALLENGED BY THE WEST
 PALM BEACH FIRE AND RESCUE DEPT., THEREFORE ADDITIONAL
 COMMENTS MAY FOLLOW THIS REVIEW.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-09-26 Cont ID  
Sent By tklarge Date 2015-09-26 Time 04:50 Rev Time 0.00
Received By tklarge Date 2015-09-26 Time 01:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-07-08 Cont ID  
Sent By tklarge Date 2015-07-08 Time 14:16 Rev Time 0.00
Received By tklarge Date 2015-07-04 Time 07:02 Sent To  
Notes
2015-07-08 14:16:121)THERE ARE SEVERAL SHEETS IN THE FRONT OF THE PLANS
 THAT NOTE FOR REFERENCE ONLY-SEE E 15040015. WHAT IS
 THIS IN REFERENCE TO? CLARIFY.
 2)SHT. AE160 DETAILS #2 & #3 SHOWS A ROOF DRAIN &
 PIPING/OVERFLOW DRAIN LOCATED IN THE STAIRWELLS AND
 PENETRATING THE WALL OF THE ENCLOSURE. PENETRATIONS
 INTO AND OPENINGS THROUGH AN EXIT ENCLOSURE ARE
 PROHIBITED IN ACCORDANCE WITH THE 2010 FBC SEC.1022.4.
 3)SHT.AE 179 - SHOW THE DEPTH OF THE GUTTER ON DETAILS
 #2 & #5. WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 4)SHT. AE 401 - SHOW THE INSIDE CLEAR DIMENSIONS (L X
 W) OF THE ACCESSIBLE RESTROOM.
 5)SHT.AE 401 - SHOW THE CLEAR FLOOR SPACE FOR THE BREAK
 ROOM SINK PER FAC SEC. 606. THE CLEAR FLOOR SPACE SHALL
 BE CENTERED ON THE FIXTURE.
 6)SHT. AE 404 - SHOWS PERFORATED DRAIN PIPE AT
 PERIMETER OF OUTER WALL OF STRUCTURE. SUBMIT DETAILS:
 SIZE OF PIPE, DEPTH AND WIDTH OF BALLAST ROCK, AND SHOW
 LOCATION ON PLANS. I COULD NOT LOCATE THIS PIPING ON
 THE CIVIL DRAWINGS. WPB AMEND. TO 2010 FBC SEC.
 107.2.1.
 7) CALCULATIONS FOR THE SIZING OF RAIN WATER DRAINAGE
 FOR THE ROOF OF THE STAIRWELLS SHALL INCLUDE - THE AREA
 OF ANY VERTICAL WALL THAT DIVERTS RAINWATER TO THE ROOF
 SHALL BE INCLUDED IN THE CALCULATIONS. 2010 FPC SEC.
 1106.4.
 8) INDICATE ON THE PLANS IF THE ELEVATOR IS HYDRAULIC
 OR TRACTION. IF HYDRAULIC, THE CYLINDER SHALL COMPLY
 WITH THE 2010 FBC SEC.3011.1 THRU 3011.1.3.
 9) SUBMIT A DETAIL DRAWING FOR THE BOOSTER PUMP FOR THE
 POTABLE WATER SYSTEM. WPB AMEND. TO 2010 FBC SEC.
 107.2.1.
 10) SHT.PP110A - SHOWS A 2"INDIRECT WASTE LINE THAT
 APPEARS TO BE PENETRATING THE WALL OF STAIR #1.
 PENETRATIONS INTO AND THROUGH AN EXIT ENCLOSURE ARE
 PROHIBITED EXCEPT FOR THE ITEMS LISTED IN 2010 FBC
 1022.4. CLARIFY.
 11) SUBMIT SIZING CALCULATIONS FOR THE OIL INTERCEPTOR.
 THE PLANS SHOW A SCHIER OIL INTERCEPTOR. THE SIZING
 CALCULATIONS SHALL BE REVIEWED BY SCHIER FOR CORRECT
 SIZING PER THE 2010 FPC SEC. 1003.2. PLEASE CONTACT LEE
 SCHNEEWEISS, SCHIER REPRESENTATIVE AT 1-800-538-4792.
 12) SHT.PP110B - INDICATE THE SLOPE OF THE 10 INCH & 12
 INCH STORM DRAIN LINES ON GRID LINE #F BETWEEN GRID
 LINE 10-1. NOTE: THE SQUARE FOOTAGE DRAINED SHALL
 COMPLY WITH 2010 FPC TABLE 1106.3.
 13) SHT.PP160D - SHOW THE CONTINUATION POINT OF THE 6_
