Plan Review Details - Permit 15050799
Plan Review Stops For Permit 15050799
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2015-08-13 Cont ID  
Sent By jgomez Date 2015-08-12 Time 18:20 Rev Time 0.00
Received By jgomez Date 2015-08-12 Time 18:20 Sent To  
Notes
2015-08-12 18:27:23BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC RULE 9N-3 FOR:
 A) HURRICANE STORM SHUTTERS USED ON FOR PERMIT
 #03012377 SPECIFIED ON SHEET S-1. AND REVISE SHUTTERS
 INSTALLATION SCHEDULE ACCORDING TO THAT PRODUCT
 APPROVAL. FOR EXAMPLE GLASS SEPARATION IS NOT 1".
  
 2- TYP. SECTION ON SHEET S-1:
 A) SPECIFY SIZE OF CROSS VENTILATION AS REQUIRED BY
 SEC. R806 OF 2010 FBC-RESIDENTIAL.
  
 3- NEED SINGLE HUNG ALUMINUM WINDOW (NOT VINYL) FOR
 BEDROOM #2 AS REQUIRED BY HISTORIC. PROVIDE PRODUCT
 APPROVAL.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2015-08-03 Cont ID  
Sent By jgomez Date 2015-08-03 Time 13:36 Rev Time 0.00
Received By jgomez Date 2015-08-03 Time 13:36 Sent To  
Notes
2015-08-03 13:43:54RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY BUILDING (2300 N. JOG RD.) FOR IMPACT FEES
 ASSESSMENT. BRING BACK COUNTY STAMPED PLANS AND COPY OF
 PAID RECEIPT IF FEES ARE DUE. REQUIRED BY THE COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  
 ***RESPONSE:
 RESPONSE LETTER STATES "PBC STAMPED PLANS AND COPY OF
 RECEIPT IS ATTACHED". THERE ARE NO COUNTY STAMPED PLANS
 AND NO COPY OF PAID RECEIPT SUBMITTED.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC RULE 9N-3 FOR:
 A) SINGLE HUNG WINDOWS ON THE NEW ADDITION. NOTE: THE
 ADDITION IS NEW CONSTRUCTION. EVERYTHING IN THE
 ADDITION NEEDS TO COMPLY WITH CURRENT CODE.
  
 ***RESPONSE:
 THERE IS A HAND WRITTEN NOTE ON NOA 11-1013.12
 SUBMITTED STATING THAT "PGT WINDOWS SH4000 (RENAMED
 SH200)". PROVIDE PROOF THAT WINDOW SERIES SH-4000 WERE
 RE-NAMED SH-200. NEED TO VERIFY THAT SERIES 4000 AND
 SERIES 200 WINDOWS ARE THE SAME.
  
 B) HURRICANE STORM SHUTTERS FOR NEW HORIZONTAL SLIDING
 WINDOWS AND NEW SINGLE HUNG WINDOWS. AND, PROVIDE
 COMPLETE INSTALLATION SCHEDULE. PLEASE VISIT THE CITY
 WEBSITE FOR SAMPLE OF HURRICANE SHUTTERS INSTALLATION
 SCHEDULE. PROTECTION OF OPENINGS IS REQUIRED BY SEC.
 R301.2.1.2 OF 2010 FBC-RESIDENTIAL.
  
 ***RESPONSE:
 (1) DRAWINGS SUBMITTED DON'T HAVE A FLORIDA PRODUCT
 APPROVAL COVER PAGE OR MIAMI DADE NOA NUMBER. NEED
 APPROVED PRODUCT APPROVAL OR MANUFACTURER MAY APPLY FOR
 LOCAL PRODUCT APPROVAL. LOCAL PRODUCT APPROVALS ARE
 APPROVED BY THE BUILDING OFFICIAL, ROBERT BROWN.
 COMPLETE INFORMATION WITH ORIGINAL ENGINEER'S SEAL AND
 SIGNATURES WILL NEED TO BE SUBMITTED FOR HIS REVIEW.
  
 (2) WHY DOOR #3 IS GOING TO HAVE SHUTTERS IF THE NOA
 12-0516.02 SUBMITTED IS LARGE AND SMALL MISSILE IMPACT
 RESISTANT?
  
 (3) INSTALLATION SCHEDULE ON SHEET S-1 STATES THAT
 SHUTTERS ARE GOING TO BE INSTALLED HORIZONTALLY.
 PRODUCT APPROVAL SUBMITTAL DOESN'T ALLOW HORIZONTAL
 INSTALLATION ON WOOD FRAMED BUILDINGS. SEE GENERAL NOTE
 #7 ON FIRST PAGE OF SHUTTERS DRAWINGS FOR SECTIONS THAT
 ALLOW HORIZONTAL INSTALLATION.
  
 3- SPECIFY CARBON MONOXIDE ALARMS ON PLANS AS REQUIRED
 BY SEC. R315 OF 2010 FBC-RESIDENTIAL.
  
 ***RESPONSE:
 THERE ARE NO CARBON MONOXIDE ALARMS SHOWN ON THE
 ELECTRICAL PLAN AND NEED THE CARBON MONOXIDE ALARMS FOR
 ALL BEDROOMS (FRONT AND REAR UNIT).
  
