Plan Review Details - Permit 15050842
Plan Review Stops For Permit 15050842
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2015-10-01 Cont ID  
Sent By skennedy Date 2015-10-01 Time 14:24 Rev Time 0.00
Received By skennedy Date 2015-10-01 Time 14:24 Sent To  
Notes
2015-10-01 14:24:5710/1/15 RECEIVED AND APPROVED LETTER PER RAB COMMENT OF
 9/28/15. SAK

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-09-28 Cont ID  
Sent By rbrown Date 2015-09-28 Time 19:42 Rev Time 0.00
Received By rbrown Date 2015-09-28 Time 19:42 Sent To  
Notes
2015-09-28 20:01:08REVIEW OF SUBMITTED ONM&J STRUCTURAL REVIEW OF GROUND
 FLOOR SLAB REINFORCEMENT CANNOT BE PASSED UNTIL THE
 FOLLOWING COMMENT IS ADDRESSED:
  
 THE USE AND PLACEMENT OF WIRE MESH REINFORCEMENT FOR
 THE SLAB INFILL IS IN CONFLICT WITH DETAIL 1 ON SHEET
 A.06 PROVIDED BY STEPHEN ROY AS THE ARCHITECT OF RECORD
 FOR THE PROJECT. PLEASE HAVE MR. ROY EITHER REVISE THAT
 DETAIL TO SHOW HIS AGREEMENT WITH THE AS-BUILT
 REINFORCEMET CONFIGURATION, OR REVIEW ONM&J STRUCTURAL
 REVIEW OF GROUND FLOOR SLAB REINFORCEMENT AND PROVIDE A
 SIGNED AND SEALED LETTER REFERRING TO THAT DOCUMENT AND
 STATING HIS ACCEPTANCE OF THE AS-BUILT CONDITION
 DESCRIBED THEREIN.
  
 ROBERT BROWN
 TELEPHONE: (561) 805 6652
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-06-24 Cont ID  
Sent By jwitmer Date 2015-06-24 Time 06:58 Rev Time 0.00
Received By jwitmer Date 2015-06-24 Time 06:15 Sent To  
Notes
2015-06-24 06:53:50NO ROOFING PERMIT NOR PRODUCT APPROVALS WERE SUBMITTED
 UNDER THE MASTER PERMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-06-08 Cont ID  
Sent By jwitmer Date 2015-06-08 Time 12:29 Rev Time  
Received By jwitmer Date 2015-06-08 Time 08:06 Sent To  
Notes
2015-06-08 09:59:17BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15050842
 ADD: 1100 W TECHNOLOGY PLACE # 104
 CONT: HEDRICK BROS.
 TEL: (561)689-8880
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JUNE 08/2015
 ACTION: DENIED
  
 1)SHEET A.01 THE PROJECT DATA INDICATES THE OCCUPANCY
 AS A F1 OCCUPANCY. WHERE THE PLANS INDICATE A MIXED USE
 OCCUPANCY BETWEEN A F-1 AND STORAGE OCCUPANCY AND
 OFFICE AS A ACCESSORY OCCUPANCY. WHERE LESS THAN 10% OF
 THE FLOOR AREA OF THE BUILDING IS USED IN A OCCUPANCY
 TYPE IT IS CONSIDERED A ACCESSORY OCCUPANCY. OVER 10 %
 OF THE BUILING FLOOR AREA IT IS CONSIDERED A MIXED USE
 BUILDING. THE QUESTION IS IF THE STORAGE OCCUPANCY IS
 TO BE CONSIDERED A S1 OR S2. THE S2 OCCUPANCY DOES
 INCLUDE FROZEN FOODS, FOOD PRODUCT AND THIS IS THE
 QUESTION, DAIRY PRODUCTS IN NONWAXED COATED PAPER
 CONTAINERS? HOW IS THE ICE CREAM PACKAGED?
  