 RAIN WATER DRAIN (SEE GRID LINES 2-3 & C-D). IS THIS
 TURNING UP OR DOWN? AND TO WHERE?
 14) SHT.PP 170A - THE PLAN SHOWS A 4" STORM DRAIN
 DISCHARGING ABOVE THE TOP LEVEL NEXT TO A PARKING
 SPACE. THIS APPEARS THAT IT MAY CAUSE A NUISANCE DUE TO
 THE DISCHARGING WATER FOR THAT PARKING AREA DURING A
 RAIN EVENT. THE SAME ISSUE OCCURS BY STAIR #2. CLARIFY.
 15) SHT. PP 170A - THERE IS A HORIZONTAL SECTION OF 4"
 STORM THAT IS COLLECTING 2170 SQUARE FEET OF AREA. THE
 MAXIMUM SQUARE FOOTAGE THAT A 4" HORIZONTAL STORM DRAIN
 CAN ACCOMMODATE AT AN 1/8" PER FOOT SLOPE AND A 5"
 RAINFALL RATE IS 1504 SQUARE FEET PER TABLE 1106.3.
 ADJUST THE SIZE TO THE NEXT LARGER PIPE SIZE OR
 INCREASE THE SLOPE.
 16) SHT.PP170C - SHOWS A 6" O.D. SERVING 4500 SQ. FT.
 THE MAXIMUM SQUARE FOOTAGE AT 1/8? PER FT. SLOPE IS
 4280 SQ. FT. PER TABLE 1106.3.
 17) SHT. PP180A & PP180B - SHOW THE SQUARE FOOTAGE
 DRAINED BY EACH DRAIN. ALSO SHOW THIS ON THE STORM
 WATER RISER. COMPLY WITH TABLE 1106.3 OF THE 2010 FPC.
 18) SHT. PP401 - SUBMIT A WATER ISOMETRIC FOR THE PUMP
 ROOM AND SUBMIT AN ELEVATION/PIPING DETAIL FOR THE
 DOMESTIC BOOSTER PUMP. WPB AMEND. TO 2010 FBC SEC.
 107.3.5.1.3.
 19) SHT. PP501 -SHOW THE SQUARE FOOTAGE OF THE AREA
 BEING DRAINED BY EACH DRAIN FOR THE STORM WATER RISERS.
 ALL VERTICAL LEADERS SHALL BE SIZED IN ACCORDANCE WITH
 THE 2010 FPC TABLE 1106.2 (1), 1106.2 (2) & ALL
 HORIZONTAL PIPING SHALL BE SIZED IN ACCORDANCE WITH
 TABLE 1106.3.ALL SIZING SHALL BE BASED ON A RAINFALL
 RATE OF 5 INCHES PER HOUR.
 20) INDICATE THE SLOPE OF THE HORIZONTAL STORM DRAIN
 PIPING. COMPLY WITH TABLE 1106.3 OF 2010 FPC.
 21) SHT.PP502 - THE AUTOMATIC AIR VENT CONNECTION TO
 THE HORIZONTAL DRAIN SHALL COMPLY WITH 2010 FPC SEC.
 905.3. THE VENT SHALL CONNECT TO THE HORIZONTAL DRAIN
 ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN PIPE.
 CHECK ALL OF THE AAV CONNECTIONS. SEE ALSO 4? LINE AT
 HUB DRAIN BY STAIR #2.
 22) SHT. PP502 - SUBMIT AN ENLARGED SANITARY RISER FOR
 THE GROUND LEVEL RESTROOM, BREAKROOM AND JANITOR. THE
 RISER IS TOO SMALL TO REVIEW.
 23) SHT. PP503 -A SHUT-OFF VALVE IS REQUIRED AT THE
 BASE OF THE WATER RISER PER 2010 FPC SEC. 606.1 (4).
 24) SHT. PP504 - SHOW THE SQUARE FOOTAGE DRAINED BY
 EACH 4? ROOF DRAIN. COMPLY WITH 2010 FPC TABLE 1106.3.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2016-12-27 Cont ID  
Sent By shill Date 2016-12-27 Time 09:40 Rev Time 0.00
Received By shill Date 2016-12-27 Time 09:40 Sent To  
Notes
2016-12-27 09:41:07ROOF HATCH AND ROOFING REVIEWED UNDER SUBMITTAL
 #16120406
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2015-07-16 Cont ID  
Sent By shill Date 2015-07-16 Time 18:20 Rev Time 0.00
Received By shill Date 2015-07-16 Time 18:20 Sent To  
Notes
2015-07-16 18:33:49DESIGN PRESSURES ON PAGE S7.5:
  
