Plan Review Details - Permit 15050879
Plan Review Stops For Permit 15050879
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2015-12-09 Cont ID  
Sent By skennedy Date 2015-12-09 Time 08:12 Rev Time 0.00
Received By skennedy Date 2015-12-09 Time 08:12 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-10-17 Cont ID  
Sent By skennedy Date 2015-10-17 Time 17:16 Rev Time 0.00
Received By skennedy Date 2015-10-17 Time 17:16 Sent To  
Notes
2015-10-17 17:43:433RD REVIEW: FBC 2010
  
 FBC 107, MINIMUM PLAN REVIEW CRITERIA. THIS REVIEW IS
 DENIED FOR LACK OF INFORMATION AS FOLLOWS:
  
 THE DESIGNER MUST PROVIDE FURTHER DETAILS, TO SPECIFY
 MATERIALS, CONNECTION AND ATTACHMENTS AS FOLLOWS:
 WALL SECTION SHEET A-1.2 & NOTES 09.1 & 09.2:
 ATTACHMENT OF FLOOR JOIST, CEILING JOIST, SPECFY WALL
 STUD SIZE AND OC SPACING AND ALL SHEATHING NAILING.
  
 ADDITIONAL SUBMITTAL IS NEEDED TO CLARIFY THE SELECTED
 WINDOW/DOOR, STORM PANEL AND ROOFING PRODUCTS TO BE
 USED . CLARIFY THE CONFLICT OF NOTE 08.8 VERSUS THE
 PROVIDED SLIDING GLASS DOOR NOA TO ACHIEVE IMPACT
 PROTECTION. THE OTHER DOOR SUBMITTALS ARE NOT CLEAR. A
 ROOFING PRODUCT IS NOT SUBMITTED. A COVER SHEET ONLY
 HAS BEEN PROVIDED FOR STORM PANELS. IF PANELS ARE TO BE
 USED, PROVIDE FULL INFORMATION.
  
 YOU MAY CHOOSE TO DEFER THE PRODUCT APPROVAL
 SUBMITTALS.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-07-13 Cont ID  
Sent By skennedy Date 2015-07-13 Time 10:29 Rev Time 0.00
Received By skennedy Date 2015-06-24 Time 19:46 Sent To  
Notes
2015-07-11 13:26:072ND REVIEW: FBC 2010
  
 NEW COMMENTS:
  
 PROVIDE DETAILS FOR EACH SET OF THE NEW STAIRS,
 LANDINGS, AND HANDRAILS.
  
 EXPLAIN TO WHICH PART OF THE BUILDING THE WALL SECTION
 ON SHEET A-1.2 APPLIES.
  
 FBC 107.3.5.1.6 ENERGY CALCULATIONS - PROVIDE AN ENERGY
 SUBMITTAL.
  
 THE PROJECT QUALIFIES AS A RENOVATION AS THE PROPOSED
 COST EXCEEDS 30% OF THE VALUE OF THE EXISTING
 STRICTURE.
  
 FBCE-103.2.1.1 RESIDENTIAL LESS THAN OR EQUAL TO 3
 STORIES.
  
 FBCE-103.2.1.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM 402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 FBCE-103.2.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM 405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 PREVIOUS COMMENTS:
  
 PROVIDE STRUCTURAL DETAILS FOR ALTERATIONS OF OPENINGS
 TO ACCOMODATE THE INSTALLATION OF NEW WINDOW AND DOOR
 PRODUCTS, AS MAY BE NECESSARY.
  
 ADDITIONALLY, THE PLAN NOTES ARE IN CONFLICT WITH THE
 PRODUCT APPROVALS AND NOTE 08.1 & 08.2 ON SHEET A-1.1
 INDICATING IMPACT RESISTANT WINDOWS, SPECIFYING NON
 IMPACT, AND ALSO PROVIDING STORM PANELS. PLEASE FURTHER
 EVALUATE THESE ISSUES AND SPECFY WHAT IS SPECIFICALLY
 PROPOSED.
  
 THE DESIGN PRESSURES PROVIDED SHOULD BE SPECIFIC TO
 EACH OPENING. YOU HAVE APPARENTLY PROVIDED A ONLY
 GENERAL ZONE INFORMATION.
  