 2) TABLE 508.4 DOES NOT REQUIRE OCCUPANCY SEPARATION
 BETWEEN THE F1 & S1 WHEREAS THE F1 & S2 DOES REQUIRE
 SEPARATION, 2 HR IF NON-SPRINKLERED & 1 HOUR FOR
 SPRINKLERED. THE OTHER OPTION IS TO REVIEW THE
 REQUIREMENTS OF NON-SEPARATED OCCUPANCIES FOUND UNDER
 FBC-B 508.3.
  
 3) THE OCCUPANCY COUNT IS TAKEN ON THE WHOLE OF THE
 FACILITY BEING F1 AND THE OCCUPANT LOAD TAKEN AT 100
 SQ. FT/ PER OCCUPANT. STORAGE STOCK AND SHIPPING ARE TO
 BE TAKEN AT 300 GROSS AND BUSINESS AT 100 GROSS. PLEASE
 REVISE THE OCCUPANCY COUNT. 2010 FBC-B TABLE 1004.1.1.
  
 4) THE COVERSHEET INDICATES THIS BUILDING NOT FIRE
 SPRINKLERED AND ADDS THE STATEMENT EXIT TRAVEL 200 FT.
 W/O FIRE SPRINKLERS. SHEET A.03 STATES THE BUILDING IS
 FIRE SPRINKLERED BUT THE TRAVEL DISTANCE IS STILL AT
 200 FT, TAKEN FOR F1 NON-FIRE SPRINKLERED? SEE FBC-B
 TABLE 1016.1.
  
 5) THE SHEET A.03 SHOWS (2) NEW COOLER AND FREEZERS
 COMBINED THEY ARE WELL OVER 400 SQ. FT. IN AREA. FBC-B
 2603.4.1.3 IN NON-SPRINKLERED BUILDINGS LIMITS THE AREA
 TO A AGGREGATE AREA OF 400 SQ. FT.
  
 6A) THE WALK IN CCOLER & FREEZERS ARE TO BE UNDER
 SEPARATE PERMIT WITH ASSOCIATED FEES. THEY WILL NEED TO
 SHOW COMPLIANCE WITH 2603.4.1.2 (1-4). THEY WILL ALSO
 NEED TO SUPPLY FRAMING SPANS FOR THE WALLS & CEILING,
 SHOW ALLOWABLE DEFLECTION LIMITS FBC-B TABLE 1604.3.
  
 6B) THE FREEZER APPEARS IT MAY BE LARGER THAN 1000 SQ,
 FT. IF SO IT WILL NEED TO COMPLY WITH 1015.5 ALSO SEE
 EXCEPTION. PLEASE ALSO NOTE THAT FOR UNSPRINKLERED
 BUILDINGS COMMON PATH OF TRAVEL IS LIMITED TO 50 FT.
 FOR F & S OCCUPANCIES. SEE FBC-B 1014.3 EXCEPTION # 7.
  
 7) SHEET M-5 SHOWS DETAILS FOR THE ROOF TOP A/H UNITS
 ON CURBS. NOTE THERE ARE NO STRUCTURAL SHEETS SHOWING
 THE NEW HOLES CUT INTO THE ROOF DECK, NOR IS THERE
 INFORMATION IF THE EXISTING FRAMING SYSTEM WILL TAKE ON
 THE ADDITIONAL POINT LOADING OR CONCENTRATED LOADS
 WITHOUT ANY REINFORCEMENT? 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED. FBC-B 1607.4. / 1607.11.1
 DISTRIBUTION OF ROOF LOADS.
  
 8A) SHEET M5 SHOWS A DETAIL OF A NEW ROOF CURB BUT
 THERE IS NO INFORMATION ON THE ATTACHMENT TO THE ROOF
 FRAMING SYSTEM PART OF COMPONENTS & CLADDING, WILL NEED
 TO SUBMIT PRODUCT APPROVAL FOR CURB. 2010 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31) (D) ROOFING PRODUCTS AND ASSEMBLIES
 (G) PRE-ENGINEERED A/C STANDS, ROOF TOP CURBS
  
 8B) THE OTHER ISSUE THIS SAME DETAIL INDICATES SEE THE
 PRODUCT APPROVALS FOR THE ATTACHMENT OF THE AIR HANDLER
 TO THE ROOFTOP CURB. THIS IS NOT PART OF A PRODUCT
 APPROVAL AND WILL NEED TO BE ENGINEERED TO THE SITE
 SPECIFIC JOBSITE CONDITIONS. SEE 2010 FBC-B 1609.8
 ROOFTOP STRUCTURES AND EQUIPMENT.
  