 4- SHEET A-1: SPECIFY SAFETY GLASS FOR THE ADDITION NEW
 SINGLE HUNG WINDOWS ADJACENT TO THE NEW EXTERIOR DOOR.
 SEC. R308.4(2) OF 2010 FBC-RESIDENTIAL.
  
 5- TYP. SECTION ON SHEET S-1:
 A) SPECIFY CROSS VENTILATION AS REQUIRED BY SEC. R806
 OF 2010 FBC-RESIDENTIAL.
  
 ***RESPONSE:
 ENGINEER OF RECORD RESPONSE LETTER SAID "THE CEILING IN
 THE ADDITION IS NOT FASTENED DIRECTLY TO THE RAFTERS
 AND AS SUCH THERE IS CROSS VENTILATION AND R806 CROSS
 VENTILATION IS NOT REQUIRED.". THIS IS NOT CORRECT.
 CROSS VENTILATION IS REQUIRED OR ENGINEER OF RECORD MAY
 DESIGN THE ROOF AS UNVENTED. SEE SEC. R806.4.
  
 B) COORDINATE SIZE OF BOTTOM PLATE WITH SIZE SPECIFIED
 ON THE FOUNDATION ELEVATION S1 ON SAME SHEET. SEC.
 107.2.1 CITY AMENDMENTS.
  
 ***RESPONSE:
 NOT DONE.
  
 C) CLARIFY IF THERE IS AN UNDER-FLOOR SPACE. IF SO,
 THEN PROVIDE COMPLETE INFORMATION SHOWING COMPLIANCE
 WITH SEC. R408 OF 2010 FBC-RESIDENTIAL.
  
 ***RESPONSE:
 IT'S AN UNDER-FLOOR SPACE. VENTILATION WAS SPECIFIED.
 NEED TO PROVIDE ACCESS AS REQUIRED BY SEC. R408.4
  
 D) COORDINATE ATTACHMENT OF 2X8 LEDGER TO THE EXISTING
 WALL WITH INFORMATION SHOWN ON FLOOR/WALL FRAMING PLAN.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 ***RESPONSE:
 NOT DONE.
  
 6- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN
 PROFESSIONAL FEES. SEC. 109.3 CITY AMENDMENTS. REVISE
 VALUATION AS REQUIRED.
  
 *** RESPONSE:
 NEW VALUATION IS STILL TOO LOW. OVERHEAD AND PROFIT
 STILL NEED TO BE CONSIDERED EVEN IF THE OWNER IS THE
 GC. PROVIDE A COMPLETE ITEMIZED ESTIMATE FOR ALL THE
 SCOPE OF WORK SHOWN ON PLANS. DESIGN PROFESSIONAL FEES
 ARE TOO LOW ALSO.
  
 7- PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS
 FOR THE NEW SINGLE HUNG WINDOWS ON THE NEW ADDITION.
 SEC. R301.
  
 ***RESPONSE:
 A TYPICAL WINDOW OPENING WAS PROVIDED BUT IT DOESN'T
 MATCH ACTUAL CONDITIONS. REVISED PLANS SHOW A DOOR WITH
 2 WINDOWS ASSEMBLY. PROVIDE COMPLETE FRAMING DETAILS
 FOR PROPOSED ASSEMBLY.
  
 8- NEW COMMENT: SHEET A1 DOESN'T PROVIDE ANY
 INFORMATION FOR THE NEW STEPS BY THE NEW ADDITION.
 PROVIDE COMPLETE INFORMATION SHOWING COMPLIANCE WITH
 SEC. R311.7.4
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REPLACE AND REMOVE ANY REVISED SHEET. PROVIDE
 ORIGINAL DRAWIINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-07-23 Cont ID  
Sent By jgomez Date 2015-07-23 Time 18:32 Rev Time 0.00
Received By jgomez Date 2015-07-23 Time 18:24 Sent To  
Notes
2015-07-23 18:53:287/23/15 COMMENTS TO E-MAILED SECOND REVISED PLAN:
  
 MET WITH ROBERT BROWN THESE ARE THE COMMENTS
 1) POCKET DOORS ARE NOT ACCEPTABLE. HINGED SWING DOORS
 ARE OK.
  
 2) BEDROOM #2 IS SHOWN LIKE GOING THRU THE CLOSET TO GO
 TO THE PORCH. THIS IS NOT ALLOWED. CLEARLY SHOW THE
 CLOSET DOORS AND HALLWAY FROM BEDROOM TO THE DOOR
 LEADING TO THE PORCH.
  
 3) CLEARLY IDENTIFY WHICH WINDOWS ARE GOING TO BE
 REPLACED OR REMOVED. WINDOWS ON THE EXISTING FLOOR PLAN
 AND PROPOSED FLOOR PLAN DON'T MATCH. SEE NEW LIVING
 AREA ON REAR APARTMENT AND LIVING ROOM ON MAIN HOUSE.
 IS THE FIREPLACE GOING TO BE REMOVED? SPECIFY EGRESS
 WINDOWS FOR BEDROOM #1 ON REAR APARTMENT.
  
