Plan Review Details - Permit 15060144
Plan Review Stops For Permit 15060144 |
Review Stop |
AIPP |
ART IN PUBLIC PLACES |
Rev No |
1 |
Status |
P |
Date |
2016-04-20 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2016-04-20 |
Time |
14:48 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2016-04-20 |
Time |
14:48 |
Sent To |
|
|
Notes |
2016-04-20 14:49:04 | RECEIVED EMAIL FROM SYBILLE WELTER; ROUTED TO RECORDS | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2015-10-30 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2015-10-30 |
Time |
14:42 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2015-10-30 |
Time |
14:42 |
Sent To |
|
|
Notes |
2015-10-27 08:45:50 | ***PROVISOS*** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. SEPARATE PERMITS (APPLICATION, PLANS, AND FEES BASED | | ON VALUE) ARE REQUIRED FOR FENCES, SIGNS, MONUMENT | | SIGNS, PARKING LOT, SITE LIGHTING, ROOFTOP ALUMINUM | | CANOPY. | | | | 2. PRODUCT APPROVALS (AND FLOOR HATCH SPEC SHEETS) ARE | | TO BE SUBMITTED AND REVIEWED **PRIOR TO PRODUCT | | INSTALLATION**. ALL SUBMITTALS ARE TO BE REVIEWED BY | | DESIGNER OF RECORD PRIOR TO SUBMITTAL TO THE BUILDING | | DIVISION, FBC 107. | | PRODUCTS TO COMPLY WITH THE FOLLOWING DESIGN PRESSURES | | (SEE S7.5): | | | | ZONE 1: +16 / -57.8 | | ZONE 2 : +16 / -93 | | ZONE 3: +16 / -93 | | ZONE 4: +41.8 / -44 | | ZONE 5: +41.8 / -71 | | | | PROVIDE FIRE RESISTANCE RATING INFORMATION WITH PRODUCT | | APPROVALS, IF APPLICABLE. | | | | PROVIDE ROOF/FLOOR HATCH SPECS WITH FIRE RESISTANCE | | RATING INFORMATION | | | | 3. FBC 2010 603.1, PROVIDE INFORMATION REGARDING THE | | THE VINYL COVERED FENCE. THIS SECTION LISTS THE | | COMBUSTIBLES PERMITTED IN TYPE I AND II BUILDINGS. | | COMPLIANCE NOT CLEAR. THIS IS REQUIRED AS A SUBMITTAL | | PRIOR TO INSTALLATION. | | | | 4. THREE SETS OF ALL DOCUMENTS REQUIRED FOR ALL | | REVISIONS AND SUBMITTALS. | | | | 5. SPEC BOOK HAS NOT BEEN REVIEWED. A COPY MAY BE | | RETAINED AS A PART OF THE PERMIT FILE BUT IS NOT TO BE | | USED IN LIEU OF PLANS TO DEMONSTRATE CODE COMPLIANCE. | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2015-10-26 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2015-10-26 |
Time |
13:44 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2015-10-26 |
Time |
13:44 |
Sent To |
|
|
Notes |
2015-10-26 13:46:46 | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FROM PROVISO LIST: | | | | ***REQUIRED PRIOR TO PERMIT ISSUANCE*** | | | | 11. SEE SHEETS SA1 THROUGH 6D AND OTHER SHEETS AS | | APPLICABLE, AS000, THE THRESHOLD STATEMENTS ARE NOT | | CONSISTENT WITH FLORIDA STATUTE 553.79(7)(D). PLEASE | | REVISE OR CLARIFY. | | | | THE LANGUAGE IN FS 553.79: | | | | ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED TO BE | | SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF | | RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE | | ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND | | SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM | | BUILDING CODES AND THE APPLICABLE FIRESAFETY STANDARDS | | AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH | | THIS CHAPTER AND CHAPTER 633. | | | | STATEMENT ON STRUCTURAL SHEETS: | | | | TO THE BEST OF THE ENGINEER'S KNOWLEDGE, THE PLANS AND | | SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM | | BUILDING CODES AND THE LOCAL AUTHORITY IN ACCORDANCE | | WITH THIS SECTION AND 633 FLORIDA STATUTES. | | | | (NOTE THAT LANGUAGE NOT CONSISTENT WITH STATUTE.) | | | | *************************************************** | | ***PROVISO*** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. INFORMATIONAL ONLY; SEPARATE PERMITS REQUIRED FOR | | FENCES, SIGNS, MONUMENT SIGNS, PARKING LOT, SITE | | LIGHTING. | | | | 2. INFORMATIONAL ONLY, PRODUCT APPROVALS ARE TO BE | | SUBMITTED AND REVIEWED PRIOR TO PRODUCT INSTALLATION. | | ALL SUBMITTALS ARE TO BE REVIEWED BY DESIGNER OF RECORD | | PRIOR TO SUBMITTAL TO THE BUILDING DIVISION, FBC 107. | | PRODUCTS TO COMPLY WITH THE FOLLOWING DESIGN PRESSURES | | (SEE S7.5): | | | | ZONE 1: +16 / -57.8 | | ZONE 2 : +16 / -93 | | ZONE 3: +16 / -93 | | ZONE 4: +41.8 / -44 | | ZONE 5: +41.8 / -71 | | | | 3. PROVISO, FBC 2010 ACCESSIBILITY 502.5, HEIGHT | | RESTRICTION SIGNAGE REQUIRED FOR ACCESSIBLE VANS. PER | | ARCHITECT, THIS IS INCLUDED ON SHEET SW129 (SEE INDEX, | | THIS SHEET NOT SUBMITTED FOR REVIEW). | | | | 4. PROVISO, FBC 2010 603.1, PROVIDE INFORMATION | | REGARDING THE THE VINYL COVERED FENCE. THIS SECTION | | LISTS THE COMBUSTIBLES PERMITTED IN TYPE I AND II | | BUILDINGS. COMPLIANCE NOT CLEAR. THIS IS REQUIRED AS A | | SUBMITTAL PRIOR TO INSTALLATION. | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2015-10-15 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2015-10-15 |
Time |
12:01 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2015-10-07 |
Time |
07:42 |
Sent To |
|
|
Notes |
2015-10-10 15:20:37 | ***PROVISO*** | | ***ISSUED AT CONTRACTOR'S RISK*** | | ***REVISION REQUIRED*** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. INFORMATIONAL ONLY; SEPARATE PERMITS REQUIRED FOR | | FENCES, SIGNS, MONUMENT SIGNS, PARKING LOT, SITE | | LIGHTING. | | | | 2. INFORMATIONAL ONLY, PRODUCT APPROVALS ARE TO BE | | SUBMITTED AND REVIEWED PRIOR TO PRODUCT INSTALLATION. | | ALL SUBMITTALS ARE TO BE REVIEWED BY DESIGNER OF RECORD | | PRIOR TO SUBMITTAL TO THE BUILDING DIVISION, FBC 107. | | | | 3. PROVIDE MORE INFORMATION REGARDING COST BREAKDOWN, | | FBC 109. IT IS NOT CLEAR HOW THE COST OF THE JOB | | DECREASED SIGNFICANTLY, ESPECIALLY IN LIGHT OF THE FACT | | THE CONSTRUCTION COSTS HAVE INCREASED SINCE | | APPLICATION. PROVIDE A COPY OF THE CONTRACT, FBC 109. | | PRIOR TO PAYMENT OF THIS PERMIT, FEES SHOULD BE | | RESOLVED AND APPLIED TO OTHER PERMITS AS APPLICABLE. | | | | 4. AS000, REVISE SITE PLAN TO SHOW COMPLIANCE WITH FBC | | 705.8, FBC 705.3 (ASSUMED PROPERTY LINE, DISTANCE OF | | EACH BUILDING TO THE ASSUMED PROPERTY LINE). | | INCORPORATE ANY EXCEPTIONS UTILIZED INTO THE PLAN. | | (THIS SHOULD BE CONSISTENT WITH THE CHANGES ALREADY | | MADE TO THE FOUNDATION PERMIT PLAN.) | | | | 2ND REVIEW, THE PLAN SUBMITTED (AS000 DATED 9/4/15) | | DOES NOT INCLUDE FOUNDATION REVISION NUMBER 3 DATED | | 6/9/15. THE PLAN SUBMITTED, ALTHOUGH THIS REVISION IS | | INCLUDED IN THE REVISION BLOCK, DOES NOT SHOW THE | | ASSUMED PROPERTY LINE CORRECTLY AND DOES NOT MATCH THE | | ISSUED FOUNDATION PERMIT. ALSO, THIS SHEET WAS REDLINED | | TO INCORPORATE EXCEPTIONS WHICH WERE INCLUDED IN THE | | RESPONSE LETTER BUT