Plan Review Details - Permit 15051289
Plan Review Stops For Permit 15051289
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2015-10-29 Cont ID  
Sent By rmcdouga Date 2015-10-29 Time 07:07 Rev Time 0.00
Received By rmcdouga Date 2015-10-28 Time 18:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-10-16 Cont ID  
Sent By rmcdouga Date 2015-10-16 Time 15:19 Rev Time 0.00
Received By rmcdouga Date 2015-10-16 Time 15:19 Sent To  
Notes
2015-10-16 15:07:52PLAN
 REVIEW COMMENTS
  
 3RD REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE ENERGY FORM DOES NOT SHOW COMPLIANCE WITH FBC
 ENERGY CONSERVATION SECTION 402. THE U-FACTOR SPECIFIED
 IS MORE THAN THE MAXIMUM OF .65. THE PERCENTAGE OF
 GLASS TO FLOOR AREA IS NOT 20 PERCENT. THE RAISED FLOOR
 AREA IS SPECIFIED AS 56 SQFT AND THE ENCLOSED AREA IS
 177 SQFT. THE AHU LOCATION IS NOT LISTED ON THE FORM.
 THE FORM IS NOT SIGNED BY THE OWNER/AGENT. YOU WILL
 NEED TO SUBMIT DOCUMENTATION FOR THE WINDOWS THAT WILL
 BE INSTALLED TO SHOW THEIR U-FACTOR AND SHGC.
  
 2) ONE SET OF THE PLANS WAS SIGNED OUT AND NOT
 RETURNED. TWO SETS OF PLANS ARE REQUIRED FOR REVIEW.
 FBC 107.1
  
 3) AN IMPACT FEE REVIEW BY PALM BEACH COUNTY IS
 REQUIRED.
  
 4) IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE
 CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER
 INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN
 ADDRESSED.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-09-11 Cont ID  
Sent By rmcdouga Date 2015-09-11 Time 11:33 Rev Time 0.00
Received By rmcdouga Date 2015-09-10 Time 17:32 Sent To  
Notes
2015-09-10 19:10:58PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE ENERGY FORM DOES NOT SHOW COMPLIANCE WITH FBC
 ENERGY CONSERVATION SECTION 402. THE U-FACTOR SPECIFIED
 IS MORE THAN THE MAXIMUM OF .65. THE PERCENTAGE OF
 GLASS TO FLOOR AREA IS NOT 20 PERCENT. THE RAISED FLOOR
 AREA IS SPECIFIED AS 56 SQFT AND THE ENCLOSED AREA IS
 177 SQFT. THE AHU LOCATION IS NOT LISTED ON THE FORM.
 THE FORM IS NOT SIGNED BY THE OWNER/AGENT. YOU WILL
 NEED TO SUBMIT DOCUMENTATION FOR THE WINDOWS THAT WILL
 BE INSTALLED TO SHOW THEIR U-FACTOR AND SHGC.
  
 2) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE NEW
 WINDOWS THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING
 BY THE DESIGNER OF RECORD. FBC107.3.4.1
  
 3) SHOW THAT THE WINDOWS WILL COMPLY WITH R301.2.1.2
 PROTECTION OF OPENINGS. WINDOWS IN BUILDINGS LOCATED IN
 WINDBORNE DEBRIS REGIONS SHALL HAVE GLAZED OPENINGS
 PROTECTED FROM WINDBORNE DEBRIS. GLAZED OPENING
 PROTECTION FOR WINDBORNE DEBRIS SHALL MEET THE
 REQUIREMENTS OF THE LARGE MISSILE TEST OF ASTM E 1996,
 ASTM E 1886, SSTD 12 OR TAS 201,202 AND 203 OR AAMA 506
 REFERENCED THEREIN. ( IF USING STORM PANELS, SUBMIT
 PRODUCT APPROVALS AND AN INSTALLATION SCHEDULE. )
  
 4) THE VALUE OF $10,000.00 ON THE APPLICATION FOR THE
 SCOPE OF WORK SHOWN ON THE PLANS APPEARS TO
 UNDERVALUED. SUBMIT A COPY OF THE SIGNED CONTRACT. FBC
 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. SUBMIT
 A COPY OF THE SIGNED CONTRACT TO VERIFY THE VALUATION
 OF THE PROJECT.
  
