Plan Review Details - Permit 15060049
Plan Review Stops For Permit 15060049
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-10-06 Cont ID  
Sent By shill Date 2015-10-06 Time 07:43 Rev Time 0.00
Received By shill Date 2015-10-06 Time 07:43 Sent To  
Notes
2015-10-06 07:55:14****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 THESE THREE COMMENTS ARE REPEAT COMMENTS. PLEASE HAVE
 QUALIFIER READ COMMENT LIST AND REVIEW PLAN BEFORE PLAN
 IS RESUBMITTED.
 PLEASE NOTE THAT PLANS ARE TO BE REVISED TO SHOW CODE
 COMPLIANCE (SEE FBC 107). ISSUES CANNOT BE ADDRESSED
 THROUGH A RESPONSE LETTER AS THAT IS DISCARDED, NOT A
 PART OF THE PERMIT PACKAGE. ALSO COMMENT CANNOT BE
 ADDRESSED WITH VERBAL INFORMATION - FOR INSTANCE, I WAS
 TOLD THAT THE SOUTHWEST BUILDING WAS A PART OF THE OIL
 CHANGE BUSINESS AND HAD NO OFFICE, BUT THE SURVEY AND
 AERIALS SHOW AN OFFICE.
  
 IF QUALIFIER WOULD LIKE TO DISCUSS POSSIBLE
 RESOLUTIONS, PLEASE HAVE QUALIFIER CALL ME TO DISCUSS.
 THIS WAS THIRD SUBMITTAL, SAME INFORMATION SUBMITTED,
 $50 EACH SUBMITTAL.
  
 1. SEE PREVIOUS LIST REGARDING THE TWO ACCESSIBLE
 SPACES ON THE SOUTH END OF THE PARKING LOT. A PATH OF
 TRAVEL IS SHOWN LEADING TO THE RESTAURANT, BUT THIS
 LOCATION IS NOT THE SHORTEST ROUTE.
  
 THE BUILDING IN THE SOUTHWEST PORTION OF THE LOT DOES
 NOT APPEAR TO BE SERVED BY ANY ACCESSIBLE SPACES.
  
 RESPONSE LETTER STATES THAT THIS BUILDING IS FOR STAFF
 ONLY. SURVEY APPEARS TO INCLUDE A NOTE THAT STATES THAT
 THIS BUILDING INCLUDES OFFICE SPACE. RESPONSE LETTER
 STATES THAT "THE BUILDING . . . IS A REPAIR SHOP FOR A
 COMPANY THAT ONLY STORES THEIR WORK VEHICLES FOR
 MAINTENANCE AND STORAGE. THIS AREA IS FOR WORKERS
 ONLY."
  
 AS THERE IS AN OFFICE, IT APPEARS THAT ACCESSIBLE
 PARKING NEEDS TO BE PROVIDED FOR THIS BUILDING (FOR
 STAFF/EMPLOYEES OR FOR VISITORS).
  
 SEE FBC 2010 ACCESSIBLITY 202.3 (ALTERATIONS), 208.2
 (PARKING SPACES), 502 (PARKING SPACES), 206 (ACCESSIBLE
 ROUTE).
  
 THIS ISSUE HAS BEEN DISCUSSED AT LENGTH WITH KRISTINE
 FROM THE CONTRACTOR'S OFFICE. PLEASE HAVE QUALIFIER
 CALL ME TO DISCUSS OPTIONS FOR RESOLUTION. A REDLINE
 WAS OFFERED IN PREVIOUS PLAN REVIEW, BUT WE WERE UNABLE
 TO OBTAIN RESOLUTION.
  
 SEE SECTION FBC ACCESSIBILITY 208.3.1:
  
 PARKING SPACES COMPLYING WITH 502 THAT SERVE A
 PARTICULAR BUILDING OR FACILITY SHALL BE LOCATED ON THE
 SHORTEST ACCESSIBLE ROUTE FROM PARKING TO AN ENTRANCE
 COMPLYWING WITH 206.4.
  