NOT INCLUDED ON THE PLAN. | | | | PROVIDE A PLAN CONSISTENT WITH THE ISSUED FOUNDATION | | PERMIT. IT IS UNCLEAR WHY THIS REVISION WOULD BE | | REMOVED FROM THIS SHEET. PLEASE CONFIRM THAT NO OTHER | | REVISIONS WERE REMOVED FROM THIS PLAN. A RE-REVIEW | | TYPICALLY TAKES LESS TIME AS ONLY NEW ITEMS ARE | | REVIEWED. IF REVISIONS WHICH WERE REQUIRED TO SHOW CODE | | COMPLIANCE ARE REMOVED FROM THE PLAN, A COMPLETE REVIEW | | OF THE ENTIRE PLAN IS REQUIRED AND TAKES SIGNIFICANTLY | | MORE TIME. | | | | 4A. SEE FOUNDATION PERMIT, REVISION 15090442 SHEET | | AS000 AND ISSUED SHEET AS000. IT APPEARS THAT, ALTHOUGH | | THE DIMENSIONS DEMONSTRATING CODE COMPLIANCE FBC 705.8, | | 705.3 WAS REMOVED, THAT CHANGE TO THE PLAN (REMOVAL OF | | REQUIRED DIMENSIONS) WAS NOT CLOUDED AND THEREFORE NOT | | REVIEWED. REVISE THIS SHEET AND SUBMIT AS A REVISION TO | | THE FOUNDATION PERMIT, INCORPORATING REDLINES WHICH | | INCLUDED THE EXCEPTIONS REFERRED TO IN THE RESPONSE | | LETTER (NOT A PART OF THE PERMIT RECORD). PLEASE SEE | | FOUNDATION COMMENT WHICH REQUESTED THAT ALL EXCEPTIONS | | UTILIZED BE INCORPORATED INTO THE PLAN (IN ORDER TO | | AVOID FIELD ISSUES AND TO CLEARLY DEMONSTRATE CODE | | COMPLIANCE). | | | | 4B. TWO SHEETS WERE ENTIRELY NEW SHEETS SUBMITTED AS A | | REVISION TO THE FOUNDATION PERMIT (S8.2, S9.4) BUT WERE | | NOT INDICATED AS NEW SHEETS AND THEREFORE ONLY CLOUDED | | REVISIONS WERE REVIEWED. SUBMIT A NEW INDEX AS A | | REVISION TO THE FOUNDATION PERMIT INDICATING THE NEW | | SHEETS. CONFIRM THAT ALL CHANGES IN THAT REVISION WERE | | CLOUDED. IN ADDITION TO THE CHANGE ON AS000, SEE | | F-PP110D; THIS SHEET INCLUDES A CHANGE WHICH WAS NOT | | CLOUDED. OTHER CHANGES WERE MADE TO THE STRUCTURAL | | SHEETS WHICH WERE NOT CLOUDED. PLEASE CONFIRM THAT ALL | | REVISIONS TO THE ISSUED FOUNDATION PERMIT WERE PROPERLY | | CLOUDED AND, IF ANY CHANGES WERE NOT, PLEASE CLOUD AT | | THIS TIME AND SUBMIT WITH THE REVISION SO THOSE ITEMS | | CAN BE REVIEWED. DISCREPANCIES WERE FOUND ON TWO S | | SHEETS, BUT A THOROUGH REVIEW WAS NOT DONE, ONLY A SPOT | | CHECK. | | | | SHEET AS000 TO BE CORRECTED AND SUBMITTED AS A | | REVISION. | | | | 5. PROVISO, FBC 1008, PER ARCHITECT, BOTH MEANS OF | | EGRESS GATES WILL INCLUDE PANIC HARDWARE. | | | | 6. PROVISO, FBC 2010 ACCESSIBILITY 502.5, HEIGHT | | RESTRICTION SIGNAGE REQUIRED FOR ACCESSIBLE VANS. | | | | 7. PROVISO, PROVIDE CALCULATIONS AND MORE INFORMATION | | TO DOCUMENT THE PERCENTAGES (OPEN PARKING GARAGE) SHOWN | | ON AE201 AND AE202. CALCULATIONS AND REPORT PREPARED BY | | SARAH MAMAN PE, FIRE PROTECTION ENGINEER, HAS BEEN | | RECEIVED VIA EMAIL; SIGNED, SEALED, DATED ORIGINALS | | REQUIRED. SUBMIT AS A "SUBMITTAL" (NO FEE). | | | | 8. PROVISO, PROVIDE ARCHITECT'S EXHIBIT "C" (ADDITIONAL | | DOCUMENTATION FOR "OPEN" CLASSIFICATION) FULL SIZE | | SHEETS, SIGNED AND SEALED (SUBMITTAL, NO FEE). | | | | 9. PROVISO, FBC 2010 ACCESSIBILITY 209.4, 503, REVISE | | PLAN TO SHOW THE VEHICULAR PULL UP SPACE AND ACCESS | | AISLE. SUBMIT AS A REVISION. (RESPONSE LETTER STATES | | THAT THIS IS SHOWN ON AE172 AND REVISED CIVIL DRAWINGS. | | SEE SECTION 503.3.3, THE ACCESS AISLE IS TO BE MARKED. | | IT IS NOT CLEAR ON AE172 WHERE THE LOADING ZONE IS | | LOCATED AND I WAS UNABLE TO FIND THE MARKED ACCESS | | AISLE, PLEASE REVISE PLAN. PLEASE REVISE PLANS TO SHOW | | DIMENSIONS OF FBC 2010 ACCESSIBILITY 503.2, THE PULL UP | | SPACE, AND 503.3, THE MARKED ACCESS AISLE. AN | | ACCESSIBLE PASSENGER LOADING ZONE COMPLIANT WITH 503 IS | | REQUIRED. RESPONSE APPEARS TO INDICATE AGREEMENT FROM | | THE DESIGNER, BUT IT IS NOT CLEAR HOW THIS HAS BEEN | | ADDRESSED.) | | | | 10. PROVISO, FBC 2010 603.1, PROVIDE INFORMATION | | REGARDING THE THE VINYL COVERED FENCE. THIS SECTION | | LISTS THE COMBUSTIBLES PERMITTED IN TYPE I AND II | | BUILDINGS. COMPLIANCE NOT CLEAR. THIS IS REQUIRED AS A | | SUBMITTAL PRIOR TO INSTALLATION. | | | | ***REQUIRED PRIOR TO PERMIT ISSUANCE*** | | | | 11. SEE SHEETS SA1 THROUGH 6D AND OTHER SHEETS AS | | APPLICABLE, AS000, THE THRESHOLD STATEMENTS ARE NOT | | CONSISTENT WITH FLORIDA STATUTE 553.79(7)(D). PLEASE | | REVISE OR CLARIFY. | | | | THE LANGUAGE IN FS 553.79: | | | | ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED TO BE | | SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF | | RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE | | ARCHITECT?S OR ENGINEER?S KNOWLEDGE, THE PLANS AND | | SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM | | BUILDING CODES AND THE APPLICABLE FIRESAFETY STANDARDS | | AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH | | THIS CHAPTER AND CHAPTER 633. | | | | STATEMENT ON STRUCTURAL SHEETS: | | | | TO THE BEST OF THE ENGINEER'S KNOWLEDGE, THE PLANS AND | | SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM | | BUILDING CODES AND THE LOCAL AUTHORITY IN ACCORDANCE | | WITH THIS SECTION AND 633 FLORIDA STATUTES. | | | | (NOTE THAT LANGUAGE NOT CONSISTENT WITH STATUTE.) | | | | STATEMENT ON AS000: | | | | TO THE BEST OF ARCHITECT?S KNOWLEDGE, THE PLANS AND | | SPECIFICATIONS COMPLY WITH THE APPLICABLE FIRE SAFETY | | STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN | | ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE. | | | | (NOTE THAT MINIMUM BUILDING CODES WAS OMITTED.) | | | | PLEASE EITHER REVISE THE STATEMENT TO BE CONSISTENT | | WITH THE STATUTE OR EMAIL RATIONALE FOR LANGUAGE WHICH | | DEVIATES FROM THE STATUTE. | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2015-07-16 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2015-07-16 |
Time |
18:19 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2015-06-05 |
Time |
07:56 |
Sent To |
|
|
Notes |