  
  
  
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-06-04 Cont ID  
Sent By skennedy Date 2015-06-04 Time 06:10 Rev Time 0.00
Received By skennedy Date 2015-06-04 Time 05:24 Sent To  
Notes
2015-06-04 06:43:171ST REVIEW: FBC 2010
  
 FBC 107 PLEASE PROVIDE ADDITIONAL DETAILS AS FOLLOWS:
  
 STRUCTURAL DETAIL FOR ALTERATIONS OF OPENINGS TO
 ACCOMODATE THE INSTALLATION OF NEW WINDOW AND DOOR
 PRODUCTS, AS MAY BE NECESSARY.
  
 THE ARCHITECTS LETTER OF 4/17/15 INDICATES FL 15227-68M
 WILL BE USED AS AN EXTERIOR SWING DOOR. THE PROVIDED
 DOOR PRODUCT INFORMATION IS BY A MANUFACTURER
 INCONSISTENT WITH THE ONE FOUND UNDER THIS NUMBER AT
 HTTPS://FLORIDABUILDING.ORG/PR/PR_DEFAULT.ASPX
  
 THE ARCHITECTS LETTER OF 4/17/15 INDICATES FL 13578-R1
 WILL BE USED FOR STEEL SHUTTERS. THE PRODUCT
 INFORMATION IS NOT PROVIDED.
  
 NOTE: IT MAY BE ADVISABLE FOR THE DESIGNER OR A
 CONSULTANT ENGINEER TO REVIEW THE WINDOW AND DOOR
 PRODUCTS FURTHER AND PROVIDE ADDITION ANALYSIS AS TO
 DESIGN PRESSURES AND TO PROVIDE AN INSTALLATION
 SCHEDULE FOR THE SHUTTERS.
 YOU MAY WISH TO UTILIZE THE SCHEDULE FOUND AT: HTTP://W
 PB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/2013/09/
 SCHEDULE_FOR_INSTALLATION.PDF
  