 4) PROPOSED PORCH DOOR. SEE FRIEDERIKE'S COMMENTS. NEED
 PRODUCT APPROVAL. MAKE SURE LANDING AND STEPS COMPLY
 WITH SEC. R311.3
  
  
  
  
 ORIGINAL COMMENTS:
 RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY BUILDING (2300 N. JOG RD.) FOR IMPACT FEES
 ASSESSMENT. BRING BACK COUNTY STAMPED PLANS AND COPY OF
 PAID RECEIPT IF FEES ARE DUE. REQUIRED BY THE COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  
 2- ENGINEER OF RECORD TO REVISE ALTERATION LEVEL
 SPECIFIED ON SHEET S-1. REAR UNIT IS MORE THAN 50% WORK
 AREA AND THERE IS AN ADDITION ON THE FRONT UNIT.
 SPECIFY COMBINATION ALTERATION LEVELS AS REQUIRED BY
 SEC. 401.4 OF 2010 FBC-EXISTING BUILDING.
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC RULE 9N-3 FOR:
 A) ROOF MATERIAL TO BE INSTALLED.
  
 B) SINGLE HUNG WINDOWS ON THE NEW ADDITION. NOTE: THE
 ADDITION IS NEW CONSTRUCTION. EVERYTHING IN THE
 ADDITION NEEDS TO COMPLY WITH CURRENT CODE.
  
 C) HURRICANE STORM SHUTTERS FOR NEW HORIZONTAL SLIDING
 WINDOWS AND NEW SINGLE HUNG WINDOWS. AND, PROVIDE
 COMPLETE INSTALLATION SCHEDULE. PLEASE VISIT THE CITY
 WEBSITE FOR SAMPLE OF HURRICANE SHUTTERS INSTALLATION
 SCHEDULE. PROTECTION OF OPENINGS IS REQUIRED BY SEC.
 R301.2.1.2 OF 2010 FBC-RESIDENTIAL.
  
 D) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON ROOF
 FRAMING PLAN, WALL SECTIONS AND DETAILS. PROVIDE ONLY
 THE FLORIDA PRODUCT APPROVAL COVER PAGE AND PAGE
 SHOWING THE SPECIFIED CONNECTOR OR ENGINEER TO LIST THE
 FLORIDA PRODUCT APPROVAL NEXT TO EACH SPECIFIED
 CONNECTOR.
  
 4- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVAL AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 5- SPECIFY CARBON MONOXIDE ALARMS ON PLANS AS REQUIRED
 BY SEC. R315 OF 2010 FBC-RESIDENTIAL.
  
 6- BEDROOMS #2 AND #3 OF MAIN HOUSE DON'T COMPLY WITH
 THE EGRESS REQUIREMENTS. PROPOSED BEDROOM #3 WILL BLOCK
 THE EGRESS THAT WAS THERE FOR THESE TWO BEDROOMS. BASED
 ON CITY RECORDS, THERE IS A PORCH ON THE SOUTH SIDE OF
 THE BEDROOMS. THERE ARE DOORS LEADING TO THIS PORCH.
 CLOSING THE DOORS WILL CREATE A SAFETY HAZARD. SEC.
 601.2 OF 2010 FBC-EXISTING BUILDING.
  
 7- PROVIDE INFORMATION FOR EGRESS FOR PROPOSED BEDROOM
 #3 ON MAIN HOUSE SHOWING COMPLIANCE WITH SEC. R310 OF
 2010 FBC-RESIDENTIAL. NOTE: SEE COMMENT ABOVE REGARDING
 EGRESS FOR BEDROOM #2 AND #3.
  
 8- SIZE OF HORIZONTAL SLIDING WINDOW SHOWN ON THE PLANS
 FOR BEDROOM #2 AND #3 OF REAR UNIT IS NOT SHOWN ON THE
 PRODUCT APPROVAL SUBMITTED (NOA 12-1017.03). ARE THESE
 CUSTOM WINDOWS?. NOTE: CUSTOM WINDOWS REQUIRE BUILDING
 OFFICIAL APPROVAL. COMPLETE ENGINEERING PACKAGE WILL BE
 REQUIRED FOR REVIEW AND APPROVAL. FAC RULE 9N-3.
  
 9- SQUARE FOOTAGE FOR REAR UNIT IS INCORRECT. SEE FLOOR
 PLANS AND REVISE PROJECT DATA INFORMATION ON SHEET C-1
 AND SHEET A-1 AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 10- SHEET A-1:
 A) SPECIFY SAFETY GLASS FOR NEW SINGLE HUNG WINDOW
 ADJACENT TO THE NEW DOOR LEADING TO THE NEW BEDROOM #3.
 SEC. R308.4(2) OF 2010 FBC-RESIDENTIAL.
  
 B) SPECIFY ALL DIMENSIONS FOR NEW BEDROOM #1 ON REAR
 UNIT TO VERIFY COMPLIANCE WITH SEC. R304.3 OF 2010
 FBC-RESIDENTIAL. SPECIFY THE SHORTEST DIMENSION BETWEEN
 THE NEW CLOSET AND THE EXTERIOR WALL.
  
