Plan Review Details - Permit 15050862
Plan Review Stops For Permit 15050862
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-06-01 Cont ID  
Sent By jgomez Date 2015-06-01 Time 18:58 Rev Time 0.00
Received By jgomez Date 2015-06-01 Time 18:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-05-26 Cont ID  
Sent By jgomez Date 2015-05-26 Time 09:34 Rev Time 0.00
Received By jgomez Date 2015-05-26 Time 07:57 Sent To  
Notes
2015-05-26 09:40:50RE-ROOF AND RECOVER BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- TAS 126 MOISTURE TESTING IS MISSING THE ROOF
 MOISTURE SURVEY SHOWING LOCATION AND RESULTS OF ALL
 TESTS PERFORMED. SEC. 14 OF TAS 125-95.
  
 2- NOA 13-0219.14 SUBMITTED FOR THE ROOF SYSTEM OVER
 RECOVERY DECKS EXPIRED ON 08/31/14. NEED TO PROVIDE
 CURRENT NOA. DCA RULE 9N-3.
  
 3- ENGINEER TO REVISE ALL CALCULATIONS TO MATCH NEW
 NOA. SEC. 107.2.1 CITY AMENDMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]