 8C) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 9) NO WIND DESIGN CRITERIA WAS PROVIDED TO BE ABLE TO
 CALCULATE THE PRESSURES REQUIRED FOR COMMENT # 8B.
 WIND DESIGN CRITERIA
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
  
  
 9.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 9.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 9.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 9.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 9.5) COMPONENTS & CLADDING PRESSURES POSITIVE &
 NEGATIVE TABLE 1609.2(2)
  
 10) SHEET M1.1 SHOWS A GENERATOR BUT THERE IS NO
 INFORMATION ON THE SLAB, AND ANCHORING OF THE GENERATOR
 TO RESIST THE MOMENT OF OVERTURNING.
 2010 FBC-B 1609.6.4 WIND DESIGN PROCEDURE.
  
 11) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2015-07-13 Cont ID  
Sent By skennedy Date 2015-07-13 Time 16:18 Rev Time 0.00
Received By skennedy Date 2015-07-13 Time 16:18 Sent To  
Notes
2015-07-13 16:19:21REVIEW BY MIKE ALBARRAN. SEE PROVISO.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2015-07-08 Cont ID  
Sent By albarran Date 2015-07-08 Time 15:16 Rev Time 0.00
Received By albarran Date 2015-07-08 Time 13:53 Sent To  
Notes
2015-07-08 15:21:03THIS WAS A COURTESY REVIEW PERFORMED ON 6 PDF SHEETS
 EMAIL TO ME BY SEAN KAUFFMAN OF HENDRICKS BROTHERS
 CONSTRUCTION. ALL THE SHEETS WERE MARKED AS APPROVED
 AND DATED WITH THE EXCEPTION OF ONE WHICH HAS A NOTE
 ADVISING THE CONTRACTOR OF A POSSIBILITY FOR ADDITIONAL
 EMERGENCY LIGHTING.
2015-07-08 13:55:18CONTRACTOR SENT IN VIA EMAIL, PRELIMINARY PLANS FOR
 REVIEW PRIOR TO BEING SIGNED AND SEALED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-07-06 Cont ID  
Sent By albarran Date 2015-07-06 Time 14:21 Rev Time 0.00
Received By albarran Date 2015-07-06 Time 12:48 Sent To I
Notes
2015-07-06 14:45:34THE REVISED SET OF DRAWINGS NOW HAS A ROOF PLANS WHICH
 IS LACKING THE GFCI SERVICE OUTLETS REQUIRED BY NEC
 210.63
 I TRIED TO FOLLOW YOUR THE NEW PLANS TO LOCATE THE
 NOTES IN RESPONSE TO COMMENTS 1, 3 & 5, AND WAS UNABLE
 TO FIND THEM. THESE NOTES NEED TO BE ADDED TO THE
 DRAWINGS AND CLOUDED.
 MY NOTE #8 REFERS TO SPECIFIC IDENTIFICATION OR MARKING
 REQUIREMENTS AS WELL AS SECURITY OR MECHANICAL
 PROTECTION REQUIREMENTS OF THE NFPA 72, SECTION
 10.6.5.2.
  
 PLEASE CORRECT THE PLANS ACCORDINGLY AND RESUBMIT. IF
 YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
 MIKE ALBARRAN 561-805-6746

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-06-16 Cont ID  
Sent By albarran Date 2015-06-16 Time 14:38 Rev Time 0.00
Received By albarran Date 2015-06-16 Time 11:37 Sent To I
Notes
2015-06-16 14:40:23PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE CORRECTIONS NOTED.
  