2015-07-16 18:20:34 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. INFORMATIONAL ONLY; SEPARATE PERMITS REQUIRED FOR | | FENCES, SIGNS, MONUMENT SIGNS, PARKING LOT, SITE | | LIGHTING. | | | | 2. PROVIDE A COST BREAKDOWN FOR THE PROJECT. SOME ITEMS | | WILL REQUIRE SEPARATE PERMITS (SUCH AS THE PARKING LOT | | AND LANDSCAPING) AND SHOULD NOT BE INCLUDED IN THE | | BUILDING PERMIT VALUE. | | | | 3. INFORMATIONAL ONLY, PRODUCT APPROVALS ARE TO BE | | SUBMITTED AND REVIEWED PRIOR TO PRODUCT INSTALLATION. | | ALL SUBMITTALS ARE TO BE REVIEWED BY DESIGNER OF RECORD | | PRIOR TO SUBMITTAL TO THE BUILDING DIVISION, FBC 107. | | | | 4. AS000, REVISE SITE PLAN TO SHOW COMPLIANCE WITH FBC | | 705.8, FBC 705.3 (ASSUMED PROPERTY LINE, DISTANCE OF | | EACH BUILDING TO THE ASSUMED PROPERTY LINE). | | INCORPORATE ANY EXCEPTIONS UTILIZED INTO THE PLAN. | | (THIS SHOULD BE CONSISTENT WITH THE CHANGES ALREADY | | MADE TO THE FOUNDATION PERMIT PLAN.) | | | | 5. LS110 AND C2.00, FBC 1008.2, PROVIDE A DETAIL FOR | | THE GATES AND GATE HARDWARE FOR THE PEDESTRIAN GATES | | ADJACENT TO THE FIRE LANE. THE GATES ARE TO MEET ALL OF | | THE REQUIREMENTS AS DOORS AS THEY ARE IN THE EXIT | | DISCHARGE FOR SEVERAL EXITS. | | | | 6. C3.05, LEGEND DOES NOT INCLUDE THE GRAPHIC FOR THE | | FIRE LANE. ON OTHER SHEETS, THE FIRE LANE IS NOTED AS | | STABILIZED GRADE. LS110, THE SIDEWALK WHICH LEADS TO | | THE TWO GATES APPEAR TO BE BLOCKED BY STAIRS (FOR | | EXAMPLE, SEE STAIR 3 AND DOOR 105). IN OTHER AREAS (SE | | STAIR TO BASEMENT, SE CORNER OF BUILDING) SIDEWALK | | WIDTH IS NOT CLEAR. SEE FBC 1003.1, 1005.1, 1003.4, | | 1003.5. ARE OCCUPANTS TO WALK AROUND THE STAIRS, ON THE | | FIRE LANE, WHICH APPEARS UNPAVED? | | | | 7. LS110 AND C2.00, THE EXIT AT THE SOUTH (AND OTHER | | EXITS) APPEAR TO BE OBSTRUCTED BY OTHER STAIRS | | (SIDEWALK NOT CONTINUOUS). SEE FBC 1003.6, MEANS OF | | EGRESS CONTINUITY. REVISE THE LIFE SAFETY PLAN TO SHOW | | EXIT DISCHARGE, ROUTE TO THE PUBLIC WAY, WITH MORE | | INFORMATION REGARDING THE FIRE EXIT LANE (SHOWN AS | | "STABLILIZED" RATHER THAN PAVED) AS IT APPEARS THAT | | OCCUPANTS WILL BE FORCED TO WALK ACROSS THE FIRE LANE, | | AROUND THE STAIRS, AS A PART OF THE EXIT DISCHARGE. | | | | 8. LS120, FBC 2010 ACCESSIBILITY 208.3, 103, AND TITLE | | II ADA (STATE AND LOCAL GOVERNMENT REQUIREMENTS), THERE | | ARE SEVERAL ELECTRICAL VEHICLE SPACES BUT IT DOES NOT | | APPEAR THAT ANY OF THEM ARE USABLE BY AN INDIVIDUAL WHO | | REQUIRES AN ACCESSIBLE SPACE. AT LEAST ONE OF THE | | SPACES IS REQUIRED TO BE ACCESSIBLE (MEETING THE | | PARKING SPACE DIMENSION REQUIREMENTS, ACCESS AISLE). IT | | IS RECOMMENDED THAT AN EMAIL ADVISING HOW THIS WILL BE | | ADDRESSED IS SUBMITTED PRIOR TO PLAN RESUBMITTAL FOR A | | COURTESY REVIEW TO AVOID REPEAT COMMENTS. | | | | 9. LS SHEETS, SEE FBC 1007, FBC 2010 ACCESSIBILITY 207, | | PLEASE IDENTIFY METHOD OF COMPLAINCE AND NOTE | | ACCESSIBLE EXITS ON THE PLAN. A REVIEW OF THIS ITEM HAS | | NOT BEEN DONE AS METHOD SELECTED (IBC 2001 OR IBC 2003) | | HAS NOT BEEN DETERMINED. PLEASE NOTE THAT, SINCE THE | | BUILDING IS NOT SPRINKLERED AT THIS TIME, IT APPEARS | | THAT AREA OF REFUGE WILL BE REQUIRED. | | | | TO AVOID POSSIBLE COMMENTS ON THIS ITEM, A COURTESY | | REVIEW CAN BE REQUESTED PRIOR TO RESUBMITTAL. | | | | 10. LS120, FBC 2010 ACCESSIBILITY 502.5, HEIGHT | | RESTRICTION SIGNAGE REQUIRED FOR ACCESSIBLE VANS. | | | | 11. LS110, ALLOWABLE AREA IS SHOWN USING FBC TABLE | | 406.3.5 FOR OPEN PARKING GARAGES. SEE FIRE COMMENTS. IF | | THIS BUILDING IS DETERMINED TO BE AN ENCLOSED PARKING | | GARAGE, PLEASE CONTACT ME TO DISCUSS HOW TO PROCEED. | | | | 12. PROVIDE CALCULATIONS AND MORE INFORMATION TO | | DOCUMENT THE PERCENTAGES (OPEN PARKING GARAGE) SHOWN ON | | AE201 AND AE202, ESPECIALLY THE GROUND LEVEL (SHOWN AS | | 20.5%; 20% REQUIRED). AS THIS ISSUE IS CRUCIAL TO THE | | ENTIRE REVIEW AND BUILDING DESIGN, THIS INFORMATION CAN | | BE SENT VIA EMAIL FOR PRELIMINARY REVIEW PRIOR TO | | RESUBMITTAL OF THE PLAN. | | | | THIS REVIEW IS BEING PERFORMED TREATING THE BUILDING AS | | AN OPEN PARKING GARAGE. PLEASE NOTE THAT, SUBJECT TO | | REVIEW OF CALCULATIONS FOR THE OPENINGS REQUIRED, IF | | ADDITIONAL ITEMS ARE ADDED WHICH EXCEED CODE COMPLIANCE | | FOR AN OPEN PARKING GARAGE, THE ADDITIONAL SYSTEMS WILL | | NOT AFFECT THE DESIGNATION OF OPEN PARKING GARAGE. THE | | CLASSIFICATION OF OPEN PARKING GARAGE WILL BE BASED ON | | OPENING CALCULATIONS AND THE DEFINITION IN THE FBC. | | | | **7/17/15 - CALCULATIONS AND REPORT PREPARED BY SARAH | | MAMAN PE, FIRE PROTECTION ENGINEER, HAS BEEN RECEIVED | | VIA EMAIL (PENDING REVIEW AND MEETING)** | | | | 13. FBC 2010 ACCESSIBILITY 209.4, 503, REVISE PLAN TO | | SHOW THE VEHICULAR PULL UP SPACE AND ACCESS AISLE. | | | | 14. LS110, 0 FIRE RATING SHOWN FOR THE ROOF; FBC TABLE | | 601 REQUIRES 1 HOUR, FOOTNOTE B APPLIES IF THE ROOF IS | | OVER 20FT ABOVE THE FLOOR BELOW. PLEASE REVISE OR | | INCORPORATE APPLICABLE EXCEPTION INTO THE PLAN FOR 0 HR | | FIRE RATING. | | | | 15. LS110, BUILDING HEIGHT AND AREA ADDRESSES ONLY THE | | S2 OCCUPANCY. PLEASE REVISE TO INCLUDE THE BUSINESS | | OCCUPANCY. IS THIS AREA BEING TREATED AS AN ACCESSORY | | OR MIXED USE? SEE FBC 508. NO FIRE RATED SEPARATIONS | | SHOWN BETWEEN BUSINESS AND S2. | | | | 16. LS110 AND OTHER SHEETS, FBC 708.14.1, ELEVATOR | | LOBBY WALL IS NOT SHOWN AS A FIRE PARTITION. EITHER | | REVISE PLAN TO INCLUDE REQUIRED FIRE RATING OR | | INCORPORATE AN APPLICABLE EXCEPTION INTO THE PLAN. | | | | 17. LS110, FBC 509.3(5) STATES THAT THE GROUP S2 | | ENCLOSED PARKING GARAGE IS FOR THE EXCLUSIVE USE OF | | PARKING, BUT ALLOWS AN OFFICE, WAITING ROOM AND TOILET | | ROOM NOT TO EXCEED 1000 SF, AND MECHANICAL EQUIPMENT | | ROOMS IN THE ENCLOSED PARKING GARAGE PORTION. THIS | | SHEET SHOWS THREE UTILITY SPACES, B004, B005 AND B006 | | AND ONE UNIDENTIFIED SPACE (ADJACENT TO B004). IT DOES | | NOT APPEAR THAT THE CODE ALLOWS THE UTILITY SPACES, AND | | MORE INFORMATION IS REQUIRED FOR THE UNIDENTIFIED | | SPACE. PROVIDE SF AREA AND RATIONALE FOR THESE SPACES | | OR REVISE TO BE CONSISTENT WITH THE ALLOWABLE USES IN | | THE CODE. | | | | 18. LS110, PLEASE CORRECT THE TYPO FBC 1022.1 EXCEPTION | | 4 (PLAN STATES EXCEPTION 5 WHICH IS NOT APPLICABLE). | | | | 19. LS110, PLEASE CORRECT THE APPARENT TYPO (OR | | CLARIFY) FBC 905.3.1, EXCEPTION 3 REFERS TO AREAS | | SUBJECT TO FREEZING. | | | | 20. LS120, PROVIDE DIMENSIONS FOR THE FIRE COMMAND | | CENTER, FBC 403.4.5, 911.1.3. | | | | 21. LS120, STAIRS 1 AND 2, WILL THERE BE SIGNAGE TO | | HELP TO PREVENT OCCUPANTS FROM ATTEMPTING TO ENTER THE | | BASEMENT DOOR RATHER THAN THE EXIT? NOT REQUIRED BUT | | RECOMMENDED. | | | | 22. LS130 AND OTHER SHEETS, CLARIFY USE OF THE UTILITY | | SPACE AND INCLUDE THESE SPACES ON LS110 (SQUARE FOOT | | AREAS, OCCUPANCY CLASSIFICATION, HOW THEY ARE | | CLASSIFIED FBC 508). | | | | 23. FBC 1009.6.2, IT APPEARS THAT THE SOME OF THE EXIT | | STAIRS WILL BE EXPOSED TO THE WEATHER. PROVIDE | | INFORMATION (CROSS SLOPE?) TO SHOW HOW WATER WILL BE | | PREVENTED FROM ACCUMULATING. | | | | 24. AE160, SPECIFY DESIGN PRESSURES FOR THE PROPOSED | | ROOF HATCHES. IT APPEARS THAT THEY WILL BE IN ZONE 2. | | | | 25. AE152, DETAILS 1 AND 5, IDENTIFY THE SQUARES WHICH | | APPEAR TO BE HATCHES. | | | | 26. ENERGY CALCS REQUIRED, FBC 2010 ENERGY CONSERVATION | | 103. | | | | 27. FBC 2010 ENERGY CONSERVATION, CONFIRM THAT | | INFORMATION REQUIRED BY 103.2.2 IS INCLUDED IN THE | | PLAN. | | | | 28. FBC 2010 603.1, PROVIDE INFORMATION REGARDING THE | | ACRYLIC FABRIC AND THE VINYL COVERED FENCE. THIS | | SECTION LISTS THE COMBUSTIBLES PERMITTED IN TYPE I AND | | II BUILDINGS. COMPLIANCE NOT CLEAR. | | | | 29. 