 5) IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE
 CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER
 INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN
 ADDRESSED.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-08-13 Cont ID  
Sent By rmcdouga Date 2015-08-13 Time 15:50 Rev Time 0.00
Received By rmcdouga Date 2015-08-13 Time 11:40 Sent To  
Notes
2015-08-13 14:38:44PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC-R314.3.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHEN ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS.
  
 2) SUBMIT ENERGY CALCULATIONS AS REQUIRED BY FBC ENERGY
 CONSERVATION SECTION 401.2.
  
 3) PROVIDE A FRAMING DETAIL FOR THE EXTERIOR IN-FILL
 WALLS THAT SHOWS THE FRAMING CONNECTORS / STRAPS AND
 THE WINDOW OPENING FRAMING. FBC 107.2.1 AND FBC-R601.2
  
 4) FBC 107.3.5.3 - PROVIDE COMPONENT AND CLADDING
 DESIGN PRESSURES PURSUANT TO FBC-R301.2 FOR THE SINGLE
 HUNG WINDOWS IN THE NEW SITTING ROOM.
  
 5) SPECIFY THE CEILING INSULATION TYPE AND R-VALUE ON
 THE PLANS FOR THE NEW SITTING ROOM. FBC ENERGY
 CONSERVATION 401.2
  
 6) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT
 APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION
 INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR THE NEW
 WINDOW SINGLE HUNG WINDOWS.
  
 7) SHOW COMPLIANCE WITH FBC-R 301.2.1.2 FOR LARGE
 MISSILE IMPACT PROTECTION AT THE NEW WINDOWS.
  
 8) IF THE NEW WINDOWS ARE NOT RATED FOR LARGE MISSILE
 IMPACT, THEN FBC - R 301.2.1.2 SUBMIT TWO COPIES OF AN
 INSTALLATION SCHEDULE AND KEY PLAN FOR THE STORM
 PANELS. SPECIFY THE OPENING SIZE, THE WIND PRESSURES,
 TYPE OF ANCHOR, ANCHOR SPACING, EDGE DISTANCE, PANEL
 LENGTH, PANEL SPAN, SEPARATION DISTANCE FROM PANEL TO
 GLASS AND THE APPLICABLE SECTION NUMBER FROM THE
 INSTALLATION DRAWINGS. I HAVE INCLUDED A LINK TO THE
 CONSTRUCTION SERVICES DEPARTMENT SITE THAT HAS MANY OF
 THE RELATED FORMS INCLUDING
 THE SCHEDULE FOR INSTALLATION OF OPENING PROTECTIVE
 DEVICES.
 HTTP://WPB.ORG/DEVELOPMENT/FORMS-AND-PUBLICATIONS/
  
 9) THE VALUE OF $10,000.00 ON THE APPLICATION FOR THE
 SCOPE OF WORK SHOWN ON THE PLANS APPEARS TO
 UNDERVALUED. SUBMIT A COPY OF THE SIGNED CONTRACT. FBC
 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-09-10 Cont ID  
Sent By rmcdouga Date 2015-09-10 Time 17:49 Rev Time 0.00
Received By rmcdouga Date 2015-09-10 Time 17:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-05-30 Cont ID  
Sent By dhayes Date 2015-05-30 Time 14:54 Rev Time 0.00
Received By dhayes Date 2015-05-30 Time 14:54 Sent To  
Notes
2015-05-30 14:58:21APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN APPROVED
 PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION
 FEE(S).
  