 PLEASE INDICATE THE METHOD INTENDED FOR COMPLIANCE WITH
 FBC-R311.1 AS TO EGRESS WHEN THE BUILDING IS SHUTTERED.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2015-12-09 Cont ID  
Sent By skennedy Date 2015-12-09 Time 08:13 Rev Time 0.00
Received By skennedy Date 2015-12-09 Time 08:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2015-10-22 Cont ID  
Sent By albarran Date 2015-10-22 Time 19:38 Rev Time 0.00
Received By albarran Date 2015-10-22 Time 16:42 Sent To I
Notes
2015-10-22 19:39:18THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE 2008 EDITION
 OF THE NEC, (NATIONAL ELECTRICAL CODE); THE FBC,
 (FLORIDA BUILDING CODE) 2010, AS APPLICABLE AND BELOW
 ARE THE DEFICIENCIES NOTED.
 1. GENERAL NOTES REFERENCE TO THE 2010 NEC SHALL BE
 CORRECTED AS IT NEVER EXISTED. THE APPLICABLE CODE FOR
 THIS PROJECT IS THE 2008 EDITION.
 2. THE SHEET INDEX MAKES REFERENCE TO SHEET E1.0 FOR
 THE ELECTRIC WHICH IS NOT PROVIDED, YET SUBMITTED SHEET
 E2.1 IS NOT MENTIONED. CORRECT ACCORDINGLY.
 3. PER NEC 210.70)(A) EXCEPTION AUTOMATIC LIGHTING
 CONTROL IS REQUIRED FOR THE EXTERIOR STAIRWAYS.
 4. THE WORD ?ROMEX? AS USED IN NOTE 26.3 IS TO IDENTIFY
 A TYPE OF CABLE. ROMEX IS A BRAND NAME AND NOT A TYPE
 OF CABLE; REFER TO CABLE TYPES ?NM?, ?NMC? OR ?NMS?.
 5. NOTE 26.4 DICTATES KITCHEN COUNTER SPACING AT 36?
 CENTER CONTRARY TO NEC 210.52(C) REQUIREMENTS. CORRECT
 NOTE ACCORDINGLY.
 6. SMOKE DETECTOR IS REQUIRED INSIDE THE GARAGE
 APARTMENT.
 7. ARC-FAULT PROTECTION IS ERRONEOUSLY ONLY ADDRESSED
 FOR SMOKE DETECTOR CIRCUITS ON THE PLANS. ARC-FAULT
 PROTECTION REQUIREMENTS APPEAR IN NEC 210.12.
 8. ALL DWELLING RECEPTACLES SHALL BE LISTED
 TAMPER-RESISTANT ?TR? PER NEC 406.11.
 9. ALL OUTLETS IN WET LOCATIONS SHALL BE LISTED
 WEATHER-RESISTANT ?WR? AS INDICATED IN NEC 406.8.
 10. ALL CEILING OUTLET BOXES SHALL BE LISTED TO SUPPORT
 50#?S AS PER NEC 314.27.
 11. DWELLING UNIT RECEPTACLES SHALL BE SPACED AS
 INSTRUCTED IN NEC 210.52. AS SUCH YOU ARE MISSING
 OUTLETS IN THE FAMILY ROOM, BEHIND THE FIREPLACE,
 LIVING ROOM, BEDROOMS I & II.
 12. PORCH LIGHT SHALL BE CONTROLLED VIA A 3 WAY SWITCH
 BY ENTRY WAY.
 13. BEDROOM CORRIDOR SHALL BE PROPERLY ILLUMINATED AND
 SWITCHED PREFERABLY WITH A 3 OR 4 WAY SWITCHES.
 14. IF THE OUTLET INSIDE THE CLOSET IN BEDROOM II IS TO
 BE INTENDED FOR THE CONNECTION OF ANY EQUIPMENT, NEC
 210.70 REQUIRES THAT THERE BE A LIGHT CONTROLLED BY A
 WALL SWITCH FOR THAT ROOM.
 15. KITCHEN COUNTER OR PENINSULA OUTLETS SHALL BE AS
 DICTATED IN NEC 210.52 (C); THE PENINSULA SHALL HAVE AN
 OUTLET AS REQUIRED.
 16. THERE SHALL BE A GFI ?WR? OUTLET IN FRONT OF THE
 DWELLING PER NEC 210.52(E)(1).
 17. YOU SHALL SHOW THE REQUIRED LAUNDRY CIRCUIT 19 ON
 THE FLOOR PLAN.
 18. YOU SHALL PROVIDE ACCURATE AND SITE SPECIFIC FEEDER
 DIAGRAM AND LOAD CALCS SHOW PROPER CONDUCTOR AND GROUND
 CONDUCTOR SIZING FOR THE COMPLETE SERVICE AS MANDATED
 BY NEC 215.5.
 19. THE CONNECTED LOAD AS INDICATED EXCEEDS THE RATING
 OF THE MAIN CIRCUIT BREAKER AND BUS BAR OF PANEL P1.
 THE PLANS SHALL BE REVISED TO ADDRESS THE HEREIN
 MENTIONED ITEMS; ONCE CORRECTED SHALL BE RESUBMITTED
 FOR ANOTHER REVIEW. WHEN RESUBMITTING, YOU ARE REQUIRED
 TO PROVIDE A RESPONSE LETTER ADDRESSING EACH ITEM ALONG
 WITH THE STANDARD CITY RE-SUBMITTAL FORM. PLEASE,
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE SUBMITTAL
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARISON. CLOUDING THE CHANGES WILL BE GREATLY
 APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-07-14 Cont ID  
Sent By dhayes Date 2015-07-14 Time 12:51 Rev Time 0.00
Received By dhayes Date 2015-07-11 Time 13:26 Sent To  
Notes
2015-07-14 12:51:047/14/2015
 PROJECT: 347 PLYMOTH
 PERMIT#: 15050879
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC,
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER ONE,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) THE SERVICE RISER PROVIDE IS NOT COMPLIANT.
 DISCONNECTS SHALL BE GROUPED. NEC 230.72. YOU INDICATE
 PANEL P1 TO BE LOCATED INSIDE MAIN HOUSE NEW LAUNDRY
 ROOM AND P2 TO BE LOCATED IN THE DETACHED GARAGE
 BUILDING.
  