2 AE160 AND DETAILS, PENETRATIONS INTO A RATED | | STAIR SHOULD BE LIMITED TO THOSE REQUIRED FOR THE | | ENCLOSURE, FBC 1022.4; DRAINS ARE SHOWN. | | | | 30. FBC 703, PROVIDE DETAILS FOR THE FIRE RATED | | STRUCTURAL ELEMENTS TO SHOW COMPLIANCE WITH TYPE 1B | | BUILDING PER TABLE 601. | | | | 31. AE150A AND OTHER SHEETS, UPPER DECK UNDER AWNING | | PARKING INCLUDES NON ACCESSIBLE SPACES ONLY. SEE FBC | | 2010 ACCESSIBILITY 103, EQUIVALENT FACILITATION. IT | | APPEARS THAT EITHER ACCESSIBLE SPACES SHOULD BE | | INCLUDED UNDER AWNING OR ACCESSIBLE SPACES MOVED TO A | | COVERED FLOOR. | | | | REVISED 8/28/15 - PER ROBERT BROWN, BUILDING OFFICIAL, | | AS DISCUSSED IN MEETING W/ARCHITECT, IT IS ACCEPTABLE | | FOR ACCESSIBLE PARKING TO REMAIN AS DESIGNED DUE TO THE | | NUMBER OF ACCESSIBLE SPACES UNDER COVER ON OTHER | | FLOORS. | | | | 32. FBC 107, DUE TO THE SIZE OF THIS PLAN, IT IS | | SUGGESTED THAT EITHER THE PLAN BE SUBMITTED DIGITALLY | | OR THAT THE PLAN SETS BE SPLIT INTO TWO OR THREE ROLLS | | (ARCH, STRUCTURAL, MEP), FBC 107. | | | | WHEN RESUBMITTING, IF THIS REMAINS A PAPER SUBMITTAL | | RATHER THAN DIGITAL, ALL OLD SHEETS ARE TO BE REMOVED | | FROM THE BOUND SET AND NEW SHEETS PUT IN THEIR PLACE. | | THE OLD SHEETS ARE TO BE RETAINED (ALL SETS) AND BOUND | | SEPARATELY FROM THE NEW SETS. PLEASE DO NOT REMOVE | | ANYTHING FROM THE DEPARTMENT AS SOMETIMES OLD SHEETS | | ARE USED TO AVOID RE-STAMPS BY TRADES WHICH HAVE PASSED | | OR PARTIALLY PASSED. | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2015-11-18 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2015-11-18 |
Time |
12:08 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2015-11-18 |
Time |
11:30 |
Sent To |
E |
|
Notes |
2015-11-18 12:10:21 | PER THE PROVIDED RESPONSE LETTER AND REVISED SHEET | | EE405, THE REQUIRED EXIT LIGHTING HAS BEEN ADDED TO THE | | TOP LEVEL. NOW ALL THAT REMAINS IS FOR SOMEONE TO | | PROPERLY ASSEMBLE THE PLANS SET FOR STAMPING. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2015-10-01 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2015-10-01 |
Time |
16:54 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2015-10-01 |
Time |
15:50 |
Sent To |
|
|
Notes |
2015-10-01 16:56:30 | I PUT A CALL OUT TO MR. FERNANDO DELDAGO TO DISCUSS | | WITH HIM THE STILL REMAINING DEFICIENCIES, WHICH ARE | | MISSING EXIT LIGHTS IN THE ROOF LEVEL OF THE GARAGE. | | RETURNED TO C35 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2015-08-31 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2015-08-31 |
Time |
19:45 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2015-08-26 |
Time |
09:26 |
Sent To |
I |
|
Notes |
2015-08-31 19:52:26 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS | | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE | | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO | | THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE | | CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. | | | | 1. THE EXIT LIGHT DEFICIENCY IS TYPICAL THROUGH OUT THE | | LEVELS. THERE SHALL BE AN EXIT LIGHT MID WAY IN EACH OF | | THE PARKING AISLES. | | 2. THE DIRECTION OF THE FACE OF THE LIGHTS SHALL BE | | REVIEWED AS WELL. | | 3. THE PANEL LABELS DO NOT MATCH THOSE INDICATED ON THE | | RISER DIAGRAM. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE | | PREVIOUSLY REVIEWED SHEETS. | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | CONTACT ME DIRECTLY. | | |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
2 |
Status |
P |
Date |
2015-11-23 |
|
|
Cont ID |
|
Sent By |
cranford |
Date |
2015-11-23 |
Time |
10:51 |
Rev Time |
0.00 |
Received By |
cranford |
Date |
2015-11-19 |
Time |
09:12 |
Sent To |
|
|
Notes |
2015-11-23 10:51:07 | ALSO SEE ENGINEERING DEVELOPMENT APPROVAL E15040015 |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
P |
Date |
2015-06-22 |
|
|
Cont ID |
|
Sent By |
cranford |
Date |
2015-06-22 |
Time |
09:41 |
Rev Time |
0.00 |
Received By |
cranford |
Date |
2015-06-22 |
Time |
09:37 |
Sent To |
|
|
Notes |
2015-06-22 09:41:04 | 1. DISCREPANCIES BETWEEN PLUMBING PLAN VIEW, | | SCHEMATICS, AND DETAILS FOR SUMP DISCHARGE PUMP LINE | | DIAMETERS. ALSO, DISCREPANCY IN PIPE DIAMETER BETWEEN | | CIVIL PLANS AND PLUMBING PLANS. | | | | 2. ON SHEET PP110A, SANITARY DISCHARGE PIPING IS | | LABELED AS DRAINAGE NEAR NORTHWEST CORNER OF PAGE. | | | | SEE ENGINEERING DEVELOPMENT APPLICATION E15040015 FOR | | CIVIL REVIEW COMMENTS. | | | | KELLY CRANFORD, PE | | LAND DEVELOPMENT ENGINEER | | (561)494-1098 | | [email protected] |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2015-10-30 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2015-10-30 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2015-10-30 |
Time |
13:14 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2015-09-22 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2015-09-22 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2015-09-22 |
Time |
15:38 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2015-06-10 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2015-06-08 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2015-06-05 |
Time |
11:00 |
Sent To |
|
|
Notes |
2015-06-08 16:19:39 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | 1) SHEET LS 110, THE PROPOSED PROJECT SHALL MEET THE | | REQUIREMENTS OF THE 5TH EDITION OF FLORIDA FIRE | | PREVENTION CODE INCLUDING THE 2012 EDITION OF NFPA 1 | | AND NFPA 101 AND ALL OTHER APPLICABLE CODES OR | | STANDARDS. PLEASE MAKE CORRECTIONS TO THE DRAWING SET. | | | | 2) SHEET LS110 EXIT #126 SE, LEADS TO AN AREA THAT HAS | | LOCKED GATES AND IS NOT LEADING TO A PUBLIC WAY. THE | | EXIT IS NONCONFORMING | | | | 3) SHEET LS 120 EXITS # 105 S MIDDLE & 133.SE, LEAD TO | | AN AREA THAT HAS LOCKED GATES AND IS NOT LEADING TO A | | PUBLIC WAY. THESE EXITS ARE NONCONFORMING | | | | 4) EXIT SIGNAGE DIRECTIONAL'S ON ALL FLOOR LEVELS SHALL | | BE REVIEWED AND ADJUSTED TO POINT IN THE DIRECTION OF | | THE EXIT. | | | | 5) THE GATES ATEACH END OF THE FIRE LANE NOTE A KNOX | | BOX LOCATION. THE KNOX BOX CAN ONLY BE ACCESSED FROM | | ONE DIRECTON. GATE ACCESS SHALL BE FROM BOTH | | DIRECTIONS. | | | | 