 THE FOLLOWING ITEMS SHALL BE CORRECTED AND THE PLANS
 RESUBMITTED FOR A SECOND REVIEW:
  
 1. AS PER NEC 110.16, PANELS SHALL BE MARKED WITH THE
 REQUIRED ARC-FLASH PROTECTION WARNING LABEL.
 2. AS PER NEC 210.8(B)(5), ALL 125 V, 15 ? 20 AMP
 OUTLETS WITHIN 6? OF A SINK SHALL BE GFI PROTECTED.
 3. AS PER NEC 230.8, ALL UNDERGROUND SERVICE RACEWAYS
 SHALL BE SEALED TO AVOID MOISTURE ETC. AS PER NEC
 300.5.
 4. AS PER NEC 230.95, THREE PHASE WYE SERVICES OF 1000
 AMPS OR GREATER REQUIRE GFI PROTECTION.
 5. AS PER NEC 300.7, RACEWAYS EXPOSED TO DIFFERENT
 TEMPERATURES ENVIRONMENTS SHALL BE SEALED TO AVOID THE
 TRANSFER WARM AIR INTO THE COLD SPACE,
 6. AS PER NEC 422.52, ELECTRIC WATER COOLERS SHALL BE
 GFI PROTECTED.
 7. AS PER NEC 700.12, YOU SHALL INDICATE THE CIRCUIT
 NUMBER SERVING EACH EMERGENCY LIGHT TO ASCERTAIN
 COMPLIANCE IN THAT THEY HAVE TO BE ON THE SAME LIGHTING
 CIRCUIT AS THE AREA THEY OCCUPY.
 8. AS PER NEC 760.4, THE CIRCUIT SUPPLYING THE FACP
 SHALL BE LABELED AND IDENTIFIED ACCORDINGLY.
 9. FBC-ENERGY CONSERVATION, AMONG OTHER REQUIREMENTS,
 ALL LIGHTING SHALL COMPLY WITH SECTION 505 OF THIS
 CODE.
  
 IF YOU HAVE ANY QUESTIONS, OR I CAN BE OF FURTHER
 ASSISTANCE, PLEASE DO NOT HESITATE TO CONTACT ME.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-06-26 Cont ID  
Sent By pleduc Date 2015-06-26 Time   Rev Time 0.00
Received By pleduc Date 2015-06-26 Time 09:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-05-27 Cont ID  
Sent By pleduc Date 2015-05-27 Time   Rev Time 0.00
Received By pleduc Date 2015-05-27 Time 14:59 Sent To  
Notes
2015-05-27 15:09:50THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) PROVIDE HAZARD CLASSIFICATION FOR EACH AREA PER NFPA
 101.
  
 2) PROVIDE A LIFE SAFETY PLAN. COMPLETE LIFE SAFETY
 PLANS SHALL BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS,
 TRAVEL DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END
 CORRIDORS, EXIT SIGNS, EMERGENCY LIGHTING, EXITS
 LEADING TO A PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS,
 AND ALL FIRE SAFETY FEATURES AND EQUIPMENT.
  
 3) SHEET A.01 INDICATES "NO" FRIE SPRINKLER. SHEET A.03
 INDICATES "YES" FIRE SPRINKLER. PLEASE INDICATE WHICH
 IS CORRECT. FIRE SPRINKLER AND FIRE ALARM SHALL BE DONE
 UNDER SEAPRATE SHOP DRAWINGS.
  
 4) BASED ON NO SPRINKLER PROTECTION A SECOND EXIT MAYBE
 REQUIRED IN THE FREEZER. SPRINKLER PROTECTION SHALL BE
 EXTENDED TO THE COOLER AND FREEZER.
  
 5) IT IS RECOMMENDED NOT TO LOSE ACCESS TO THE REAR
 DOORS AS THEY CAN BE USED AS ALTERNATE EXITS. CONSIDER
 CREATING HALLWAY ACCESS TO THE AT LEAST ONE REAR DOOR.
 IF A SECOND EXIT IS REQUIRED FROM THE FREEZER CREATE
 ACCESS HALLWYA TO BOTH REAR EXITS. SHOULD DOORS NOT BE
 USED, SIGNS ON EXTERIOR OF DOOR INDICATING 'NO ACCESS"
 ON EACH.
  
