Plan Review Details - Permit 15060041
Plan Review Stops For Permit 15060041
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2015-06-12 Cont ID  
Sent By tklarge Date 2015-06-12 Time 04:35 Rev Time 0.00
Received By tklarge Date 2015-06-12 Time 04:08 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2015-06-04 Cont ID  
Sent By tklarge Date 2015-06-04 Time 06:09 Rev Time 0.00
Received By tklarge Date 2015-06-04 Time 05:32 Sent To  
Notes
2015-06-04 06:07:541) RE-CHECK THE BTU LOAD ON THE SYSTEM. MY CALCULATIONS
 ARRIVE AT 269 BTU'S YET THE PLANS NOTE 330 BTU'S.
 CLARIFY.
 2) IF 330 BTU'S IS CORRECT, THE MINIMUM PIPE SIZE FROM
 THE METER SHALL BE 1 1/4" PER 2010 FBC-R TABLE G2413.4
 (1).
 3) SUBMIT TWO COPIES OF A FLOOR PLAN SHOWING THE
 LOCATION OF ALL APPLIANCES.WPB AMEND. TO FBC SEC.
 107.2.1.
 4) ALL GAS APPLIANCES SHALL BE LISTED AND LABELED PER
 THE 2010 FBCR SEC.G2404.3. SUBMIT 2 COPIES OF MANUF.
 SPEC. SHEETS FOR EACH APPLIANCE THAT SHOWS EACH
 APPLIANCE HAS A LISTING FROM A NATIONALLY RECOGNIZED
 LISTING AGENCY.
 5) IF THE TANKLESS WATER HEATER IS NOT A DIRECT VENT
 APPLIANCE, SUBMIT CALCULATIONS FOR COMBUSTION AIR PER
 FBCR SEC.G2407.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-06-12 Cont ID  
Sent By tklarge Date 2015-06-12 Time 04:35 Rev Time 0.00
Received By tklarge Date 2015-06-09 Time 18:04 Sent To  
Notes
2015-06-09 18:05:06SENT TO TIM LARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-06-04 Cont ID  
Sent By tklarge Date 2015-06-04 Time 06:09 Rev Time 0.00
Received By tklarge Date 2015-06-01 Time 08:14 Sent To  
Notes
2015-06-02 08:15:10SENT TO PLUMBING UNDER $5,000