 ZONE 1: +16 / -57.8
 ZONE 2 : +16 / -93
 ZONE 3: +16 / -93
  
 ROOF PRODUCT APPROVALS NOT SUBMITTED AT THIS TIME
 ROOFING PERMIT REQUIRED
 PRODUCT APPROVALS TO BE REVIEWED BY DOR PRIOR TO
 SUBMITTAL
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status P Date 2015-06-15 Cont ID  
Sent By shill Date 2015-06-15 Time 14:23 Rev Time 0.00
Received By shill Date 2015-06-12 Time 16:37 Sent To  
Notes
***NONE***

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2015-06-11 Cont ID  
Sent By shill Date 2015-06-11 Time 14:49 Rev Time 0.00
Received By shill Date 2015-06-11 Time 14:49 Sent To  
Notes
2015-06-11 14:56:40****CORRECTIONS****
 ****REVISED 6/12/15****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PLEASE REVISE PAGE 10 OF THE THRESHOLD INSPECTION
 PLAN (REFERENCE TO MISSILE IMPACT 60'), ITEMS 602 B AND
 C. PLEASE REVISE ONLY THIS SHEET.
  
 PROVIDE SIX (THREE FOR THE FOUNDATION PERMIT
 APPLICATION, THREE FOR THE BUILDING PERMIT). THIS MAY
 BE SUBMITTED SEPARATELY FROM THE BUILDING PERMIT
 RESUBMITTALS, OR MAY BE SENT VIA EMAIL.
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2015-11-23 Cont ID  
Sent By eschneid Date 2015-11-23 Time 15:49 Rev Time 3.00
Received By eschneid Date 2015-11-23 Time 15:49 Sent To  
Notes
2015-11-23 15:51:171) THIS PERMIT IS ONLY FOR THE GARAGE STRUCTURE. ALL
 OTHER ELEMENTS DEPICTED ON THE SITE PLANS HAVE NOT
 APPROVED BY ZONING. AS SUCH, THE FOLLOWING ITEMS
 REQUIRE SEPARATE PERMIT SUBMITTALS, WITH PLANS, AND
 HAVE NOT BEEN REVIEWED AS PART OF THIS PERMIT:
  