 2) INDICATE THE LOCATION OF THE ELECTRICAL SERVICE
 METER.
  
 3) INDICATE THE SIZE AND CONTENTS OF THE EXISTING
 SERVICE RACEWAY BETWEEN THE METER AND PANEL P1. YOUR
 NOTES 26.1 ON PAGE E-2.1 INDICATE THAT YOU PROPOSE A
 NEW ELECTRICAL SERVICE WITH MAIN DISCONNECT THIS
 CONFLICTS WITH YOUR RISER DIAGRAM.
 CLARIFIFICATION REQUIRED. YOU INDICATE THE METER AND
 SERVICE ENTRANCE CONDUCTORS TO PANEL P1 ARE EXISTING
 AND YET PANEL P1 IS A NEW PANEL AND ACCORDING TO PAGE
 A-1.0 IT IS IN A NEW LOCATION.
 YOU ALSO INDICATE PANEL P2 IS FED THROUGH P1 HOWEVER
 THERE IS NO INDICATION OF AN OCPD IN PANEL P1 TO FEED
 P2. IN ADDITION THE NOTES ON PAGE E-2.1 INDICATE A NEW
 UNDERGROUND TO THE EXISTING SERVICE. THERFORE THE
 SERVICE RISER AND SITE/FLOOR PLAN NEED CLARIFICATION.
  
 4) INDICATE ALL REQUIRED SMOKE DETECTORS. YOU HAVE
 INDICATED SMOKE DETECTORS OUTSIDE OF THE SLEEPING ROOMS
 BUT NOT INSIDE. ALSO GIVE CAREFUL CONSIDERATION TO THE
 REQUIREMENTS IN THE FBC-R 315 CARBON MONOXIDE
 DETECTORS. WHEN ALTERATIONS, REPAIRS, OR ADDITIONS
 REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE
 INDIVIDUAL DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE
 ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS.
 FBC-RESIDENTIAL 314 AND 315.
  
 5) PROVIDE CLARIFICATION AT THE ELECTRICAL PANEL. EVERY
 CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY
 IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC
 PURPOSE OR USE. NEC 408.4 SPECIFICALLY THE WATER HEATER
 IN BOTH PANELS. THE SYSTEM VOLTAGE AND LOAD SHOULD BE
 CLEAR. YOU HAVE INDICATED THE WIRE SIZE AND IN MOST
 CASES THE NUMBER OF POLES USED BUT THE OCPD SIZE HAS
 NOT BEEN INDICATED. PLEASE CLARIFY.
  
 6) PROVIDE DISCONNECTS AT AHU'S NEC 440.14
  
 7) INDICATE GFI AS GEQUIRED IN THE KITCHEN FOR
 COUNTERTOP OUTLETS. NEC 210.8(6)
  
 8) VERIFY CLEARANCES REQUIRED FOR ELECTRICAL PANEL AND
 ELECTRICAL EQUIPMENT REQUIRING SERVICE. NEC 110.26
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
2015-07-11 13:26:232ND REVIEW: FBC 2010
  
 UNDER REVIEW - SENT TO DAVID HAYES
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-06-04 Cont ID  
Sent By skennedy Date 2015-06-04 Time 05:49 Rev Time 0.00
Received By skennedy Date 2015-06-04 Time 05:49 Sent To  
Notes
2015-06-04 05:51:021ST REVIEW: FBC 2010
  
 FBC 107 PROVIDE ELECTRIC SERVICE RISER WITH WIRE SIZES,
 CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE LOAD
 CALCULATIONS & PANEL SCHEDULES PER THE ARCHITECTS
 DIRECTION ON MEP-2.0.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]

Review Stop HIST HISTORICAL
Rev No 4 Status P Date 2015-12-11 Cont ID  
Sent By fmittner Date 2015-12-11 Time 10:23 Rev Time 0.00
Received By fmittner Date 2015-12-11 Time 10:23 Sent To  
Notes
2015-12-11 10:30:00PLANS DO NOT ADDRESS PREVIOUS COMMENTS FOR WINDOWS TO
 MATCH ORIGINAL STYLE.
2015-12-11 10:23:59SEE NOTE FROM PREVIOUS REVIEW....WINDOWS TO MATCH
 ORIGINAL.