 11- ALL EXTERIOR ELEVATIONS ARE MISLABELED. EAST
 ELEVATION IS THE WEST ELEVATION NOT EAST. NORTH
 ELEVATION IS SOUTH ELEVATION NOT NORTH, ETC. REVISE AS
 REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 12- EXTERIOR ELEVATIONS DON'T' MATCH PLANS. SEE NUMBER
 OF WINDOWS AND TYPE OF WINDOWS SHOWN ON PLANS AND
 REVISE ELEVATIONS TO MATCH. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 13- TYP. SECTION ON SHEET S-1:
 A) SPECIFY CROSS VENTILATION AS REQUIRED BY SEC. R806
 OF 2010 FBC-RESIDENTIAL.
  
 B) ROOF PITCH SPECIFIED ON THE EXTERIOR ELEVATION
 REQUIRES DOUBLE UNDERLAYMENT. PROVIDE SPECIFICATIONS.
 SEC. R905.2.2 OF CITY AMENDMENTS.
  
 C) PROVIDE COMPLETE SPECIFICATIONS FOR WOOD FLOOR JOIST
 SHOWING COMPLIANCE WITH SEC. R317.1 OF 2010
 FBC-RESIDENTIAL.
  
 E) SPECIFY ALL ROOF JOISTS CONNECTORS. SEC. R301.
  
 F) COORDINATE SIZE OF BOTTOM PLATE WITH SIZE SPECIFIED
 ON THE FOUNDATION ELEVATION S1 ON SAME SHEET. SEC.
 107.2.1 CITY AMENDMENTS.
  
 G) CLARIFY IF THERE IS AN UNDER-FLOOR SPACE. IF SO,
 THEN PROVIDE COMPLETE INFORMATION SHOWING COMPLIANCE
 WITH SEC. R408 OF 2010 FBC-RESIDENTIAL.
  
 H) PROVIDE COMPLETE INFORMATION FOR THE ROOF SHEATHING.
 SPECIFY SHEATHING THICKNESS AND NAIL SIZE AND SPACING
 SHOWING COMPLIANCE WITH SEC. R803.2.3.1 OF 2010
 FBC-RESIDENTIAL.
  
 I) COORDINATE ATTACHMENT OF 2X8 LEDGER TO THE EXISTING
 WALL WITH INFORMATION SHOWN ON FLOOR/WALL FRAMING PLAN.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 J) COORDINATE WALL SHEATHING INFORMATION WITH
 INFORMATION SHOWN ON FOUNDATION ELEVATION S1 ON SAME
 SHEET. SEC. 107.2.1 CITY AMENDMENTS.
  
 14- FOUNDATION ELEVATION DETAIL S1 ON SHEET S-1:
 A) REVISE FOUNDATION HEIGHT ABOVE FINISHED GRADE AS
 REQUIRED BY SEC, R404.1.6 OF 2010 FBC-RESIDENTIAL.
 (NEED 6" MIN.)
  
 B) SPECIFY ALL FLOOR JOISTS CONNECTORS. SEC. R301
  
 15- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN
 PROFESSIONAL FEES. SEC. 109.3 CITY AMENDMENTS. REVISE
 VALUATION AS REQUIRED.
  
 16- PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS
 FOR THE NEW SINGLE HUNG WINDOWS ON THE NEW ADDITION.
 SEC. R301.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REPLACE AND REMOVE ANY REVISED SHEET. PROVIDE
 ORIGINAL DRAWIINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-07-22 Cont ID  
Sent By jgomez Date 2015-07-22 Time 18:40 Rev Time 0.00
Received By jgomez Date 2015-07-22 Time 17:23 Sent To  
Notes
2015-07-22 18:55:517/22/15 COMMENTS TO E-MAILED REVISED PLAN:
  
 MET WITH ROBERT BROWN AND THESE ARE THE COMMENTS:
 1) PROPOSED BEDROOM #3 WILL REDUCE THE EGRESS FROM
 BEDROOMS #1 AND #2. THE ORIGINAL DESIGN FOR THIS ROOM
 WAS A PORCH THAT ALLOWED EGRESS FROM THE BEDROOMS THRU
 THE DOUBLE FRENCH DOORS. THE PORCH NEEDS TO STAY AND
 DOOR LEADING TO THE OUTSIDE NEEDS TO STAY ALSO.
 (CITY RECORDS FLOOR PLAN FOR PERMIT #03010028 SHOWS
 WHAT LOOKS LIKE WHAT MIGHT BE THE ORIGINAL DESIGN.
 THERE IS A PORCH ON THE WEST AND SOUTH SIDE OF THE MAIN
 HOUSE, AND THERE IS A PORCH ON THE NORTH SIDE OF THE
 REAR APARTMENT).
  
 2) THE WEST AND SOUTH PORCHES OF THE MAIN HOUSE NEED TO
 BE CLEARLY IDENTIFIED ON PLANS. REVISE THE "FRONT ROOM"
 AND "EXISTING ROOM" FOR PORCH.
  