 A. LANDSCAPE, TO INCLUDE TREE REMOVAL AND RELOCATION.
 PLEASE NOTE CUS 1 THROUGH 3 ARE SHOWN IN LOCATIONS
 WHERE THE LANDSCAPE PLAN SHOWS HEDGES AND THE NEW FIRE
 HYDRANT ON THE NORTH SIDE OF THE BUILDING IS SHOWN
 WHERE TREES ARE SHOWN. NOTE: THE AS-BUILT PLANS WILL
 NEED TO BE SUBMITTED TO THE PLANNING DIVISION AS PART
 OF A MINOR PLANNED DEVELOPMENT AMENDMENT PRIOR TO THE
 C.O. FOR THE GARAGE.
 B. IRRIGATION
 C. PARKING GARAGE ACCESS LANES, TO INCLUDE PAVING,
 STRIPING, AND SIGNAGE
 D. BICYCLE RACKS
 E. EXTERIOR SIGNAGE
 F. WORK AND IMPROVEMENTS IN THE RIGHT-OF-WAY
 G. FENCES AND GATES NOT LOCATED WITHIN THE GARAGE
 H. GENERATOR AND ENCLOSURE
 I. HARDSCAPE, TO INCLUDE THE PAVERED ENTRY AREA AND
 SIDEWALKS
 J. SITE LIGHTING, TO INCLUDE PEDESTRIAN BOLLARDS -
 NOTE:
 1. THE PHILIPS LUMEC LEONIS SERIES OF LIGHTING DOES NOT
 COMPLY WITH THE DOWNTOWN STREET LIGHTING REQUIREMENTS -
 THE FIXTURE SHALL BE MOUNTED ON TOP OF THE POLE WITH
 THE LAMP CENTER AT 17 FEET ABOVE GRADE. THE PHILIPS
 LUMEC URBANSCAPE PRODUCT MOUNTED ON A POLE APPEARS THAT
 IT WOULD COMPLY WITH THE DOWNTOWN REQUIREMENTS.
 2. PLEASE REMEMBER THAT PALM BEACH COUNTY COMMITTED TO
 COORDINATING WITH RELATED TO USE THE SAME OR SIMILAR
 LIGHT FIXTURES IN THE FLORIDA AVENUE RIGHT-OF-WAY AND
 THE ENTRY DRIVE AND PLAZA TO MAINTAIN CONSISTENCY
 BETWEEN THE TWO PROJECTS. THE SPECIFIED TYPES DO NOT
 APPEAR TO BE CONSISTENT.
 3. THE POLES SHOWN IN THE CITY RIGHT-OF-WAY MAY NOT BE
 PERMITTED ON THE SITE LIGHTING PERMIT, BUT RATHER SHALL
 BE PERMITTED THROUGH THE ENGINEERING SERVICES DIVISION.
 4. ONE OF THE LIGHT POLES IS LOCATED WITHIN THE FIRE
 DEPARTMENT ACCESS DRIVEWAY.
 K. WORK WITHIN THE FUTURE STAGING AREA
  
 2) SIGN #23 AND SIGN #24 AT STAIRWELLS #3 AND #4 SHALL
 INCLUDE THE WORD ?ONLY? AFTER EMERGENCY EGRESS.
  
 3) A SIGN SHALL BE ADDED ON EACH FLOOR AT THE STAIRWELL
 #2 DOOR DIRECTING PATRONS TO EXIT TO THE CONVENTION
 CENTER AT THE ELEVATOR LOBBY.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  

Review Stop Z ZONING
Rev No 2 Status F Date 2015-10-01 Cont ID  
Sent By eschneid Date 2015-10-01 Time 18:44 Rev Time 6.00
Received By eschneid Date 2015-10-01 Time 18:44 Sent To  
Notes
2015-10-01 18:45:45FAILED
  
 PROVIDE RESPONSES IN WRITING.
  
 1) THIS PERMIT IS ONLY FOR THE GARAGE STRUCTURE. ALL
 OTHER ELEMENTS DEPICTED ON THE SITE PLANS HAVE NOT
 APPROVED BY ZONING. AS SUCH, THE FOLLOWING ITEMS
 REQUIRE SEPARATE PERMIT SUBMITTALS, WITH PLANS, AND
 HAVE NOT BEEN REVIEWED AS PART OF THIS PERMIT:
  