6) THERE IS INSUFFICIENT INFORMATION PROVIDED TO | | DETERMINE THAT IT IS AN OPEN PARKING STRUCTURE. THE | | DEFINITION AND CONSTRUCTION OF THIS AS AN OPEN PARKING | | STRUCTURE IS NOT APPROVED. THE METAL FACADE STRUCTURE | | DOES NOT PROVIDE EACH PARKING LEVEL OPENINGS TO THE | | ATMOSPHERE. ADDITIONALLY, THE OPENINGS ARE NOT | | DISTRIBUTED OVER 40 PERCENT OF THE BUILDING PERIMETER | | OR UNIFORMLY OVER TWO OPPOSING SIDES. OPEN PARKING | | STRUCTURES PROVIDE FOR VENTILATION. WITH THE ADDITION | | OF THE METAL FACADE THE VENTILATION IS SIGNIFICANTLY | | REDUCED THAN IF THE THE AREAS WERE FULLY OPEN | | | | THE METAL FACADE IS A PERFORMANCE BASED OPTION OF AN | | OPEN PARKING STRUCTURE. PLEASE PROVIDE ADDITIONAL | | INFORMATION AS OUTLINED IN NFPA 1, CHAPTER 5 | | PERFORMANCE BASED OPTION FOR REVIEW AND CONSIDERATION | | OF AN OPEN PARKING STRUCTURE. | | | | THERE APPEARS TO BE NO WAY TO MEASURE OR TEST THAT THE | | PROPOSED WILL PROVIDE FOR VENTILATION. | | | | 7) BASED ON # 6, THE PARKING STRUCTURE IS REQUIRED TO | | BE FULLY SPRINKLED WITH MECHANICAL VENTILATION. | | | | 8) SHEET AE301, PROVIDE ADDITIONAL MORE DETAILED | | INFORMATION FOR THE STATEMENT, " VEHICLE RESTRAINT | | CABLE SYSTEM TYP. WITH WOVEN EXTERIOR ACRYLIC FABIC | | SCREEN WITH REINFORCED VINYL EDGES ONLY @ PERIMETER OF | | THE BUILDING." | | WHAT PURPOSE DOES IT SERVE? IS THIS FABRIC LFMAE | | RETARDENT? IS THIS FABRIC COVERING CALCULATED IN THE | | OPEN GARAGE FORMULA? THIS AREA WOULD NOT BE OPEN TO THE | | ATMOSPHERE AND SHOULD BE CLACULATED AS CLOSED. | | | | 9) THE FIRE HYDRANT AND FDC ARE IN LOCATIONS THAT ARE | | NOT READILY ACCESSIBLE TO FIRE APPARATUS. THE HYDRANT | | AND FDC SHOULD BE MOVED OUT IN THE AREA OF THE FIRE | | COMMAND CENTER AND KNOX BOX. | | | | 10) THERE APPEARS TO BE ONLY ONE WATER SUPPLY TO THE | | STRUCTURE, TWO ARE REQUIRED. | | | | 11) SHEET FA 701, RISER LEGEND # 10, REMOTE GENERATOR | | STATUS PANEL SHALL INCLUDE AN ADDITIONAL STATEMENT OF | | "MANUAL START AND TRANSFER FEATURES" |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2015-11-24 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2015-11-24 |
Time |
09:32 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2015-10-21 |
Time |
09:53 |
Sent To |
|
|
Notes |
2015-10-22 09:53:37 | RESUB ROUTED TO C28 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2015-10-22 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2015-10-22 |
Time |
09:52 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2015-09-16 |
Time |
11:06 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2015-08-31 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2015-08-31 |
Time |
19:52 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2015-06-03 |
Time |
12:36 |
Sent To |
|
|
Notes |
2015-08-31 19:54:49 | 8/31/15 - FAILED ELECTRICAL REVIEW. CONTRACTOR NOTIFIED | | VIA EMAIL. SENT TO LARGE DENIED BIN "W". MA | 2015-06-05 08:03:49 | C25 & C26 | | |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
N |
Date |
2015-06-11 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2015-06-11 |
Time |
14:48 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2015-06-11 |
Time |
14:48 |
Sent To |
|
|
Notes |
2015-06-11 14:49:01 | NOT REQUIRED PER WILLIE SWOPE (COUNTY OWNED) | | SEE EMAIL IN FILE | | |
|
|
Review Stop |
L |
LANDSCAPING |
Rev No |
1 |
Status |
N |
Date |
2015-07-14 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2015-07-14 |
Time |
13:30 |
Rev Time |
0.25 |
Received By |
eschneid |
Date |
2015-07-14 |
Time |
13:30 |
Sent To |
|
|
Notes |
2015-08-20 09:57:11 | MALBERRAN'S DESK | 2015-07-14 13:44:17 | SEPARATE LANDSCAPE PERMIT REQUIRED. PLEASE INCLUDE A | | COST ESTIMATE FOR THE VALUE OF THE LANDSCAPE | | INSTALLATION. | | | | SEPARATE IRRIGATION PERMIT REQUIRED. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2015-11-02 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2015-11-02 |
Time |
14:01 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2015-11-02 |
Time |
14:01 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2015-09-30 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2015-09-30 |
Time |
08:52 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2015-09-29 |
Time |
14:26 |
Sent To |
|
|
Notes |
2015-09-30 10:14:16 | 2ND REVIEW: FBC 2010 MECHANICAL | | PERMIT #15060144 | | 9/30/15 | | | | 1) SHEET MM701: INDICATE THE DURATION OF OPERATION FOR | | THE PRESSURIZATION FANS SF-1 & 2 AFTER DETECTION OF A | | FIRE- REFER TO SECTION 909.4.6 FBC-10 BUILDING AND | | PROVIDE NOTES TO CLARIFY. | | 2) MM110: INDICATE HOW THE BASEMENT LEVEL UTILITY ROOMS | | B005 & B006 ARE BEING VENTILATED. SHOW THE MEANS AND | | PROVIDE CALCULATIONS- SECTION 401 FBC-10 MECHANICAL. | | 3) MM220: PROVIDE VENTILATION CALCULATIONS FOR THE | | UTILITY ROOM. PLEASE REFER TO SHEET AE140- THE UTILITY | | ROOM IS ALSO FOUND ON FLOOR LEVELS 2,3,4,6, & 8; AND ON | | FLOOR LEVELS 1,5, & 7 IT IS LABELED AS AN ELECTRICAL | | ROOM . PLEASE SHOW THE MEANS OF VENTILATION FOR ALL OF | | THESE ROOMS AND PROVIDE SIZING CALCULATIONS. | | 4) MM220 & MM801: PROVIDE INSTALLATION AND SUPPORT | | DETAILS FOR THE SF-1 AND SF-2 PRESSURIZATION FANS. | | 5) MM801, DETAIL 11: THE HEIGHT OF THE RECIRCULATING | | FANS ABOVE THE FINISH FLOORS SHALL BE MINIMUM 8' PER | | SECTION 304.6 FBC-10 MECHANICAL. PLEASE CORRECT THE | | DETAIL. | | 6) MM802, DETAIL 3: THE DETAIL IS INCOMPLETE: PROVIDE | | FASTENING DETAILS FOR ATTACHING THE CONDENSERS TO THE | | BRACKET AND THE BRACKET TO THE WALL. DETAIL 4- PROVIDE | | THE TYPE, SIZE, AND DEPTH OF EMBEDMENT FOR THE | | CONDENSER TIE-DOWN ANCHOR BOLTS. PLEASE NOTE: SITE | | SPECIFICA WINDLOAD ENGINEERING IS REQUIRED FOR ALL | | EXTERIOR APPLIANCE INSTALLATIONS- SECTION 301.12 | | /FBC-10 MECHANICAL. | | 7) PROVIDE THE SEQUENCE OF OPERATION FOR THE | | RECIRCULATION FANS, AND ALL OF THE VARIOUS ROOM EXHAUST | | FANS. | | 8) DUCTLESS SYSTEM 8 SHOWN IN THE SCHEDULE ON MM601 IS | | NOT SHOWN ON THE PLANS- PLEASE INDICATE THE SYSTEM | | LOCATION ON THE PLANS. | | 9) AC CALCULATIONS WERE NOT PROVIDED FOR AC SYSTEMS 2, | | 3, 6, 7, & 8- PLEASE PROVIDE THE CALCULATIONS. | | 10) AC SYSTEMS 2, 3, 6, 7 & 8 ARE NOT LISTED IN THE | | ENERGY CALCULATION FORM 506-2010- PLEASE PROVIDE THE | | COMPLIANCE DATA. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2015-06-24 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2015-06-24 |
Time |
13:45 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2015-06-24 |
Time |
13:45 |
Sent To |
|
|
Notes |