  
 ALSO, YOUR REVISE PLAN SHOWS NEW MECH. NOTES. THE
 CARBON MONOXIDE ALARMS ARE NOT PART OF THE MECHANICAL
 REVIEW. THEY ARE BUILDING REVIEW COMMENTS. (WHAT IS
 S315 ?. DO YOU MEAN R315 ?). NOTE: NEED A CARBON
 MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH ROOM
 USED FOR SLEEPING. THIS INCLUDES THE NEW BEDROOMS ON
 THE REAR APARTMENT. SHOW THE LOCATION OF THE ALARMS ON
 THE PLANS.
  
  
  
 RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY BUILDING (2300 N. JOG RD.) FOR IMPACT FEES
 ASSESSMENT. BRING BACK COUNTY STAMPED PLANS AND COPY OF
 PAID RECEIPT IF FEES ARE DUE. REQUIRED BY THE COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  
 2- ENGINEER OF RECORD TO REVISE ALTERATION LEVEL
 SPECIFIED ON SHEET S-1. REAR UNIT IS MORE THAN 50% WORK
 AREA AND THERE IS AN ADDITION ON THE FRONT UNIT.
 SPECIFY COMBINATION ALTERATION LEVELS AS REQUIRED BY
 SEC. 401.4 OF 2010 FBC-EXISTING BUILDING.
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC RULE 9N-3 FOR:
 A) ROOF MATERIAL TO BE INSTALLED.
  
 B) SINGLE HUNG WINDOWS ON THE NEW ADDITION. NOTE: THE
 ADDITION IS NEW CONSTRUCTION. EVERYTHING IN THE
 ADDITION NEEDS TO COMPLY WITH CURRENT CODE.
  
 C) HURRICANE STORM SHUTTERS FOR NEW HORIZONTAL SLIDING
 WINDOWS AND NEW SINGLE HUNG WINDOWS. AND, PROVIDE
 COMPLETE INSTALLATION SCHEDULE. PLEASE VISIT THE CITY
 WEBSITE FOR SAMPLE OF HURRICANE SHUTTERS INSTALLATION
 SCHEDULE. PROTECTION OF OPENINGS IS REQUIRED BY SEC.
 R301.2.1.2 OF 2010 FBC-RESIDENTIAL.
  
 D) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON ROOF
 FRAMING PLAN, WALL SECTIONS AND DETAILS. PROVIDE ONLY
 THE FLORIDA PRODUCT APPROVAL COVER PAGE AND PAGE
 SHOWING THE SPECIFIED CONNECTOR OR ENGINEER TO LIST THE
 FLORIDA PRODUCT APPROVAL NEXT TO EACH SPECIFIED
 CONNECTOR.
  
 4- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVAL AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 5- SPECIFY CARBON MONOXIDE ALARMS ON PLANS AS REQUIRED
 BY SEC. R315 OF 2010 FBC-RESIDENTIAL.
  
 6- BEDROOMS #2 AND #3 OF MAIN HOUSE DON'T COMPLY WITH
 THE EGRESS REQUIREMENTS. PROPOSED BEDROOM #3 WILL BLOCK
 THE EGRESS THAT WAS THERE FOR THESE TWO BEDROOMS. BASED
 ON CITY RECORDS, THERE IS A PORCH ON THE SOUTH SIDE OF
 THE BEDROOMS. THERE ARE DOORS LEADING TO THIS PORCH.
 CLOSING THE DOORS WILL CREATE A SAFETY HAZARD. SEC.
 601.2 OF 2010 FBC-EXISTING BUILDING.
  
 7- PROVIDE INFORMATION FOR EGRESS FOR PROPOSED BEDROOM
 #3 ON MAIN HOUSE SHOWING COMPLIANCE WITH SEC. R310 OF
 2010 FBC-RESIDENTIAL. NOTE: SEE COMMENT ABOVE REGARDING
 EGRESS FOR BEDROOM #2 AND #3.
  
 8- SIZE OF HORIZONTAL SLIDING WINDOW SHOWN ON THE PLANS
 FOR BEDROOM #2 AND #3 OF REAR UNIT IS NOT SHOWN ON THE
 PRODUCT APPROVAL SUBMITTED (NOA 12-1017.03). ARE THESE
 CUSTOM WINDOWS?. NOTE: CUSTOM WINDOWS REQUIRE BUILDING
 OFFICIAL APPROVAL. COMPLETE ENGINEERING PACKAGE WILL BE
 REQUIRED FOR REVIEW AND APPROVAL. FAC RULE 9N-3.
  
 9- SQUARE FOOTAGE FOR REAR UNIT IS INCORRECT. SEE FLOOR
 PLANS AND REVISE PROJECT DATA INFORMATION ON SHEET C-1
 AND SHEET A-1 AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 10- SHEET A-1:
 A) SPECIFY SAFETY GLASS FOR NEW SINGLE HUNG WINDOW
 ADJACENT TO THE NEW DOOR LEADING TO THE NEW BEDROOM #3.
 SEC. R308.4(2) OF 2010 FBC-RESIDENTIAL.
  
 B) SPECIFY ALL DIMENSIONS FOR NEW BEDROOM #1 ON REAR
 UNIT TO VERIFY COMPLIANCE WITH SEC. R304.3 OF 2010
 FBC-RESIDENTIAL. SPECIFY THE SHORTEST DIMENSION BETWEEN
 THE NEW CLOSET AND THE EXTERIOR WALL.
  