 6) ADD EXIT SIGN AT THE INSIDE LARGE AREA AT FRONT
 FOYER DOOR .
  
 7) ADD EXIT SIGN INSIDE THE FREEZER FOR EACH EXIT DOOR.
  
 8) ADD EMERGENCY LIGHTING INSIDE THE FEEZER.
  
 9) ADD EXIT LIGHT INSIDE THE COOLER.
  
 10) ADD EMERGENCY LIGHTING INSIDE THE COOLER.

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2015-10-13 Cont ID  
Sent By skennedy Date 2015-07-11 Time 15:40 Rev Time 0.00
Received By skennedy Date 2015-07-11 Time 15:40 Sent To  
Notes
2015-10-13 15:41:33REVIEW BY TKL, VERIFIED PLAN IS STAMPED AND REVIEWED.
 SAK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-07-10 Cont ID  
Sent By skennedy Date 2015-07-10 Time 13:53 Rev Time 0.00
Received By skennedy Date 2015-06-22 Time 11:54 Sent To  
Notes
2015-06-23 11:54:54RE-SUBMITTAL SENT TO B7 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-06-16 Cont ID  
Sent By   Date 2015-06-16 Time   Rev Time 0.00
Received By albarran Date 2015-06-16 Time 10:05 Sent To  
Notes
2015-05-21 16:20:54B22

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2015-06-08 Cont ID  
Sent By jwitmer Date 2015-06-08 Time 12:18 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-06-25 Cont ID  
Sent By ccole Date 2015-06-25 Time 10:46 Rev Time 0.00
Received By ccole Date 2015-06-24 Time 10:46 Sent To  
Notes
2015-06-25 10:50:18MECHANICAL PLANS APPROVED WITH EXCEPTION:
  
 A REVISON IS REQUIRED TO SHEET M1.1 TO MATCH THE AC
 LAYOUT PLANS WITH THE REFLECTIVE CEILING PLAN ON A0.5.
 THE CURRENT PLAN IS SHOWING DUCT DROPS AND RETURNS OVER
 THE WALK-IN COOLER. THE REVISION MUST BE REVIEWED AND
 APPROVED PRIOR TO INSPECTION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-06-08 Cont ID  
Sent By ccole Date 2015-06-08 Time 12:47 Rev Time 0.00
Received By ccole Date 2015-06-08 Time 12:47 Sent To  
Notes
2015-06-08 12:59:171ST REVIEW: FBC 2010 MECHANICAL
  