2015-06-24 14:57:21 | 1ST REVIEW: FBC 2010 MECHANICAL | | | | 1) PROVIDE AN EXHAUST VENTILATION CALCULATION FOR THE | | BASEMENT LEVEL PARKING GARAGE TO VERIFY EF-1, 2, & 3 | | HAVE BEEN SIZED TO PROVIDE THE RATES REQUIRED BY TABLE | | 403.3 AND SECTION 404 FBC-10 MECHANICAL. | | 2) CLARIFY THE METHOD BY WHICH THE STAIR PRESSURIZATION | | FANS (EF-4, 5 AND SF-1,2) WERE SIZED: PROVIDE | | CALCULATIONS CONSISTENT WITH SECTION 909.6 INCLUSIVE | | FBC-10 BUILDING. | | 3) PROVIDE EXHAUST VENTILATION CALCULATIONS FOR THE | | BOOSTER PUMP, STORAGE, AND FIRE PUMP ROOMS- ASHRAE | | 62.1-07. | | 4) PROVIDE AC LOAD CALCULATIONS FOR ALL CONDITIONED | | ROOMS AND SPACES IN ACCORDANCE WITH ACCA MANUAL N, OR | | ASHRAE/ACCA STANDARD 183- REFERENCE SECTION 503.2.1 | | FBC-10 ENERGY CONSERVATION. | | 5) PROVIDE ENERGY CALCULATIONS FOR THE PROPOSED PROJECT | | PER SECTION101 FBC-10 ENERGY: SUBMIT TWO COPIES OF | | EITHER FORM 502 OR 506 SIGNED BY THE DESIGN | | PROFESSIONAL OF RECORD. | | 6) SHEET MM110: PROVIDE ADDITIONAL DETAILS OR NOTES | | INDICATING THE SPACING AND MOUNTING HEIGHT LOCATIONS OF | | THE C0 DETECTORS PER THE MANUFACTURER'S | | RECOMMENDATIONS. LIST THE MAKE AND MODEL NUMBERS OF THE | | DEVICES AND SUBMIT PRODUCT DATA SHEETS REVIEWED AND | | APPROVED BY THE DESIGN PROFESSIONAL OF RECORD. | | 7) MM220: CU 3 & 6 SHOWN IN DETAIL 8 SHALL BE INSTALLED | | A MINIMUM OF 8 FT. ABOVE THE FLOOR PER SECTION 304.6 | | FBC-10 MECH. | | 8) MM230: THE BOTTOM OF THE EXHAUST LOUVERS FOR THE | | BASEMENT EXHAUST FANS AS SHOWN IN DETAIL 4 SHALL BE | | INSTALLED A MINIMUM OF 10 FT. ABOVE THE ADJOINING | | GRADE- SECTION 501.2.1(2) FBC-10 MECH. | | 9) MM801: THE RECIRCULATING FANS SHOWN IN DETAIL 11 | | SHALL BE INSTALLED AT LEAST 1FT. HIGHER THAN THE GARAGE | | DOOR PER SECTION 304.6. | | 10) MM801: PROVIDE INSTALLATION DETAILS FOR THE | | FIRE/SMOKE DAMPERS, AND THE DUCT SMOKE DETECTORS. | | 11) PROVIDE A SUBMITTAL PACKAGE PREPARED BY THE DESIGN | | PROFESSIONAL OF RECORD THAT INCLUDES: A) FLORIDA | | PRODUCT APPROVALS AND/OR MIAMI-DADE NOA'S FOR THE ROOF | | MOUNTED EXHAUST FANS, THE INTAKE AND EXHAUST LOUVERS, | | AND THE CONDENSER WALL MOUNT BRACKETS. B) | | MANUFACTURER'S SPECIFICATIONS FOR THE EXHAUST AND | | INTAKE FANS, THE AC UNITS, THE MOTORIZED INTAKE | | DAMPERS, THE C0 DETECTORS, THE RECIRCULATION FANS, THE | | FIRE/SMOKE DAMPERS, AND THE DUCT SMOKE DETECTORS. IN | | REGARD TO ALL EXTERIOR INSTALLATIONS SUBJECT TO WIND | | LOAD, THE DESIGN PROFESSIONAL OF RECORD SHALL CALCULATE | | DESIGN PRESSURES AND PROVIDE TIE-DOWN ENGINEERING, AND | | ALSO CIRCLE OR HIGHLIGHT ALL APPLICABLE NOTES AND | | DETAILS IN THE NOA'S AND PRODUCT APPROVALS. | | 12) PLEASE NOTE THAT THE ABOVE REVIEW COMMENTS ARE | | BASED ON THE BUILDING BEING CLASSIFIED AS AN "OPEN | | PARKING GARAGE" BY THE DESIGN PROFESSIONAL OF RECORD. | | THIS CLASSIFICATION IS BEING CHALLENGED BY THE WEST | | PALM BEACH FIRE AND RESCUE DEPT., THEREFORE ADDITIONAL | | COMMENTS MAY FOLLOW THIS REVIEW. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2015-09-26 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2015-09-26 |
Time |
04:50 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2015-09-26 |
Time |
01:33 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2015-07-08 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2015-07-08 |
Time |
14:16 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2015-07-04 |
Time |
07:02 |
Sent To |
|
|
Notes |
2015-07-08 14:16:12 | 1)THERE ARE SEVERAL SHEETS IN THE FRONT OF THE PLANS | | THAT NOTE FOR REFERENCE ONLY-SEE E 15040015. WHAT IS | | THIS IN REFERENCE TO? CLARIFY. | | 2)SHT. AE160 DETAILS #2 & #3 SHOWS A ROOF DRAIN & | | PIPING/OVERFLOW DRAIN LOCATED IN THE STAIRWELLS AND | | PENETRATING THE WALL OF THE ENCLOSURE. PENETRATIONS | | INTO AND OPENINGS THROUGH AN EXIT ENCLOSURE ARE | | PROHIBITED IN ACCORDANCE WITH THE 2010 FBC SEC.1022.4. | | 3)SHT.AE 179 - SHOW THE DEPTH OF THE GUTTER ON DETAILS | | #2 & #5. WPB AMEND. TO 2010 FBC SEC. 107.2.1. | | 4)SHT. AE 401 - SHOW THE INSIDE CLEAR DIMENSIONS (L X | | W) OF THE ACCESSIBLE RESTROOM. | | 5)SHT.AE 401 - SHOW THE CLEAR FLOOR SPACE FOR THE BREAK | | ROOM SINK PER FAC SEC. 606. THE CLEAR FLOOR SPACE SHALL | | BE CENTERED ON THE FIXTURE. | | 6)SHT. AE 404 - SHOWS PERFORATED DRAIN PIPE AT | | PERIMETER OF OUTER WALL OF STRUCTURE. SUBMIT DETAILS: | | SIZE OF PIPE, DEPTH AND WIDTH OF BALLAST ROCK, AND SHOW | | LOCATION ON PLANS. I COULD NOT LOCATE THIS PIPING ON | | THE CIVIL DRAWINGS. WPB AMEND. TO 2010 FBC SEC. | | 107.2.1. | | 7) CALCULATIONS FOR THE SIZING OF RAIN WATER DRAINAGE | | FOR THE ROOF OF THE STAIRWELLS SHALL INCLUDE - THE AREA | | OF ANY VERTICAL WALL THAT DIVERTS RAINWATER TO THE ROOF | | SHALL BE INCLUDED IN THE CALCULATIONS. 2010 FPC SEC. | | 1106.4. | | 8) INDICATE ON THE PLANS IF THE ELEVATOR IS HYDRAULIC | | OR TRACTION. IF HYDRAULIC, THE CYLINDER SHALL COMPLY | | WITH THE 2010 FBC SEC.3011.1 THRU 3011.1.3. | | 9) SUBMIT A DETAIL DRAWING FOR THE BOOSTER PUMP FOR THE | | POTABLE WATER SYSTEM. WPB AMEND. TO 2010 FBC SEC. | | 107.2.1. | | 10) SHT.PP110A - SHOWS A 2"INDIRECT WASTE LINE THAT | | APPEARS TO BE PENETRATING THE WALL OF STAIR #1. | | PENETRATIONS INTO AND THROUGH AN EXIT ENCLOSURE ARE | | PROHIBITED EXCEPT FOR THE ITEMS LISTED IN 2010 FBC | | 1022.4. CLARIFY. | | 11) SUBMIT SIZING CALCULATIONS FOR THE OIL INTERCEPTOR. | | THE PLANS SHOW A SCHIER OIL INTERCEPTOR. THE SIZING | | CALCULATIONS SHALL BE REVIEWED BY SCHIER FOR CORRECT | | SIZING PER THE 2010 FPC SEC. 1003.2. PLEASE CONTACT LEE | | SCHNEEWEISS, SCHIER REPRESENTATIVE AT 1-800-538-4792. | | 12) SHT.PP110B - INDICATE THE SLOPE OF THE 10 INCH & 12 | | INCH STORM DRAIN LINES ON GRID LINE #F BETWEEN GRID | | LINE 10-1. NOTE: THE SQUARE FOOTAGE DRAINED SHALL | | COMPLY WITH 2010 FPC TABLE 1106.3. | | 13) SHT.PP160D - SHOW THE CONTINUATION POINT OF THE 6_ | | RAIN WATER DRAIN (SEE GRID LINES 2-3 & C-D). IS THIS | | TURNING UP OR DOWN? AND TO WHERE? | | 14) SHT.PP 170A - THE PLAN SHOWS A 4" STORM DRAIN | | DISCHARGING ABOVE THE TOP LEVEL NEXT TO A PARKING | | SPACE. THIS APPEARS THAT IT MAY CAUSE A NUISANCE DUE TO | | THE DISCHARGING WATER FOR THAT PARKING AREA DURING A | | RAIN EVENT. THE SAME ISSUE OCCURS BY STAIR #2. CLARIFY. | | 15) SHT. PP 170A - THERE IS A HORIZONTAL SECTION OF 4" | | STORM THAT IS COLLECTING 2170 SQUARE FEET OF AREA. THE | | MAXIMUM SQUARE FOOTAGE THAT A 4" HORIZONTAL STORM DRAIN | | CAN ACCOMMODATE AT AN 1/8" PER FOOT SLOPE AND A 5" | | RAINFALL RATE IS 1504 SQUARE FEET PER TABLE 1106.3. | | ADJUST