 WHERE PARKING SERVES MORE THAN ONE ACCESSIBLE ENTRANCE,
 PARKING SPACES COMPLYING WITH 502 SHALL BE DISPERSED
 AND LOCATED ON THE SHORTEST ACCESSIBLE ROUTE TO THE
 ACCESSIBLE ENTRANCES.
  
 SEE ALSO ADVISORY 208.2:
  
 THE NUMBER OF PARKING SPACES REQUIRED TO BE ACCESSIBLE
 IS TO BE CALCULATED SEPARATELY FOR EACH PARKING
 FACILITY; THE REQUIRED NUMBER IS NOT TO BE BASED ON THE
 TOTAL NUMBER OF PARKING SPACES PROVIDED IN ALL OF THE
 PARKING FACILITIES PROVIDED ON THE SITE.
  
 REGARDING PREVIOUS ITEM #2, RESPONSE ADDRESSES PARKING
 SPACES FOR THE OIL CHANGE BUILDING. AT ISSUE IS THE TWO
 ACCESSIBLE SPACES TO THE SOUTH OF THE LOT. BUILDINGS
 WHICH SERVE EMPLOYEES ARE NOT EXEMPT FROM
 ACCESSIBILITY, ONLY FROM VERTICAL ACCESSIBLITY IN VERY
 SPECIFIC CASES.
  
 PLEASE REVISE PLAN TO SHOW COMPLIANCE AND PROVIDE ALL
 INFORMATION REQUIRED. RESPONSE LETTER STATES THAT
 APPLICANT WILL NOT ADD ADDITIONAL SPACES NOR MOVE THE
 NON COMPLIANT SPACES. PLEASE HAVE QUALIFIER CALL ME TO
 DISCUSS CODE COMPLIANT OPTIONS. LEAVING TWO NON
 COMPLIANT SPACES AND ROUTE TO ONE BUILDING WHILE
 LEAVING ANOTHER WITH NO ACCESSIBLE PARKING IS NOT AN
 OPTION. IT APPEARS THAT EASIEST RESOLUTION COULD BE TO
 ELIMINATE THE TWO NON COMPLIANT ACCESSIBLE SPACES AND
 MARKED PATH OF TRAVEL, ADD ONE SPACE ADJACENT TO THE
 GENERAL REPAIR AND MAINTENANCE (WITH OFFICE) BUILDING.
  
 2. THE PRINTED NAME AND SIGNATURE OF THE INDIVIDUAL
 TAKING RESPONSIBILITY FOR THE DESIGN IS TO BE INCLUDED
 ON THE PLAN, FBC 107. THE COMPANY NAME IS INCLUDED BUT
 NO INFORMATION REGARDING THE INDIVIDUAL WHO IS TAKING
 RESPONSIBILITY FOR THE ACCURACY OF INFORMATION AND
 RESPONSIBILITY FOR DESIGN. REPEAT COMMENT, NOT
 ADDRESSED.
  
 3. SEE REVIEW #1, COMMENT NOT ADDRESSED:
  
 FBC 2010 ACCESSIBILITY 208.2.1, THE FOLLOWING USES HAVE
 ADDITIONAL PARKING REQUIREMENTS:
  