 1) SHEET M1.1: THE FLOOR PLAN LAYOUT AND ROOM
 CONFIGURATIONS ON THIS PLAN SHEET DO NOT MATCH THE
 LAYOUTS SHOWN ON THE OTHER PLAN SHEETS IN THE SET.
 PLEASE REVIEW AND REVISE.
 2) M1.1: THE LOAD ASSUMPTIONS DO NOT INDICATE ANY
 BTU/HR'S FOR THE FREEZER AND REFRIGERATOR, HOWEVER THE
 SUBMITTED SYSTEM SIZING CALCS INDICATE LOAD VALUES FOR
 EACH.
 3) M1.1: THE GENERATOR (#15 IN THE SCHEDULE) , IS
 MIS-LABELED (#14 HANDSINK). PLEASE NOTE THAT COMPLETE
 PLANS AND DETAILS SHALL BE PROVIDED FOR THE GENERATOR
 UNDER SEPARATE PERMIT.
 4) PROVIDE HOOD PLANS AND SPECIFICATIONS INCLUDING
 DIMENSIONED FRONT AND PLAN VIEW DRAWINGS, HOOD AND
 EXHAUST DUCT SIZES, DUCT RUN, TERMINATION LOCATION, AND
 EQUIPMENT SCHEDULE FOR THE EXHAUST FAN - SEE SECTION
 507 FBC-10 MECHANICAL. SUBMIT A VALID PRODUCT APPROVAL
 OR MIAMI DADE NOA FOR ROOF-MOUNTED FAN.
 5) M1,1: EQUIPMENT ID. #4 IS INDICATING A GAS STOVE,
 HOWEVER #4 IS INDICATING A KETTLE ON THE ARCHITECTURAL
 AND PLUMBING SHEETS: PLEASE CLARIFY.
 6) P.01: THE CONDENSATE FROM THE FREEZER AND COOLER
 SHALL NOT DRAIN INTO THE SANITARY SEWER- SECTION 90-126
 CITY OF WEST PALM BEACH CODE OF ORDINANCES. PLEASE
 CHOOSE ANOTHER LOCATION THAT IS IN COMPLIANCE WITH
 SECTION 307.
 7) PROVIDE COMPLETE REFRIGERATION PLANS AND
 SPECIFICATIONS FOR THE NEW COOLER AND FREEZER INCLUDING
 A) SYSTEM SIZING CALCULATIONS B) EQUIPMENT SCHEDULES-
 MAKES, MODELS, CAPACITIES OF CONDENSERS AND EVAPORATORS
 C) EQUIPMENT LOCATIONS AND INSTALLATION DETAILS D)
 PIPING RUNS AND SPECIFICATIONS, PIPE INSULATIONS ETC.
 E) WALK-IN WALLS, FLOORS, AND CEILINGS CONSTRUCTION
 DETAILS INCLUDING INSULATION THICKNESS AND TYPE.
 8) PROVIDE WIND LOAD TIE DOWN ENGINEERING FOR THE RTU'S
 AND CURBS, AND FOR THE WALK-IN BOX CONDENSERS. PLEASE
 INCLUDE TWO COPIES OF VALID FL. PRODUCT APPRIOVALS OR
 MIAMI-DADE NOA'S FOR CONDENSER STANDS AND CURBS.
 9) SUBMIT PRODUCT DATA OR CUT SHEETS FOR ALL EQUIPMENT
 SPECIFIED IN THE SCHEDULE
  
  
  
 CHRISTOPHER COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2015-07-13 Cont ID  
Sent By tklarge Date 2015-07-04 Time 15:02 Rev Time 0.00
Received By tklarge Date 2015-07-04 Time 15:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-07-04 Cont ID  
Sent By tklarge Date 2015-07-04 Time 05:34 Rev Time 0.00
Received By tklarge Date 2015-07-04 Time 03:56 Sent To  
Notes
2015-07-04 05:31:341) THE GREASE INTERCEPTOR SIZING CALCULATIONS FROM
 SCHIER SHOW THAT THREE GB-250 GREASE INTERCEPTORS ARE
 REQUIRED FOR THIS PROJECT BUT ONLY ONE IS CALLED OUT ON
 THE PLANS. THE PLANS SHALL SHOW ALL THREE INTERCEPTORS
 ON SHEETS P.01 & P.03. IF THE INTERCEPTORS WILL BE
 LOCATED IN A TRAFFIC AREA THEY SHALL BE PROTECTED WITH
 TRAFFIC LIDS.SHOW THE LOCATION OF THE INTERCEPTORS ALSO
 ON SHT. A.01. WPB AMEND. TO 2010 FBC 107.2.1. THE
 INSTALLATION SHALL COMPLY WITH THE SPECIFICATION FROM
 THE CITY WPB ENGINEERING DEPT. DRAWING # GS-7.1.
 2) THE PREVIOUS PLAN SHOWED THE WASTE FROM KITCHEN
 EQUIPMENT #1 ( BLAST MACHINE) GOING TO THE SANITARY AND
 NOW IT IS GOING TO A DRYWELL. SUBMIT MANUF.
 SPECIFICATIONS FOR THE PIECE OF EQUIPMENT AND INDICATE
 ON THE PLAN THE SPECIFIC TYPE OF WASTE THAT WILL BE
 DISCHARGE FROM THIS MACHINE. IF IT IS ANYTHING OTHER
 THAN UNCONTAMINATED CLEAR WATER WASTE IT SHALL NOT
 DISCHARGE TO THE DRYWELL. IF IT REQUIRES PRE-TREATMENT
 IT WILL HAVE TO DISCHARGE TO THE GREASE INTERCEPTOR. IF
 NOT, IT SHALL DISCHARGE TO THE SANITARY. MY PREVIOUS
 COMMENT REFERRED TO THE CONDENSATE FROM THE WALK-IN
 FREEZERS DISCHARGING TO THE SANITARY.
 3) SHT. P.03 - THE GAS PIPING DIAGRAM SHOWS THE
 TANKLESS WATER HEATER AS A RINNAI AND THE WATER PIPING
 DIAGRAM SHOWS A NORITZ AND THE SUBMITTED SPECS ARE FOR
 A NORITZ. WHICH IS IT? SUBMIT THE CORRECT SPECS FOR THE
 UNIT BEING INSTALLED.
 4) SHT. P.03 - THE VENT THAT WAS INCREASED TO 3 INCH
 SHALL BE INCREASED FOR THE ENTIRE DEVELOPED LENGTH AS
 STATED IN THE 2010 FPC SEC. 916.2. THE SANITARY RISER
 SHOWS A 2" VENT INCREASING TO 3". THIS DOES NOT MEET
 THE INTENT OF THE CODE.
  