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2015-10-06 Cont ID  
Sent By fmittner Date 2015-10-06 Time 11:14 Rev Time 0.00
Received By fmittner Date 2015-10-06 Time 11:14 Sent To  
Notes
2015-10-06 11:17:51NEW WINDOWS TO MATCH ORIGINAL (BELIEVE 4/1) AS
 DISCUSSED WITH OWNER. QUESTIONS, CONTACT FRIEDERIKE
 MITTNER AT 822-1457.
  

Review Stop HIST HISTORICAL
Rev No 2 Status F Date 2015-07-10 Cont ID  
Sent By fmittner Date 2015-07-10 Time 15:29 Rev Time 0.00
Received By fmittner Date 2015-07-10 Time 15:29 Sent To  
Notes
2015-07-10 15:32:18DOORS TO GARAGE SHALL BE SOLID OR CARRIAGE WITH GLASS
 AT TOP (NOT FRENCH)

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2015-06-01 Cont ID  
Sent By fmittner Date 2015-06-01 Time 15:31 Rev Time 0.00
Received By fmittner Date 2015-06-01 Time 15:31 Sent To  
Notes
2015-06-01 15:32:29THE DOUBLE DOORS IN THE ACCESSORY STRUCTURE SHALL
 REMAIN IN THE EXISTING GARAGE DOOR OPENING

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-12-11 Cont ID  
Sent By lmarchan Date 2015-12-11 Time 15:16 Rev Time 0.00
Received By lmarchan Date 2015-12-02 Time 08:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-10-22 Cont ID  
Sent By albarran Date 2015-10-22 Time 19:39 Rev Time 0.00
Received By albarran Date 2015-09-22 Time 12:31 Sent To  
Notes
2015-10-22 19:40:3710/22/15 FAILED ELECTRICAL REVIEW AS NOTED. PER SAK
 PLACED ON HIS DESK.
2015-09-22 12:32:00RESUB ROUTED TO FMITTNER THROUGH SGRAHAM'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-07-14 Cont ID  
Sent By dhayes Date 2015-07-14 Time 12:51 Rev Time 0.00
Received By dhayes Date 2015-06-24 Time 19:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-06-04 Cont ID  
Sent By skennedy Date 2015-06-04 Time 06:43 Rev Time  
Received By skennedy Date 2015-05-20 Time   Sent To  
Notes
2015-05-21 16:12:43R28

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2015-07-11 Cont ID  
Sent By skennedy Date 2015-07-11 Time 13:18 Rev Time 0.00
Received By skennedy Date 2015-07-11 Time 13:18 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-06-04 Cont ID  
Sent By skennedy Date 2015-06-04 Time 05:36 Rev Time 0.00
Received By skennedy Date 2015-06-04 Time 05:36 Sent To  
Notes
2015-06-04 05:39:341ST REVIEW: FBC 2010
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE PLAN AND
 TAKE TO THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED
 WITH A COPY OF RECEIPT AS APPLICABLE.
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2015-12-09 Cont ID  
Sent By skennedy Date 2015-12-09 Time 08:14 Rev Time 0.00
Received By skennedy Date 2015-12-09 Time 08:14 Sent To  
Notes
2015-12-09 08:21:18PROVISIONALLY APPROVED PROVIDE A SIZING CALCULATION
 UNLESS HOME IS A CONTRIBUTING HISTORIC STRUCTURE.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2015-10-17 Cont ID  
Sent By skennedy Date 2015-10-17 Time 17:53 Rev Time 0.00
Received By skennedy Date 2015-10-17 Time 17:53 Sent To P
Notes
2015-10-17 17:54:523RD REVIEW: FBC 2010
  