 HOSPITAL OUTPATIENT FACILITES
 REHABILITATION FACILITIES
 OUTPATIENT PHYSICAL THERAPY FACILITIES
  
 PLAN IS TO EITHER SHOW LOCATION OF TENANTS WITH ANY OF
 THE ABOVE USES OR PLAN IS TO INCLUDE A STATEMENT WHICH
 STATES THAT NONE OF THE ABOVE USES (HOSPITAL OUTPATIENT
 FACILITIES, REHABILITATION FACILITIES, OUTPATIENT
 PHYSICAL THERAPY FACILITIES) ARE AT THIS LOCATION.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-07-29 Cont ID  
Sent By shill Date 2015-07-29 Time 09:06 Rev Time 0.00
Received By shill Date 2015-07-29 Time 09:06 Sent To  
Notes
2015-07-29 09:16:36****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. THE PLAN SHOWS A BUILDING IN THE SOUTHWEST CORNER
 WHICH IS LABELED AS "GENERAL REPAIR AND MAINTENANCE"
 WHICH COULD BE EXEMPT FROM ACCESSIBILITY. HOWEVER,
 AERIALS APPEAR TO SHOW THAT THERE IS OFFICE SPACE AND A
 GOOGLE SEARCH INDICATES THAT THIS IS AN AUTOMOTIVE OIL
 CHANGE BUSINESS. NO ACCESSIBLE SPACES ARE SHOWN TO
 SERVE THIS BUILDING WHICH HAS TWO ACCESSIBLE ENTRANCES.
  
 THERE ARE TWO ACCESSIBLE SPACES SHOWN NEAR THIS SPACE,
 BUT THEY ARE SHOWN WITH AN ACCESSIBLE ROUTE TO THE
 RETAIL/RESTAURANT. IT IS NOT CLEAR WHY, IF THEY ARE TO
 SERVE THE RESTAURANT BUILDING, THE LOCATION IS NOT
 CLOSER TO THE BUILDING THEY ARE INTENDED TO SERVE. IT
 IS NOT CLEAR WHY THE OIL CHANGE BUILDING DOES NOT HAVE
 ANY ACCESSIBLE SPACES. IF THE TWO ACCESSIBLE SPACES
 SHOWN AT THE SOUTH ARE TO SERVE THE OIL CHANGE
 BUILDING, THEY SHOULD BE LOCATED ON THE SHORTEST
 ACCESSIBLE ROUTE. IN THE LOCATION SHOWN, THE USER IS
 COMPELLED TO WALK OR WHEEL BEHIND PARKED CARS.
  
 A REDLINE IS POSSIBLE UPON REQUEST FROM THE QUALIFIER.
  
 SEE FBC 2010 ACCESSIBLITY 202.3 (ALTERATIONS), 208.2
 (PARKING SPACES), 502 (PARKING SPACES), 206 (ACCESSIBLE
 ROUTE).

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-06-06 Cont ID  
Sent By shill Date 2015-06-06 Time 16:59 Rev Time 0.00
Received By shill Date 2015-06-06 Time 16:59 Sent To  
Notes
2015-06-06 17:07:41****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
  
 1. REVISE THE PLAN TO PROVIDE THE FOLLOWING
 INFORMATION:
  
 LOCATION OF ACCESSIBLE ENTRANCES
 ACCESSIBLE ROUTE FROM ACCESSIBLE SPACE TO ACCESSIBLE
 ENTRANCE
  
 SEE FBC 2010 ACCESSIBLITY 202.3 (ALTERATIONS), 208.2
 (PARKING SPACES), 502 (PARKING SPACES), 206 (ACCESSIBLE
 ROUTE).
  
 YOU MAY FIND THE FOLLOWING DOCUMENT USEFUL,
 PARTICULARLY THE INTRODUCTION: "WHEN A BUSINESS
 RESTRIPES A PARKING LOT, IT MUST PROVIDE ACCESSIBLE
 PARKING SPACES AS REQUIRED BY THE ADA STANDARDS FOR
 ACCESSIBLE DESIGN."
  
 HTTP://WWW.ADA.GOV/RESTRIPE.HTM
  
 SOME OF THE ACCESSIBLE PARKING SPACES HAVE BEEN
 RELOCATED. ACCESSIBLE PARKING SPACES ARE TO BE
 DISPERSED AMONGST THE DIFFERENT PARKING AREAS. IT IS
 NOT POSSIBLE TO DETERMINE WHERE THE SPACES SHOULD BE
 LOCATED WITHOUT INFORMATION REGARDING THE ACCESSIBLE
 ENTRANCES. MORE INFORMATION IS REQUIRED TO DETERMINE
 CODE COMPLIANCE.
  