 1) ALL NEW GENERAL PURPOSE OUTLETS SHALL BE AFCI
 PROTECTED. NEC 210.12
  
 2) ALL NEW RECEPTACLESSHALL BE TAMPER RESISTANT. NEC
 406.11
  
 3) PROVIDE A 20 AMPERE BRANCH CIRCUIT FOR THE
 BATHROOM(S). NEC 210.11 (C)
  
 4) VERIFY OR INSTALL INTERCONNECTED SMOKE DETECTORS.
 FBC R314, 315
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2015-07-31 Cont ID  
Sent By fmittner Date 2015-07-31 Time 10:42 Rev Time 0.00
Received By fmittner Date 2015-07-31 Time 10:42 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2015-06-18 Cont ID  
Sent By fmittner Date 2015-06-18 Time 10:47 Rev Time 0.00
Received By fmittner Date 2015-06-18 Time 10:47 Sent To  
Notes
2015-06-18 10:48:17PROPERTY LOCATED IN HISTORIC DISTRICT. ADDITION
 REQUIRES SUBMITTAL OF COA APPLICATION. QUESTIONS
 CONTACT FRIEDERIKE MITTNER, CITY HSITORIC PRESERVATION
 PLANNER AT 822-1457.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-10-29 Cont ID  
Sent By rmcdouga Date 2015-10-29 Time 07:07 Rev Time 0.00
Received By rmcdouga Date 2015-10-28 Time 15:15 Sent To  
Notes
2015-10-28 15:15:50RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-10-16 Cont ID  
Sent By rmcdouga Date 2015-10-16 Time 15:19 Rev Time 0.00
Received By rmcdouga Date 2015-10-14 Time 10:48 Sent To  
Notes
2015-10-15 10:48:12RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-09-11 Cont ID  
Sent By rmcdouga Date 2015-09-11 Time 11:33 Rev Time 0.00
Received By rmcdouga Date 2015-09-08 Time 08:28 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-08-13 Cont ID  
Sent By rmcdouga Date 2015-08-13 Time 15:51 Rev Time  
Received By rmcdouga Date 2015-05-29 Time   Sent To  
Notes
2015-05-30 14:58:59R05

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2015-10-29 Cont ID  
Sent By rmcdouga Date 2015-10-29 Time 06:43 Rev Time 0.00
Received By rmcdouga Date 2015-10-28 Time 18:41 Sent To  
Notes
2015-10-29 06:44:50MU-2015-25038, NO FEES WERE DUE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2015-10-16 Cont ID  
Sent By rmcdouga Date 2015-09-10 Time 17:32 Rev Time 0.00
Received By rmcdouga Date 2015-09-10 Time 17:32 Sent To  
Notes
2015-09-10 17:33:57BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-08-13 Cont ID  
Sent By rmcdouga Date 2015-08-13 Time 11:51 Rev Time 0.00
Received By rmcdouga Date 2015-08-13 Time 11:51 Sent To  
Notes
2015-08-13 11:53:02BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-09-10 Cont ID  
Sent By rmcdouga Date 2015-09-10 Time 17:52 Rev Time 0.00
Received By rmcdouga Date 2015-09-10 Time 17:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2015-08-13 Cont ID  
Sent By rmcdouga Date 2015-08-13 Time 14:09 Rev Time 0.00
Received By rmcdouga Date 2015-08-13 Time 14:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-06-17 Cont ID  
Sent By tklarge Date 2015-06-17 Time 04:15 Rev Time 0.00
Received By tklarge Date 2015-06-17 Time 03:50 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2015-08-13 Cont ID  
Sent By rmcdouga Date 2015-08-13 Time 11:51 Rev Time 0.00
Received By rmcdouga Date 2015-08-13 Time 11:51 Sent To  
Notes
2015-08-13 11:52:15NO ROOFING WORK INDICATED ON PLANS.

Review Stop Z ZONING
Rev No 2 Status P Date 2015-09-11 Cont ID  
Sent By fmittner Date 2015-09-11 Time 11:32 Rev Time 0.00
Received By fmittner Date 2015-09-11 Time 11:32 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2015-07-31 Cont ID  
Sent By rmcdouga Date 2015-06-18 Time 10:53 Rev Time 0.00
Received By fmittner Date 2015-06-18 Time 10:48 Sent To  
Notes
2015-06-18 11:05:39ADDITION REQUIRES SUBMITTAL OF TWO SURVEYS, FAR AND LOT
 COVERAGE CALCULATIONS. QUESTIONS CONTACT FRIEDERIKE
 MITTNER, CITY HSITORIC PRESERVATION PLANNER AT
 822-1457.