 A. LANDSCAPE, TO INCLUDE TREE REMOVAL AND RELOCATION.
 PLEASE NOTE CUS 1 THROUGH 3 ARE SHOWN IN LOCATIONS
 WHERE THE LANDSCAPE PLAN SHOWS HEDGES AND THE NEW FIRE
 HYDRANT ON THE NORTH SIDE OF THE BUILDING IS SHOWN
 WHERE TREES ARE SHOWN. NOTE: THE AS-BUILT PLANS WILL
 NEED TO BE SUBMITTED TO THE PLANNING DIVISION AS PART
 OF A MINOR PLANNED DEVELOPMENT AMENDMENT PRIOR TO THE
 C.O. FOR THE GARAGE.
 B. IRRIGATION
 C. PARKING GARAGE ACCESS LANES, TO INCLUDE PAVING,
 STRIPING, AND SIGNAGE
 D. BICYCLE RACKS
 E. EXTERIOR SIGNAGE
 F. WORK AND IMPROVEMENTS IN THE RIGHT-OF-WAY
 G. FENCES AND GATES NOT LOCATED WITHIN THE GARAGE
 H. GENERATOR AND ENCLOSURE
 I. HARDSCAPE, TO INCLUDE THE PAVERED ENTRY AREA AND
 SIDEWALKS
 J. SITE LIGHTING, TO INCLUDE PEDESTRIAN BOLLARDS -
 NOTE:
 1. THE PHILIPS LUMEC LEONIS SERIES OF LIGHTING DOES NOT
 COMPLY WITH THE DOWNTOWN STREET LIGHTING REQUIREMENTS.
 THE FIXTURE SHALL BE MOUNTED ON TOP OF THE POLE WITH
 THE LAMP CENTER AT 17 FEET ABOVE GRADE. THE PHILIPS
 LUMEC URBANSCAPE PRODUCT MOUNTED ON A POLE APPEARS THAT
 IT WOULD COMPLY WITH THE DOWNTOWN REQUIREMENTS.
 2. PLEASE REMEMBER THAT PALM BEACH COUNTY COMMITTED TO
 COORDINATING WITH RELATED TO USE THE SAME OR SIMILAR
 LIGHT FIXTURES IN THE FLORIDA AVENUE RIGHT-OF-WAY AND
 THE ENTRY DRIVE AND PLAZA TO MAINTAIN CONSISTENCY
 BETWEEN THE TWO PROJECTS. THE SPECIFIED TYPES DO NOT
 APPEAR TO BE CONSISTENT.
 3. THE POLES SHOWN IN THE CITY RIGHT-OF-WAY MAY NOT BE
 PERMITTED ON THE SITE LIGHTING PERMIT, BUT RATHER SHALL
 BE PERMITTED THROUGH THE ENGINEERING SERVICES DIVISION.
 4. ONE OF THE LIGHT POLES IS LOCATED WITHIN THE FIRE
 DEPARTMENT ACCESS DRIVEWAY.
 K. WORK WITHIN THE FUTURE STAGING AREA
  
 2) REPEAT COMMENT: SHEET AE160 HAS AN ARROW CALLING OUT
 THE ADA ACCESS AISLE AS YELLOW STRIPING. THIS STRIPING
 SHALL BE BLUE, NOT YELLOW.
  
 3) REPEAT COMMENT: SHEET AE501 AND SHEETS SW 120-SW170
 DO NOT SHOW COMPLIANCE WITH THE CONDITION THAT THE
 SIGNS WITHIN THE CONVENTION CENTER GARAGE GUIDE USERS
 TO THE ELEVATORS AND STAIRWELLS AT THE NORTHWEST CORNER
 OF THE CONVENTION CENTER GARAGE AND CLEARLY SIGN THE
 REMAINING STAIRWELLS AS EMERGENCY EGRESS ONLY. SIGN S23
 BEING SHOWN AT THE NORTHEAST STAIRWELL INDICATES THAT
 THE STAIRWELL IS FOR NORMAL EXITING OF THE GARAGE. IF
 THIS IS THE CASE, THEN THE EXIT TO THE STAIRWELL NEEDS
 TO BE CONNECTED INTO THE SITE SIDEWALK NETWORK ALONG
 THE NORTH SIDE OF THE GARAGE WITH NO LOSS OF LANDSCAPE.
 SIGN TYPE S22 IS SHOWN ON THE PLAN BUT NO DETAIL OF
 THIS SIGN IS INCLUDED.
  
 4) REPEAT COMMENT: THE PHOTOMETRICS ON EACH FLOOR NEED
 TO BE CONTINUED OUTSIDE OF THE GARAGE WALL TO THE
 PROPERTY LINE AROUND THE GARAGE.
  
 5) REPEAT COMMENT: PROVIDE INFORMATION ON HOW GLARE
 FROM THE INTERIOR AND EXTERIOR LIGHTS ONTO THE ADJACENT
 RESIDENTIAL PROPERTY AND RIGHTS-OF-WAY WILL BE
 CONTROLLED.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2015-07-14 Cont ID  
Sent By eschneid Date 2015-07-14 Time 13:44 Rev Time 10.00
Received By eschneid Date 2015-07-10 Time 16:27 Sent To  
Notes
2015-07-14 14:03:17FAILED
  
 PROVIDE RESPONSES IN WRITING.
  