 2. THE INDIVIDUAL TAKING RESPONSIBILITY SHALL PROVIDE
 THEIR PRINTED NAME AND SIGNATURE ON THE PLAN, FBC 107.
  
 4. FBC 2010 ACCESSIBILITY 208.2.1, THE FOLLOWING USES
 HAVE ADDITIONAL PARKING REQUIREMENTS:
  
 HOSPITAL OUTPATIENT FACILITES
 REHABILITATION FACILITIES
 OUTPATIENT PHYSICAL THERAPY FACILITIES
  
 PLAN IS TO EITHER SHOW LOCATION OF TENANTS WITH ANY OF
 THE ABOVE USES OR PLAN IS TO INCLUDE A STATEMENT WHICH
 STATES THAT NONE OF THE ABOVE USES (HOSPITAL OUTPATIENT
 FACILITIES, REHABILITATION FACILITIES, OUTPATIENT
 PHYSICAL THERAPY FACILITIES) ARE AT THIS LOCATION.
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2015-07-09 Cont ID  
Sent By cranford Date 2015-07-09 Time 12:15 Rev Time 0.00
Received By cranford Date 2015-07-06 Time 15:56 Sent To B
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2015-06-03 Cont ID  
Sent By cranford Date 2015-06-03 Time 10:08 Rev Time 0.00
Received By cranford Date 2015-06-03 Time 09:46 Sent To B
Notes
2015-06-03 10:08:20PROPOSED STRIPING DOES NOT COMPLY WITH SECTION 94-485
 OF THE CODE OF ORDINANCES.
  
 BASED ON FAILED INSPECTION IN JANUARY 2015, THE WORK
 WAS DONE NOT IN ACCORDANCE WITH THE PLANS APPROVED
 UNDER 14081121. THIS APPLICATION IS A REQUEST TO
 APPROVE STRIPING NOT CONSISTENT WITH CITY CODE.
  
 KELLY CRANFORD, P.E.
 LAND DEVELOPMENT ENGINEER
 PUBLIC WORKS DEPARTMENT
 CITY OF WEST PALM BEACH
 [email protected]
 561-494-1098 (OFFICE)

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-10-06 Cont ID  
Sent By shill Date 2015-10-06 Time 08:22 Rev Time 0.00
Received By shill Date 2015-09-21 Time 08:57 Sent To  
Notes
2015-10-01 17:31:5310/1 TO SH DESK
  
2015-09-22 08:57:58RESUB ROUTED TO SGRAHAM

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-07-29 Cont ID  
Sent By shill Date 2015-07-29 Time 09:16 Rev Time 0.00
Received By shill Date 2015-07-29 Time 09:16 Sent To  
Notes
2015-06-18 16:12:30INCOMING SENT TO ZONING BOX.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-06-06 Cont ID  
Sent By shill Date 2015-06-06 Time 17:07 Rev Time 0.00
Received By shill Date 2015-06-01 Time 08:00 Sent To  
Notes
2015-06-02 08:01:16SENT TO ZONING

Review Stop Z ZONING
Rev No 3 Status P Date 2015-09-23 Cont ID  
Sent By sgraham Date 2015-09-23 Time 08:33 Rev Time 0.00
Received By sgraham Date 2015-09-23 Time 08:33 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2015-06-19 Cont ID  
Sent By sgraham Date 2015-06-19 Time 13:01 Rev Time 0.00
Received By sgraham Date 2015-06-19 Time 13:01 Sent To ENG
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2015-06-02 Cont ID  
Sent By sgraham Date 2015-06-02 Time 10:01 Rev Time 0.00
Received By sgraham Date 2015-06-02 Time 10:01 Sent To B
Notes
***NONE***