 FBC-EC 403.2.5 PROVIDE A SIZING CALCULATION
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-07-13 Cont ID  
Sent By skennedy Date 2015-07-13 Time 09:50 Rev Time 0.00
Received By skennedy Date 2015-07-11 Time 13:26 Sent To  
Notes
2015-07-11 13:26:472ND REVIEW: FBC 2010
  
 FBC 107 _ PROVIDE AN ENERGY SUBMITTAL.
 FBC- 107.3.5.3 ? PROVIDE A MECHANICAL PLAN TO SHOW
 SUPPLY DUCTS PER FBC-R M16 & BATH EXHAUST PER FBC-R
 M15.
 PROVIDE AN EQUIPMENT SCHEDULE.
 FBC-EC 403.2.5 PROVIDE A SIZING CALCULATION
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-06-04 Cont ID  
Sent By skennedy Date 2015-06-04 Time 05:44 Rev Time 0.00
Received By skennedy Date 2015-06-04 Time 05:44 Sent To  
Notes
2015-06-04 05:49:261ST REVIEW: FBC 2010
  
 FBC 107 PROVIDE A MECHANICAL PLAN PER THE ARCHITECTS
 DIRECTION ON MEP-2.0.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2015-12-09 Cont ID  
Sent By skennedy Date 2015-12-09 Time 08:12 Rev Time 0.00
Received By skennedy Date 2015-12-09 Time 08:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2015-10-19 Cont ID  
Sent By gjohnson Date 2015-10-19 Time 09:36 Rev Time 0.00
Received By gjohnson Date 2015-10-19 Time 09:36 Sent To  
Notes
2015-10-19 09:41:56 
  
 1ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
  
  
 1. SHEET MP-2.0 RISER DIAGRAM FOR WASHING MACHINE IS
 MISSING PLEASE PROVIDE.
 PER WPB AMEND. TO FBC SEC107.3.5.3(11)
2015-10-17 18:10:19ASSIGNED TO GEORGE JOHNSON

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-07-13 Cont ID  
Sent By skennedy Date 2015-07-13 Time 10:53 Rev Time 0.00
Received By skennedy Date 2015-07-11 Time 13:26 Sent To  
Notes
2015-07-11 13:27:162ND REVIEW: FBC 2010
  
 FBC 107 PROVIDE AN ACCURATE PLUMBING RISER TO INDICATE
 THE ALTERATIONS AND ADDITIONS OF FIXTURES.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-06-04 Cont ID  
Sent By skennedy Date 2015-06-04 Time 05:51 Rev Time 0.00
Received By skennedy Date 2015-06-04 Time 05:51 Sent To  
Notes
2015-06-04 05:52:561ST REVIEW: FBC 2010
  
 FBC 107 PROVIDE A PLUMBING RISER TO INDICATE THE
 ALTERATIONS AND ADDITIONS OF FIXTURES CONSISTENT WITH
 THE ARCHITECTS PLAN ON MEP-2.0.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2015-12-09 Cont ID  
Sent By skennedy Date 2015-12-09 Time 08:15 Rev Time 0.00
Received By skennedy Date 2015-12-09 Time 08:15 Sent To  
Notes
2015-12-09 08:16:53ROOFING WORK WILL REQUIRE AN ADDITIONAL SUBMITTAL AS TO
 ANY PROPOSED NEW ROOF COVERING.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop Z ZONING
Rev No 3 Status P Date 2015-12-11 Cont ID  
Sent By fmittner Date 2015-12-11 Time 10:24 Rev Time 0.00
Received By fmittner Date 2015-12-11 Time 10:24 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2015-07-10 Cont ID  
Sent By fmittner Date 2015-07-10 Time 15:29 Rev Time 0.00
Received By fmittner Date 2015-07-10 Time 15:29 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2015-06-01 Cont ID  
Sent By fmittner Date 2015-06-01 Time 15:32 Rev Time 0.00
Received By fmittner Date 2015-06-01 Time 15:32 Sent To  
Notes
2015-06-01 15:32:56THE ACCESSORY UNIT IS NOT PERMITTED TO HAVE A KITCHEN
 FACILITY PER THE ZONING ORDINANCE NOR BE UTILIZED AS A
 SEPARATE LIVING UNIT.