  
  
  
  
  
  
 PLUMBING PLAN REVIEW -
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-06-06 Cont ID  
Sent By tklarge Date 2015-06-06 Time 08:19 Rev Time 0.00
Received By tklarge Date 2015-06-06 Time 07:28 Sent To  
Notes
2015-06-06 08:20:441) SUBMIT MANUFACTURER SPECIFICATIONS FOR THE EQUIPMET
 TO BE USED IN THE MANUFACTURING PROCESS.2010 FPC
 SEC.303.2, WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 2) A MINIMUM OF 2 DRINKING FOUNTAINS SHALL BE PROVIDED
 IN ACCORDANCE WITH 2010 FL. ACCESS. CODE SEC.211.2.
 3) SUBMIT MANUF. SPEC SHEETS FOR THE WATER HEATER. WPB
 AMEND. TO 2010 FBC SEC. 107.2.1.
 4) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE WATER
 HEATER PER 2010 FGC SEC. 304.1.
 5) ALL HOSE BIBBS SHALL BE SEPARATELY VALVED PER FPC
 SEC.606.2.
 6) SHT. A.03 - THE EQUIPMENT SCHEDULE NOTES ITEM #15 AS
 A GENERATOR BUT I DO NOT SEE THIS ON THE PLANS.
 CLARIFY.
 7) INDICATE THE PSI OF THE GAS SYSTEM.THE SIZING CANNOT
 BE CHECKED WITHOUT THE PSI INFORMATION.
 8) SUBMIT SIZING CALCULATIONS FOR THE GREASE
 INTERCEPTORS. THE CALCULATIONS SHALL BE REVIEWED AND
 APPROVED BY SCIER IN ACCORDANCE WITH 2010 FPC
 SEC.1003.2. CONTACT LEE SCHNEEWEISS AT 1-800-538-4792.
 9) THE BRANCHVENTING APPEARS TO BE OVER 40 FEET IN
 DEVELOPED LENGTH. THE VENT SHALL BE INCREASED ONE PIPE
 SIZE TO A MINIMUM OF 3 " PER 2010 FPC SEC.916.2 &
 916.4.1.
 10) THE PLANS SHOW CONDENSATE LINES DISCHARGING INTO
 THE SANITARY SYSTEM. CLEAR WATER WASTE SHALL NOT
 DISCHARGE TO THE SANITARY SYSTEM PER WPB CITY ORDINANCE
 SEC. 90-126 ( B) (5).
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2015-05-27 Cont ID  
Sent By ajones Date 2015-05-27 Time 11:54 Rev Time 0.00
Received By ajones Date 2015-05-27 Time 11:54 Sent To  
Notes
***NONE***