 11- ALL EXTERIOR ELEVATIONS ARE MISLABELED. EAST
 ELEVATION IS THE WEST ELEVATION NOT EAST. NORTH
 ELEVATION IS SOUTH ELEVATION NOT NORTH, ETC. REVISE AS
 REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 12- EXTERIOR ELEVATIONS DON'T' MATCH PLANS. SEE NUMBER
 OF WINDOWS AND TYPE OF WINDOWS SHOWN ON PLANS AND
 REVISE ELEVATIONS TO MATCH. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 13- TYP. SECTION ON SHEET S-1:
 A) SPECIFY CROSS VENTILATION AS REQUIRED BY SEC. R806
 OF 2010 FBC-RESIDENTIAL.
  
 B) ROOF PITCH SPECIFIED ON THE EXTERIOR ELEVATION
 REQUIRES DOUBLE UNDERLAYMENT. PROVIDE SPECIFICATIONS.
 SEC. R905.2.2 OF CITY AMENDMENTS.
  
 C) PROVIDE COMPLETE SPECIFICATIONS FOR WOOD FLOOR JOIST
 SHOWING COMPLIANCE WITH SEC. R317.1 OF 2010
 FBC-RESIDENTIAL.
  
 E) SPECIFY ALL ROOF JOISTS CONNECTORS. SEC. R301.
  
 F) COORDINATE SIZE OF BOTTOM PLATE WITH SIZE SPECIFIED
 ON THE FOUNDATION ELEVATION S1 ON SAME SHEET. SEC.
 107.2.1 CITY AMENDMENTS.
  
 G) CLARIFY IF THERE IS AN UNDER-FLOOR SPACE. IF SO,
 THEN PROVIDE COMPLETE INFORMATION SHOWING COMPLIANCE
 WITH SEC. R408 OF 2010 FBC-RESIDENTIAL.
  
 H) PROVIDE COMPLETE INFORMATION FOR THE ROOF SHEATHING.
 SPECIFY SHEATHING THICKNESS AND NAIL SIZE AND SPACING
 SHOWING COMPLIANCE WITH SEC. R803.2.3.1 OF 2010
 FBC-RESIDENTIAL.
  
 I) COORDINATE ATTACHMENT OF 2X8 LEDGER TO THE EXISTING
 WALL WITH INFORMATION SHOWN ON FLOOR/WALL FRAMING PLAN.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 J) COORDINATE WALL SHEATHING INFORMATION WITH
 INFORMATION SHOWN ON FOUNDATION ELEVATION S1 ON SAME
 SHEET. SEC. 107.2.1 CITY AMENDMENTS.
  
 14- FOUNDATION ELEVATION DETAIL S1 ON SHEET S-1:
 A) REVISE FOUNDATION HEIGHT ABOVE FINISHED GRADE AS
 REQUIRED BY SEC, R404.1.6 OF 2010 FBC-RESIDENTIAL.
 (NEED 6" MIN.)
  
 B) SPECIFY ALL FLOOR JOISTS CONNECTORS. SEC. R301
  
 15- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN
 PROFESSIONAL FEES. SEC. 109.3 CITY AMENDMENTS. REVISE
 VALUATION AS REQUIRED.
  
 16- PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS
 FOR THE NEW SINGLE HUNG WINDOWS ON THE NEW ADDITION.
 SEC. R301.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REPLACE AND REMOVE ANY REVISED SHEET. PROVIDE
 ORIGINAL DRAWIINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-07-20 Cont ID  
Sent By jgomez Date 2015-07-20 Time 17:40 Rev Time 0.00
Received By jgomez Date 2015-07-20 Time 17:39 Sent To  
Notes
2015-07-20 17:40:41RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY BUILDING (2300 N. JOG RD.) FOR IMPACT FEES
 ASSESSMENT. BRING BACK COUNTY STAMPED PLANS AND COPY OF
 PAID RECEIPT IF FEES ARE DUE. REQUIRED BY THE COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  
 2- ENGINEER OF RECORD TO REVISE ALTERATION LEVEL
 SPECIFIED ON SHEET S-1. REAR UNIT IS MORE THAN 50% WORK
 AREA AND THERE IS AN ADDITION ON THE FRONT UNIT.
 SPECIFY COMBINATION ALTERATION LEVELS AS REQUIRED BY
 SEC. 401.4 OF 2010 FBC-EXISTING BUILDING.
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC RULE 9N-3 FOR:
 A) ROOF MATERIAL TO BE INSTALLED.
  
 B) SINGLE HUNG WINDOWS ON THE NEW ADDITION. NOTE: THE
 ADDITION IS NEW CONSTRUCTION. EVERYTHING IN THE
 ADDITION NEEDS TO COMPLY WITH CURRENT CODE.
  
 C) HURRICANE STORM SHUTTERS FOR NEW HORIZONTAL SLIDING
 WINDOWS AND NEW SINGLE HUNG WINDOWS. AND, PROVIDE
 COMPLETE INSTALLATION SCHEDULE. PLEASE VISIT THE CITY
 WEBSITE FOR SAMPLE OF HURRICANE SHUTTERS INSTALLATION
 SCHEDULE. PROTECTION OF OPENINGS IS REQUIRED BY SEC.
 R301.2.1.2 OF 2010 FBC-RESIDENTIAL.
  
