Plan Review Details - Permit 15051158
Plan Review Stops For Permit 15051158
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-07-08 Cont ID  
Sent By shill Date 2015-07-08 Time 14:26 Rev Time 0.00
Received By shill Date 2015-07-08 Time 14:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2015-06-10 Cont ID  
Sent By dhayes Date 2015-06-05 Time 11:23 Rev Time 0.00
Received By shill Date 2015-06-10 Time 15:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-07-06 Cont ID  
Sent By shill Date 2015-07-06 Time 12:03 Rev Time 0.00
Received By dhayes Date 2015-07-06 Time 11:47 Sent To B
Notes
2015-07-06 12:05:20SEPARATE PERMIT APPLICATIONS AND SHOP DRAWINGS ARE
 REQUIRED FOR TEMPORARY ELECTRIC POWER FOR CONSTRUCTION.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-06-05 Cont ID  
Sent By misc2 Date 2015-06-05 Time 11:23 Rev Time 0.00
Received By dhayes Date 2015-06-05 Time 10:35 Sent To B
Notes
2015-06-05 11:09:466/5/2015
 PROJECT: WESMINSTER RESIDENCE
 PERMIT#: 15051158
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) THE ELECTRICAL PLAN INDIACTES VIA NOTES ON A.01 THAT
 THE ELECTRICAL PANEL CERTAIN LIGHTING AND SMOKE
 DETECTORS WILL REMAIN FOR THE DURATION OF THE
 CONSTRUCTION PROCESS. INDICATE THE LOCATION OF THE
 ELECTRICAL PANEL, ELECTRICAL SERVICE, LIGHTING AND
 SMOKE DETECTORS THAT ARE EXISTING TO REMAIN.
  
 2) PROVIDE A PANEL SCHEDULE FOR CIRCUITS THAT WILL
 REMAIN. NEC 408.4
  
 3) INDICATE THE LOCATION OF THE REQUIRED GFI
 RECEPTACLES FOR CONSTRUCTION. NEC 590.6
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-07-08 Cont ID  
Sent By shill Date 2015-07-08 Time 14:26 Rev Time 0.00
Received By shill Date 2015-06-30 Time 14:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-06-10 Cont ID  
Sent By shill Date 2015-06-10 Time 15:39 Rev Time 0.00
Received By shill Date 2015-05-28 Time 16:02 Sent To  
Notes
2015-05-28 16:03:04TO DAH DESK
  