THE SIZE TO THE NEXT LARGER PIPE SIZE OR | | INCREASE THE SLOPE. | | 16) SHT.PP170C - SHOWS A 6" O.D. SERVING 4500 SQ. FT. | | THE MAXIMUM SQUARE FOOTAGE AT 1/8? PER FT. SLOPE IS | | 4280 SQ. FT. PER TABLE 1106.3. | | 17) SHT. PP180A & PP180B - SHOW THE SQUARE FOOTAGE | | DRAINED BY EACH DRAIN. ALSO SHOW THIS ON THE STORM | | WATER RISER. COMPLY WITH TABLE 1106.3 OF THE 2010 FPC. | | 18) SHT. PP401 - SUBMIT A WATER ISOMETRIC FOR THE PUMP | | ROOM AND SUBMIT AN ELEVATION/PIPING DETAIL FOR THE | | DOMESTIC BOOSTER PUMP. WPB AMEND. TO 2010 FBC SEC. | | 107.3.5.1.3. | | 19) SHT. PP501 -SHOW THE SQUARE FOOTAGE OF THE AREA | | BEING DRAINED BY EACH DRAIN FOR THE STORM WATER RISERS. | | ALL VERTICAL LEADERS SHALL BE SIZED IN ACCORDANCE WITH | | THE 2010 FPC TABLE 1106.2 (1), 1106.2 (2) & ALL | | HORIZONTAL PIPING SHALL BE SIZED IN ACCORDANCE WITH | | TABLE 1106.3.ALL SIZING SHALL BE BASED ON A RAINFALL | | RATE OF 5 INCHES PER HOUR. | | 20) INDICATE THE SLOPE OF THE HORIZONTAL STORM DRAIN | | PIPING. COMPLY WITH TABLE 1106.3 OF 2010 FPC. | | 21) SHT.PP502 - THE AUTOMATIC AIR VENT CONNECTION TO | | THE HORIZONTAL DRAIN SHALL COMPLY WITH 2010 FPC SEC. | | 905.3. THE VENT SHALL CONNECT TO THE HORIZONTAL DRAIN | | ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN PIPE. | | CHECK ALL OF THE AAV CONNECTIONS. SEE ALSO 4? LINE AT | | HUB DRAIN BY STAIR #2. | | 22) SHT. PP502 - SUBMIT AN ENLARGED SANITARY RISER FOR | | THE GROUND LEVEL RESTROOM, BREAKROOM AND JANITOR. THE | | RISER IS TOO SMALL TO REVIEW. | | 23) SHT. PP503 -A SHUT-OFF VALVE IS REQUIRED AT THE | | BASE OF THE WATER RISER PER 2010 FPC SEC. 606.1 (4). | | 24) SHT. PP504 - SHOW THE SQUARE FOOTAGE DRAINED BY | | EACH 4? ROOF DRAIN. COMPLY WITH 2010 FPC TABLE 1106.3. | | | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | | | |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
2 |
Status |
P |
Date |
2016-12-27 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2016-12-27 |
Time |
09:40 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2016-12-27 |
Time |
09:40 |
Sent To |
|
|
Notes |
2016-12-27 09:41:07 | ROOF HATCH AND ROOFING REVIEWED UNDER SUBMITTAL | | #16120406 | | | | |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
N |
Date |
2015-07-16 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2015-07-16 |
Time |
18:20 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2015-07-16 |
Time |
18:20 |
Sent To |
|
|
Notes |
2015-07-16 18:33:49 | DESIGN PRESSURES ON PAGE S7.5: | | | | ZONE 1: +16 / -57.8 | | ZONE 2 : +16 / -93 | | ZONE 3: +16 / -93 | | | | ROOF PRODUCT APPROVALS NOT SUBMITTED AT THIS TIME | | ROOFING PERMIT REQUIRED | | PRODUCT APPROVALS TO BE REVIEWED BY DOR PRIOR TO | | SUBMITTAL | | | | |
|
|
Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
Rev No |
2 |
Status |
P |
Date |
2015-06-15 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2015-06-15 |
Time |
14:23 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2015-06-12 |
Time |
16:37 |
Sent To |
|
|
Notes |
|
|
Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
Rev No |
1 |
Status |
F |
Date |
2015-06-11 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2015-06-11 |
Time |
14:49 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2015-06-11 |
Time |
14:49 |
Sent To |
|
|
Notes |
2015-06-11 14:56:40 | ****CORRECTIONS**** | | ****REVISED 6/12/15**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. PLEASE REVISE PAGE 10 OF THE THRESHOLD INSPECTION | | PLAN (REFERENCE TO MISSILE IMPACT 60'), ITEMS 602 B AND | | C. PLEASE REVISE ONLY THIS SHEET. | | | | PROVIDE SIX (THREE FOR THE FOUNDATION PERMIT | | APPLICATION, THREE FOR THE BUILDING PERMIT). THIS MAY | | BE SUBMITTED SEPARATELY FROM THE BUILDING PERMIT | | RESUBMITTALS, OR MAY BE SENT VIA EMAIL. | | | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2015-11-23 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2015-11-23 |
Time |
15:49 |
Rev Time |
3.00 |
Received By |
eschneid |
Date |
2015-11-23 |
Time |
15:49 |
Sent To |
|
|
Notes |
2015-11-23 15:51:17 | 1) THIS PERMIT IS ONLY FOR THE GARAGE STRUCTURE. ALL | | OTHER ELEMENTS DEPICTED ON THE SITE PLANS HAVE NOT | | APPROVED BY ZONING. AS SUCH, THE FOLLOWING ITEMS | | REQUIRE SEPARATE PERMIT SUBMITTALS, WITH PLANS, AND | | HAVE NOT BEEN REVIEWED AS PART OF THIS PERMIT: | | | | A. LANDSCAPE, TO INCLUDE TREE REMOVAL AND RELOCATION. | | PLEASE NOTE CUS 1 THROUGH 3 ARE SHOWN IN LOCATIONS | | WHERE THE LANDSCAPE PLAN SHOWS HEDGES AND THE NEW FIRE | | HYDRANT ON THE NORTH SIDE OF THE BUILDING IS SHOWN | | WHERE TREES ARE SHOWN. NOTE: THE AS-BUILT PLANS WILL | | NEED TO BE SUBMITTED TO THE PLANNING DIVISION AS PART | | OF A MINOR PLANNED DEVELOPMENT AMENDMENT PRIOR TO THE | | C.O. FOR THE GARAGE. | | B. IRRIGATION | | C. PARKING GARAGE ACCESS LANES, TO INCLUDE PAVING, | | STRIPING, AND SIGNAGE | | D. BICYCLE RACKS | | E. EXTERIOR SIGNAGE | | F. WORK AND IMPROVEMENTS IN THE RIGHT-OF-WAY | | G. FENCES AND GATES NOT LOCATED WITHIN THE GARAGE | | H. GENERATOR AND ENCLOSURE | | I. HARDSCAPE, TO INCLUDE THE PAVERED ENTRY AREA AND | | SIDEWALKS | | J. SITE LIGHTING, TO INCLUDE PEDESTRIAN BOLLARDS - | | NOTE: | | 1. THE PHILIPS LUMEC LEONIS SERIES OF LIGHTING DOES NOT | | COMPLY WITH THE DOWNTOWN STREET LIGHTING REQUIREMENTS - | | THE FIXTURE SHALL BE MOUNTED ON TOP OF THE POLE WITH | | THE LAMP CENTER AT 17 FEET ABOVE GRADE. THE PHILIPS | | LUMEC URBANSCAPE PRODUCT MOUNTED ON A POLE APPEARS THAT | | IT WOULD COMPLY WITH THE DOWNTOWN REQUIREMENTS. | | 2. PLEASE REMEMBER THAT PALM BEACH COUNTY COMMITTED TO | | COORDINATING WITH RELATED TO USE THE SAME OR SIMILAR | | LIGHT FIXTURES IN THE FLORIDA AVENUE RIGHT-OF-WAY AND | | THE ENTRY DRIVE AND PLAZA TO MAINTAIN CONSISTENCY | | BETWEEN THE TWO PROJECTS. THE SPECIFIED TYPES DO NOT | | APPEAR TO BE CONSISTENT. | | 3. THE POLES SHOWN IN THE CITY RIGHT-OF-WAY MAY NOT BE | | PERMITTED ON THE SITE LIGHTING PERMIT, BUT RATHER SHALL | | BE PERMITTED THROUGH THE ENGINEERING SERVICES DIVISION. | | 4. ONE OF THE LIGHT POLES IS LOCATED WITHIN THE FIRE | | DEPARTMENT ACCESS DRIVEWAY. | | K. WORK WITHIN THE FUTURE STAGING AREA | | | | 2) SIGN #23 AND SIGN #24 AT STAIRWELLS #3 AND #4 SHALL | | INCLUDE THE WORD ?ONLY? AFTER EMERGENCY EGRESS. | | | | 3) A SIGN SHALL BE ADDED ON EACH FLOOR AT THE STAIRWELL | | #2 DOOR DIRECTING PATRONS TO EXIT TO THE CONVENTION | | CENTER AT THE ELEVATOR LOBBY. | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2015-10-01 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2015-10-01 |
Time |
18:44 |