 D) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON ROOF
 FRAMING PLAN, WALL SECTIONS AND DETAILS. PROVIDE ONLY
 THE FLORIDA PRODUCT APPROVAL COVER PAGE AND PAGE
 SHOWING THE SPECIFIED CONNECTOR OR ENGINEER TO LIST THE
 FLORIDA PRODUCT APPROVAL NEXT TO EACH SPECIFIED
 CONNECTOR.
  
 4- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVAL AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 5- SPECIFY CARBON MONOXIDE ALARMS ON PLANS AS REQUIRED
 BY SEC. R315 OF 2010 FBC-RESIDENTIAL.
  
 6- BEDROOMS #2 AND #3 OF MAIN HOUSE DON'T COMPLY WITH
 THE EGRESS REQUIREMENTS. PROPOSED BEDROOM #3 WILL BLOCK
 THE EGRESS THAT WAS THERE FOR THESE TWO BEDROOMS. BASED
 ON CITY RECORDS, THERE IS A PORCH ON THE SOUTH SIDE OF
 THE BEDROOMS. THERE ARE DOORS LEADING TO THIS PORCH.
 CLOSING THE DOORS WILL CREATE A SAFETY HAZARD. SEC.
 601.2 OF 2010 FBC-EXISTING BUILDING.
  
 7- PROVIDE INFORMATION FOR EGRESS FOR PROPOSED BEDROOM
 #3 ON MAIN HOUSE SHOWING COMPLIANCE WITH SEC. R310 OF
 2010 FBC-RESIDENTIAL. NOTE: SEE COMMENT ABOVE REGARDING
 EGRESS FOR BEDROOM #2 AND #3.
  
 8- SIZE OF HORIZONTAL SLIDING WINDOW SHOWN ON THE PLANS
 FOR BEDROOM #2 AND #3 OF REAR UNIT IS NOT SHOWN ON THE
 PRODUCT APPROVAL SUBMITTED (NOA 12-1017.03). ARE THESE
 CUSTOM WINDOWS?. NOTE: CUSTOM WINDOWS REQUIRE BUILDING
 OFFICIAL APPROVAL. COMPLETE ENGINEERING PACKAGE WILL BE
 REQUIRED FOR REVIEW AND APPROVAL. FAC RULE 9N-3.
  
 9- SQUARE FOOTAGE FOR REAR UNIT IS INCORRECT. SEE FLOOR
 PLANS AND REVISE PROJECT DATA INFORMATION ON SHEET C-1
 AND SHEET A-1 AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 10- SHEET A-1:
 A) SPECIFY SAFETY GLASS FOR NEW SINGLE HUNG WINDOW
 ADJACENT TO THE NEW DOOR LEADING TO THE NEW BEDROOM #3.
 SEC. R308.4(2) OF 2010 FBC-RESIDENTIAL.
  
 B) SPECIFY ALL DIMENSIONS FOR NEW BEDROOM #1 ON REAR
 UNIT TO VERIFY COMPLIANCE WITH SEC. R304.3 OF 2010
 FBC-RESIDENTIAL. SPECIFY THE SHORTEST DIMENSION BETWEEN
 THE NEW CLOSET AND THE EXTERIOR WALL.
  
 11- ALL EXTERIOR ELEVATIONS ARE MISLABELED. EAST
 ELEVATION IS THE WEST ELEVATION NOT EAST. NORTH
 ELEVATION IS SOUTH ELEVATION NOT NORTH, ETC. REVISE AS
 REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 12- EXTERIOR ELEVATIONS DON'T' MATCH PLANS. SEE NUMBER
 OF WINDOWS AND TYPE OF WINDOWS SHOWN ON PLANS AND
 REVISE ELEVATIONS TO MATCH. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 13- TYP. SECTION ON SHEET S-1:
 A) SPECIFY CROSS VENTILATION AS REQUIRED BY SEC. R806
 OF 2010 FBC-RESIDENTIAL.
  
 B) ROOF PITCH SPECIFIED ON THE EXTERIOR ELEVATION
 REQUIRES DOUBLE UNDERLAYMENT. PROVIDE SPECIFICATIONS.
 SEC. R905.2.2 OF CITY AMENDMENTS.
  
 C) PROVIDE COMPLETE SPECIFICATIONS FOR WOOD FLOOR JOIST
 SHOWING COMPLIANCE WITH SEC. R317.1 OF 2010
 FBC-RESIDENTIAL.
  
 E) SPECIFY ALL ROOF JOISTS CONNECTORS. SEC. R301.
  
 F) COORDINATE SIZE OF BOTTOM PLATE WITH SIZE SPECIFIED
 ON THE FOUNDATION ELEVATION S1 ON SAME SHEET. SEC.
 107.2.1 CITY AMENDMENTS.
  
