Plan Review Details - Permit 15051260
Plan Review Stops For Permit 15051260
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-07-24 Cont ID  
Sent By jwitmer Date 2015-07-24 Time 14:11 Rev Time 0.00
Received By jwitmer Date 2015-07-24 Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-06-22 Cont ID  
Sent By jwitmer Date 2015-06-22 Time 09:20 Rev Time  
Received By jwitmer Date 2015-06-22 Time   Sent To  
Notes
2015-06-22 09:20:37BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15051260
 ADD: 440 COLUMBIA DR. SUITE # 105
 CONT: CHANDLER CONSTRUCTION
 TEL: (561) 791-6934
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JUNE 22/2015
 ACTION: DENIED
  
 1) SHEET A-1 THE CODE RESEARCH INDICATES THIS BUILDING
 TYPE AS A TYPE IV OR HEAVY TIMBER, PLEASE CORRECT. 2010
 FBC-B 602.4.
  
 2) SHEET A-2 SHOWS A ROOM # 03 AS A WAREHOUSE, IS THIS
 ROOM A WAREHOUSE OR A STORAGE ROOM? WHAT TYPE OF
 ARTICLES ARE GOING TO BE STORED IN THIS ROOM? THIS ROOM
 APPEARS TO BE A ASSESORY OCCUPANCY SINCE IT MEETS THE
 LESS THAN 10% OF THE FLOOR AREA( 433 SQ. FT. / FBC-B
 508.2.1.) PLEASE PROVIDE IF THIS IS A S1 OR S2
 OCCUPANCY. PLEASE ALSO BE AWARE THAT FBC-B TABLE 508.4
 HAS THE S1 & S2 OCCUPANCIES REVERSED AS TO THE REQUIRED
 RATING, HAS BEEN SINCE THE 2007 FBC-B, SEE THE BOAF
 INFORMAL INTERPRETATION 7357.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-07-27 Cont ID  
Sent By skennedy Date 2015-07-27 Time 08:56 Rev Time 0.00
Received By skennedy Date 2015-07-27 Time 08:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-07-08 Cont ID  
Sent By skennedy Date 2015-07-08 Time 09:39 Rev Time 0.00
Received By skennedy Date 2015-07-08 Time 09:39 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-06-03 Cont ID  
Sent By pleduc Date 2015-06-03 Time   Rev Time 0.00
Received By pleduc Date 2015-06-03 Time 15:28 Sent To  
Notes
2015-06-03 15:45:39THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THE WALL SEPARATING THE WAREHOUSE AND THE BUSINESS
 OFFICES IS REQUIRED TO BE 1 HOUR FIRE RATED. THE DOOR
 AND ASSEMBLY TO THE WAREHOUSE IS REQUIRED TO 20 MIN
 FIRE RATED.
  
 PROVIDE REVISIONS PRIOR TO INSPECTIONS.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-07-27 Cont ID  
Sent By skennedy Date 2015-07-27 Time 09:04 Rev Time 0.00
Received By skennedy Date 2015-07-16 Time 16:11 Sent To  
Notes
2015-07-16 16:11:46C23

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-07-08 Cont ID  
Sent By skennedy Date 2015-07-08 Time 09:39 Rev Time  
Received By skennedy Date 2015-05-29 Time   Sent To  
Notes
2015-05-29 12:28:23B18

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2015-07-08 Cont ID  
Sent By skennedy Date 2015-07-08 Time 09:39 Rev Time 0.00
Received By skennedy Date 2015-07-08 Time 09:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-07-24 Cont ID  
Sent By tklarge Date 2015-07-24 Time 03:01 Rev Time 0.00
Received By tklarge Date 2015-07-24 Time 02:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-06-17 Cont ID  
Sent By tklarge Date 2015-06-17 Time 03:47 Rev Time 0.00
Received By tklarge Date 2015-06-17 Time 03:12 Sent To  
Notes
2015-06-17 03:47:091) A DRINKING FOUNTAIN IS REQUIRED IN THIS SPACE PER
 TABLE 403.1 OF THE 2010 FBC-PLUMBING. A MINIMUM OF 2
 DRINKING FOUNTAINS ARE REQUIRED PER TABLE 403.1,
 FOOTNOTE # E AND FBC-ACCESSIBILITY SEC.211.2.
 2) SHT. A2.3 - ELEVATION # J - THE GRAB BAR BEHIND THE
 WATER CLOSET SHALL COMPLY WITH 2010 FBC-ACCESSIBILITY,
 SEC.604.5.2 FOR SPACING REQS.
 3) THE HEIGHT OF THE GRAB BARS SHALL BE MEASURED FROM
 THE FINISH FLOOR TO THE TOP OF THE GRIPPING SURFACE PER
 2010 FBC- ACCESSIBILITY, SEC.609.4.
 4) THE HEATER PAN SHALL COMPLY WITH THE 2010
 FBC-PLUMBING, SEC.504.7.
 5) SUBMIT DETAILS FOR THE WATER HEATER SUPPORT.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  