Rev Time |
6.00 |
Received By |
eschneid |
Date |
2015-10-01 |
Time |
18:44 |
Sent To |
|
|
Notes |
2015-10-01 18:45:45 | FAILED | | | | PROVIDE RESPONSES IN WRITING. | | | | 1) THIS PERMIT IS ONLY FOR THE GARAGE STRUCTURE. ALL | | OTHER ELEMENTS DEPICTED ON THE SITE PLANS HAVE NOT | | APPROVED BY ZONING. AS SUCH, THE FOLLOWING ITEMS | | REQUIRE SEPARATE PERMIT SUBMITTALS, WITH PLANS, AND | | HAVE NOT BEEN REVIEWED AS PART OF THIS PERMIT: | | | | A. LANDSCAPE, TO INCLUDE TREE REMOVAL AND RELOCATION. | | PLEASE NOTE CUS 1 THROUGH 3 ARE SHOWN IN LOCATIONS | | WHERE THE LANDSCAPE PLAN SHOWS HEDGES AND THE NEW FIRE | | HYDRANT ON THE NORTH SIDE OF THE BUILDING IS SHOWN | | WHERE TREES ARE SHOWN. NOTE: THE AS-BUILT PLANS WILL | | NEED TO BE SUBMITTED TO THE PLANNING DIVISION AS PART | | OF A MINOR PLANNED DEVELOPMENT AMENDMENT PRIOR TO THE | | C.O. FOR THE GARAGE. | | B. IRRIGATION | | C. PARKING GARAGE ACCESS LANES, TO INCLUDE PAVING, | | STRIPING, AND SIGNAGE | | D. BICYCLE RACKS | | E. EXTERIOR SIGNAGE | | F. WORK AND IMPROVEMENTS IN THE RIGHT-OF-WAY | | G. FENCES AND GATES NOT LOCATED WITHIN THE GARAGE | | H. GENERATOR AND ENCLOSURE | | I. HARDSCAPE, TO INCLUDE THE PAVERED ENTRY AREA AND | | SIDEWALKS | | J. SITE LIGHTING, TO INCLUDE PEDESTRIAN BOLLARDS - | | NOTE: | | 1. THE PHILIPS LUMEC LEONIS SERIES OF LIGHTING DOES NOT | | COMPLY WITH THE DOWNTOWN STREET LIGHTING REQUIREMENTS. | | THE FIXTURE SHALL BE MOUNTED ON TOP OF THE POLE WITH | | THE LAMP CENTER AT 17 FEET ABOVE GRADE. THE PHILIPS | | LUMEC URBANSCAPE PRODUCT MOUNTED ON A POLE APPEARS THAT | | IT WOULD COMPLY WITH THE DOWNTOWN REQUIREMENTS. | | 2. PLEASE REMEMBER THAT PALM BEACH COUNTY COMMITTED TO | | COORDINATING WITH RELATED TO USE THE SAME OR SIMILAR | | LIGHT FIXTURES IN THE FLORIDA AVENUE RIGHT-OF-WAY AND | | THE ENTRY DRIVE AND PLAZA TO MAINTAIN CONSISTENCY | | BETWEEN THE TWO PROJECTS. THE SPECIFIED TYPES DO NOT | | APPEAR TO BE CONSISTENT. | | 3. THE POLES SHOWN IN THE CITY RIGHT-OF-WAY MAY NOT BE | | PERMITTED ON THE SITE LIGHTING PERMIT, BUT RATHER SHALL | | BE PERMITTED THROUGH THE ENGINEERING SERVICES DIVISION. | | 4. ONE OF THE LIGHT POLES IS LOCATED WITHIN THE FIRE | | DEPARTMENT ACCESS DRIVEWAY. | | K. WORK WITHIN THE FUTURE STAGING AREA | | | | 2) REPEAT COMMENT: SHEET AE160 HAS AN ARROW CALLING OUT | | THE ADA ACCESS AISLE AS YELLOW STRIPING. THIS STRIPING | | SHALL BE BLUE, NOT YELLOW. | | | | 3) REPEAT COMMENT: SHEET AE501 AND SHEETS SW 120-SW170 | | DO NOT SHOW COMPLIANCE WITH THE CONDITION THAT THE | | SIGNS WITHIN THE CONVENTION CENTER GARAGE GUIDE USERS | | TO THE ELEVATORS AND STAIRWELLS AT THE NORTHWEST CORNER | | OF THE CONVENTION CENTER GARAGE AND CLEARLY SIGN THE | | REMAINING STAIRWELLS AS EMERGENCY EGRESS ONLY. SIGN S23 | | BEING SHOWN AT THE NORTHEAST STAIRWELL INDICATES THAT | | THE STAIRWELL IS FOR NORMAL EXITING OF THE GARAGE. IF | | THIS IS THE CASE, THEN THE EXIT TO THE STAIRWELL NEEDS | | TO BE CONNECTED INTO THE SITE SIDEWALK NETWORK ALONG | | THE NORTH SIDE OF THE GARAGE WITH NO LOSS OF LANDSCAPE. | | SIGN TYPE S22 IS SHOWN ON THE PLAN BUT NO DETAIL OF | | THIS SIGN IS INCLUDED. | | | | 4) REPEAT COMMENT: THE PHOTOMETRICS ON EACH FLOOR NEED | | TO BE CONTINUED OUTSIDE OF THE GARAGE WALL TO THE | | PROPERTY LINE AROUND THE GARAGE. | | | | 5) REPEAT COMMENT: PROVIDE INFORMATION ON HOW GLARE | | FROM THE INTERIOR AND EXTERIOR LIGHTS ONTO THE ADJACENT | | RESIDENTIAL PROPERTY AND RIGHTS-OF-WAY WILL BE | | CONTROLLED. | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2015-07-14 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2015-07-14 |
Time |
13:44 |
Rev Time |
10.00 |
Received By |
eschneid |
Date |
2015-07-10 |
Time |
16:27 |
Sent To |
|
|
Notes |
2015-07-14 14:03:17 | FAILED | | | | PROVIDE RESPONSES IN WRITING. | | | | 1) THIS PERMIT IS ONLY FOR THE GARAGE STRUCTURE AND THE | | COVERED ENTRY STRUCTURE. ALL OTHER ELEMENTS DEPICTED ON | | THE SITE PLANS HAVE NOT APPROVED BY ZONING. AS SUCH, | | THE FOLLOWING ITEMS REQUIRE SEPARATE PERMIT SUBMITTALS, | | WITH PLANS, AND HAVE NOT BEEN REVIEWED AS PART OF THIS | | PERMIT: | | | | A. LANDSCAPE, TO INCLUDE TREE REMOVAL AND RELOCATION. | | PLEASE NOTE CUS 1 THROUGH 3 ARE SHOWN IN LOCATIONS | | WHERE THE LANDSCAPE PLAN SHOWS HEDGES. | | B. IRRIGATION | | C. PARKING GARAGE ACCESS LANES, TO INCLUDE PAVING, | | STRIPING, AND SIGNAGE | | D. BICYCLE RACKS | | E. EXTERIOR SIGNAGE | | F. WORK AND IMPROVEMENTS IN THE RIGHT-OF-WAY | | G. FENCES AND GATES NOT LOCATED WITHIN THE GARAGE | | H. GENERATOR AND ENCLOSURE | | I. HARDSCAPE, TO INCLUDE THE PAVERED ENTRY AREA AND | | SIDEWALKS | | J. SITE LIGHTING, TO INCLUDE PEDESTRIAN BOLLARDS - | | NOTE: THE PHILIPS LUMEC LEONIS SERIES OF LIGHTING DOES | | NOT COMPLY WITH THE DOWNTOWN STREET LIGHTING | | REQUIREMENTS ? THE FIXTURE SHALL BE MOUNTED ON TOP OF | | THE POLE WITH THE LAMP CENTER AT 17 FEET ABOVE GRADE. | | THE PHILIPS LUMEC URBANSCAPE PRODUCT MOUNTED ON A POLE | | APPEARS THAT IT WOULD COMPLY WITH THE DOWNTOWN | | REQUIREMENTS. PLEASE REMEMBER THAT PALM BEACH COUNTY | | COMMITTED TO COORDINATING WITH RELATED TO USE THE SAME | | OR SIMILAR LIGHT FIXTURES IN THE FLORIDA AVENUE | | RIGHT-OF-WAY AND THE ENTRY DRIVE AND PLAZA TO MAINTAIN | | CONSISTENCY BETWEEN THE TWO PROJECTS. | | K. WORK WITHIN THE FUTURE STAGING AREA | | | | 2) SHEET AE160 HAS AN ARROW CALLING OUT THE ADA ACCESS | | AISLE AS YELLOW STRIPING. THIS STRIPING SHALL BE BLUE, | | NOT YELLOW. | | | | 3) SHEET AE501 AND SHEETS SW 120-SW170 DO NOT SHOW | | COMPLIANCE WITH THE CONDITION THAT THE SIGNS WITHIN THE | | CONVENTION CENTER GARAGE GUIDE USERS TO THE ELEVATORS | | AND STAIRWELLS AT THE NORTHWEST CORNER OF THE | | CONVENTION CENTER GARAGE AND CLEARLY SIGN THE REMAINING | | STAIRWELLS AS EMERGENCY EGRESS ONLY. SIGN S23 BEING | | SHOWN AT THE NORTHEAST STAIRWELL INDICATES THAT THE | | STAIRWELL IS FOR NORMAL EXITING OF THE GARAGE. IF THIS | | IS THE CASE, THEN THE EXIT TO THE STAIRWELL NEEDS TO BE | | CONNECTED INTO THE SITE SIDEWALK NETWORK ALONG THE | | NORTH SIDE OF THE GARAGE WITH NO LOSS OF LANDSCAPE. | | SIGN TYPE S22 IS SHOWN ON THE PLAN BUT NO DETAIL OF | | THIS SIGN IS INCLUDED. | | | | 4) THE PHOTOMETRICS ON EACH FLOOR NEED TO BE CONTINUED | | OUTSIDE OF THE GARAGE WALL TO THE PROPERTY LINE AROUND | | THE GARAGE. | | | | 5) PROVIDE INFORMATION ON HOW GLARE FROM THE INTERIOR | | AND EXTERIOR LIGHTS ONTO THE ADJACENT RESIDENTIAL | | PROPERTY AND RIGHTS-OF-WAY WILL BE CONTROLLED. | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. | | |
|
|
|