Plan Review Details - Permit 15050966
Plan Review Stops For Permit 15050966
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-06-08 Cont ID  
Sent By albarran Date 2015-06-08 Time 18:13 Rev Time 0.00
Received By albarran Date 2015-06-08 Time 18:05 Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-05-29 Cont ID  
Sent By scaldero Date 2015-05-29 Time 11:14 Rev Time 0.00
Received By scaldero Date 2015-05-29 Time 11:14 Sent To E
Notes
2015-05-29 11:15:30PERMIT # 15050966
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 WHERE MUSIC SYSTEMS ARE BEING INSTALLED IN TENANT
 SPACES: THE SPEAKER SYSTEM WILL NEED TO BE TESTED
 AGAINST THE FIRE ALARM SYSTEM TO ENSURE THAT THE
 MINIMUM REQUIRED DECIBEL LEVELS OF THE FIRE ALARM
 SYSTEM ARE BEING MET. PENDING RESULTS OF FIELD
 INSPECTION/FIRE ALARM TEST, ADDITIONAL REQUIREMENTS MAY
 BE NEEDED.
  
 PROVISO: ALL TENANT SPACES FOR THE MARKETPLACE MUST BE
 TIED INTO THE MASTER FIRE ALARM PANEL FOR THE BUILDING.
 EACH TENANT SPACE WILL BE INTERCONNECTED AND UPON
 ACTIVATION OF AN ALARM IN ANY ONE SPACE, ALL SPACES
 WILL HAVE THEIR NOTIFICATION DEVICES ACTIVATE. AN FACP
 IN A TENANT SPACES WILL HAVE THE "RESET" AND "SILENCE"
 FUNCTIONS DEACTIVATED. RESET AND SILENCE OF AN ALARM IS
 LIMITED TO THE MASTER PANEL FOR THE BUILDING AND MAY
 ONLY BE DONE BY A LICENSED FIRE ALARM TECHNICIAN.
 SHOULD IT BE FOUND THAT TENANTS ARE ACCESSING THE
 PANELS IN THE TENANT SPACES AND/OR USING THE "RESET" OR
 "SILENCE" FUNCTIONS, THE OFFICE OF THE FIRE MARSHAL MAY
 REQUIRE THAT THE TENANT FACP BE REMOVED.
 PER APPROVED MASTER PLANS: MAIN FACP FOR THIS BUILDING
 IS TO BE THE ONLY PANEL TO NOTIFY THE FIRE DEPARMENT.
 NOTIFICATION WILL DESIGNATE SPECIFIC ADDRESS OF TENANT
 WHERE TROUBLE IS LOCATED. EACH BUILDING SHALL
 ALARM/EVACUATE ONLY THE SPACES IN THAT BUILDING (IE AN
 ALARM IN "B" WILL NOT EVACUATE ANY SPACE IN "A", "BII",
 OR "C". EACH TENANT SPACE FACP SHALL BE CONNECTED TO
 MAIN FACP FOR THIS BUILDING VIA MODULES. TENANT SYSTEM
 SHALL BE COMPATIBLE WITH NOTIFIER OR EQUAL APPROVED
 MAIN FACP/HARDWARE EACH FLOW/TAMPER SHALL BE ZONED SO
 THAT AN ALARM WILL SOUND FOR EACH BUILDING SEPARATELY.
  
 SUE ELLEN CALDERON
 FIRE INSPECTOR & INVESTIGATOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-06-08 Cont ID  
Sent By albarran Date 2015-06-08 Time 18:15 Rev Time  
Received By albarran Date   Time   Sent To  
Notes
2015-06-08 18:16:18SENT TO SMALL READY BIN "A"
2015-05-21 13:22:31ROUTED TO FIRE