Plan Review Details - Permit 15051220
Plan Review Stops For Permit 15051220
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-06-29 Cont ID  
Sent By dhayes Date 2015-06-29 Time 08:34 Rev Time 0.00
Received By dhayes Date 2015-06-29 Time 08:14 Sent To  
Notes
2015-06-29 08:34:16APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN APPROVED
 PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION
 FEE(S).
  
 1) NEC 430.102 (B) MOTOR.
 A DISCONNECTING MEANS SHALL BE PROVIDED FOR A MOTOR IN
 ACCORDANCE WITH (B)(1) OR (B)(2).
 (1) A DISCONNECTING MEANS FOR THE MOTOR SHALL BE
 LOCATED IN SIGHT FROM THE MOTOR LOCATION AND THE DRIVEN
 MACHINERY LOCATION.
 EXCEPTION: THE DISCONNECTING MEANS FOR THE MOTOR SHALL
 NOT BE REQUIRED PROVIDED THE CONTROLLER DISCONNECT IS
 INDIVIDUALLY CAPABLE OF BEING LOCKED IN THE OPEN
 POSITION AND SHALL REMAIN IN PLACE WITH OR WITHOUT THE
 LOCK INSTALLED.
  
 2) NEC 110.22 (A)
 EACH DISCONNECTING MEANS SHALL BE LEGIBLY MARKED TO
 INDICATE ITS PURPOSE UNLESS LOCATED AND ARRANGED SO THE
 PURPOSE IS EVIDENT. THE MARKING SHALL BE OF SUFFICIENT
 DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-05-30 Cont ID  
Sent By dhayes Date 2015-05-30 Time 14:07 Rev Time 0.00
Received By dhayes Date 2015-05-30 Time 14:07 Sent To  
Notes
2015-05-30 14:20:285/30/2015
 PROJECT: FOUNTAIN ELECTRIC
 PERMIT#: 15051220
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) PROVIDE A SITE PLAN AND INDICATE THE LOCATION OF
 PANEL RACK AND FOUNTAIN. FBC 107.2.1
  
 2) PROVIDE A PANEL SCHEDULE INCLUDING ALL OCPD AND WIRE
 SIZES. EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE
 LEGIBLY IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND
 SPECIFIC PURPOSE OR USE. NEC 408.4
  
 3) INDICATE ALL WIRE AND CONDIUT SIZES ON RISER
 DIAGRAM. WPB AMENDMENTS FBC 107.3.5.1.2
  
 4) INDICATE SYSTEM AND OPERATING VOLTAGE ON RISER
 DIAGRAM. WPB AMENDMENTS FBC 107.3.5.1.2
  
 5) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS
 HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT
 NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED. NEC 110.9
  
 6) PROVIDE MANUFACTURER PRODUCT DATA SHEETS INDICATING
 THE TYPE OF OPERATION AND TYPE OF FOUNTAIN.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status   Date   Cont ID  
Sent By dhayes Date   Time   Rev Time 0.00
Received By   Date 2015-06-23 Time   Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-05-30 Cont ID  
Sent By dhayes Date 2015-05-30 Time 14:20 Rev Time  
Received By dhayes Date 2015-05-29 Time   Sent To  
Notes
***NONE***