 1) THIS PERMIT IS ONLY FOR THE GARAGE STRUCTURE AND THE
 COVERED ENTRY STRUCTURE. ALL OTHER ELEMENTS DEPICTED ON
 THE SITE PLANS HAVE NOT APPROVED BY ZONING. AS SUCH,
 THE FOLLOWING ITEMS REQUIRE SEPARATE PERMIT SUBMITTALS,
 WITH PLANS, AND HAVE NOT BEEN REVIEWED AS PART OF THIS
 PERMIT:
  
 A. LANDSCAPE, TO INCLUDE TREE REMOVAL AND RELOCATION.
 PLEASE NOTE CUS 1 THROUGH 3 ARE SHOWN IN LOCATIONS
 WHERE THE LANDSCAPE PLAN SHOWS HEDGES.
 B. IRRIGATION
 C. PARKING GARAGE ACCESS LANES, TO INCLUDE PAVING,
 STRIPING, AND SIGNAGE
 D. BICYCLE RACKS
 E. EXTERIOR SIGNAGE
 F. WORK AND IMPROVEMENTS IN THE RIGHT-OF-WAY
 G. FENCES AND GATES NOT LOCATED WITHIN THE GARAGE
 H. GENERATOR AND ENCLOSURE
 I. HARDSCAPE, TO INCLUDE THE PAVERED ENTRY AREA AND
 SIDEWALKS
 J. SITE LIGHTING, TO INCLUDE PEDESTRIAN BOLLARDS -
 NOTE: THE PHILIPS LUMEC LEONIS SERIES OF LIGHTING DOES
 NOT COMPLY WITH THE DOWNTOWN STREET LIGHTING
 REQUIREMENTS ? THE FIXTURE SHALL BE MOUNTED ON TOP OF
 THE POLE WITH THE LAMP CENTER AT 17 FEET ABOVE GRADE.
 THE PHILIPS LUMEC URBANSCAPE PRODUCT MOUNTED ON A POLE
 APPEARS THAT IT WOULD COMPLY WITH THE DOWNTOWN
 REQUIREMENTS. PLEASE REMEMBER THAT PALM BEACH COUNTY
 COMMITTED TO COORDINATING WITH RELATED TO USE THE SAME
 OR SIMILAR LIGHT FIXTURES IN THE FLORIDA AVENUE
 RIGHT-OF-WAY AND THE ENTRY DRIVE AND PLAZA TO MAINTAIN
 CONSISTENCY BETWEEN THE TWO PROJECTS.
 K. WORK WITHIN THE FUTURE STAGING AREA
  
 2) SHEET AE160 HAS AN ARROW CALLING OUT THE ADA ACCESS
 AISLE AS YELLOW STRIPING. THIS STRIPING SHALL BE BLUE,
 NOT YELLOW.
  
 3) SHEET AE501 AND SHEETS SW 120-SW170 DO NOT SHOW
 COMPLIANCE WITH THE CONDITION THAT THE SIGNS WITHIN THE
 CONVENTION CENTER GARAGE GUIDE USERS TO THE ELEVATORS
 AND STAIRWELLS AT THE NORTHWEST CORNER OF THE
 CONVENTION CENTER GARAGE AND CLEARLY SIGN THE REMAINING
 STAIRWELLS AS EMERGENCY EGRESS ONLY. SIGN S23 BEING
 SHOWN AT THE NORTHEAST STAIRWELL INDICATES THAT THE
 STAIRWELL IS FOR NORMAL EXITING OF THE GARAGE. IF THIS
 IS THE CASE, THEN THE EXIT TO THE STAIRWELL NEEDS TO BE
 CONNECTED INTO THE SITE SIDEWALK NETWORK ALONG THE
 NORTH SIDE OF THE GARAGE WITH NO LOSS OF LANDSCAPE.
 SIGN TYPE S22 IS SHOWN ON THE PLAN BUT NO DETAIL OF
 THIS SIGN IS INCLUDED.
  
 4) THE PHOTOMETRICS ON EACH FLOOR NEED TO BE CONTINUED
 OUTSIDE OF THE GARAGE WALL TO THE PROPERTY LINE AROUND
 THE GARAGE.
  
 5) PROVIDE INFORMATION ON HOW GLARE FROM THE INTERIOR
 AND EXTERIOR LIGHTS ONTO THE ADJACENT RESIDENTIAL
 PROPERTY AND RIGHTS-OF-WAY WILL BE CONTROLLED.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  