 G) CLARIFY IF THERE IS AN UNDER-FLOOR SPACE. IF SO,
 THEN PROVIDE COMPLETE INFORMATION SHOWING COMPLIANCE
 WITH SEC. R408 OF 2010 FBC-RESIDENTIAL.
  
 H) PROVIDE COMPLETE INFORMATION FOR THE ROOF SHEATHING.
 SPECIFY SHEATHING THICKNESS AND NAIL SIZE AND SPACING
 SHOWING COMPLIANCE WITH SEC. R803.2.3.1 OF 2010
 FBC-RESIDENTIAL.
  
 I) COORDINATE ATTACHMENT OF 2X8 LEDGER TO THE EXISTING
 WALL WITH INFORMATION SHOWN ON FLOOR/WALL FRAMING PLAN.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 J) COORDINATE WALL SHEATHING INFORMATION WITH
 INFORMATION SHOWN ON FOUNDATION ELEVATION S1 ON SAME
 SHEET. SEC. 107.2.1 CITY AMENDMENTS.
  
 14- FOUNDATION ELEVATION DETAIL S1 ON SHEET S-1:
 A) REVISE FOUNDATION HEIGHT ABOVE FINISHED GRADE AS
 REQUIRED BY SEC, R404.1.6 OF 2010 FBC-RESIDENTIAL.
 (NEED 6" MIN.)
  
 B) SPECIFY ALL FLOOR JOISTS CONNECTORS. SEC. R301
  
 15- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN
 PROFESSIONAL FEES. SEC. 109.3 CITY AMENDMENTS. REVISE
 VALUATION AS REQUIRED.
  
 16- PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS
 FOR THE NEW SINGLE HUNG WINDOWS ON THE NEW ADDITION.
 SEC. R301.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REPLACE AND REMOVE ANY REVISED SHEET. PROVIDE
 ORIGINAL DRAWIINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2015-08-19 Cont ID  
Sent By skennedy Date 2015-08-19 Time 16:48 Rev Time 0.00
Received By skennedy Date 2015-08-19 Time 16:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2015-08-06 Cont ID  
Sent By albarran Date 2015-08-06 Time 16:14 Rev Time 0.00
Received By albarran Date 2015-08-06 Time 15:05 Sent To  
Notes
2015-08-06 16:13:528/6/15/ COURTESY PDF REVIEW AND RESEND FOR CORRECTIONS.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-07-30 Cont ID  
Sent By albarran Date 2015-07-30 Time 11:29 Rev Time 0.00
Received By albarran Date 2015-07-30 Time 09:27 Sent To  
Notes
2015-07-30 11:30:00PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE SECOND (2ND) REVIEW OF THE
 ABOVE MENTIONED JOB. BELOW ARE THE COMMENTS WITH
 REGARDS TO THE REQUIRED CORRECTIONS. THE FOLLOWING
 ITEMS SHALL BE CORRECTED AND THE PLANS RESUBMITTED FOR
 ANOTHER REVIEW.
  
 1. THE RISER DIAGRAM MAY BE IN VIOLATION OF NEC 230.2 &
 NEC 230.40. HAD THIS BEEN THE ONLY DEFICIENCY NOTED A
 NOTE FOR THE FIELD INSPECTOR TO VERIFY COMPLIANCE WOULD
 HAVE SOLVED THE PROBLEM, BUT OTHER ITEMS ARE MISSING AS
 NOTED BELOW.
 2. RISER DIAGRAM, LOAD CALCS & PANEL SCHEDULE SHALL BE
 SITE SPECIFIC. LOAD CALCS, PANEL SCHEDULE AND RISER
 DIAGRAM AS SUBMITTED DO NOT MATCH.
 3. DEFINE ON THE ELECTRICAL PLAN THE AREA OF WORK.
 4. INDICATE ON THE ELECTRICAL PLAN WHERE IS ?MAIN HOUSE
 BEDROOM 3?, AS DESCRIBED ON THE NOTES.
 5. ALL REPLACEMENT RECEPTACLES SHALL BE INSTALLED AS
 DESCRIBED IN NEC 406.3(D)(1) THROUGH (D)(3).
 6. ALL NEW RECEPTACLES SHALL BE LISTED AS ?TAMPER
 RESISTANT? AS INDICATED IN NEC 406.11.
 7. NEC 210.52(E)(1) REQUIRES THAT THERE BE A GFI OUTLET
 IN BOTH THE FRONT AND REAR OF THE DWELLING. IF THE
 SCOPE OF WORK ENCOMPASSES ANY WORK AT ANY OF THOSE
 AREAS, THAT OUTLETS SHALL BE INSTALLED AS INSTRUCTED BY
 NEC 406.8.
 8. SMOKE DETECTOR PLACEMENT AS REFLECTED ON THE
 ELECTRICAL SHEET DOES NOT MEET THE FBC-R 314 OR 315
 REQUIREMENTS. DUE TO THIS ADDITION, SMOKE DETECTOR
 COMPLIANCE SHALL BE ADHERED TO THROUGHOUT THE WHOLE
 HOUSE. THESE DEVICES SHALL BE INTER-CONNECTED AS WELL.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-06-29 Cont ID  
Sent By albarran Date 2015-06-29 Time 17:45 Rev Time 0.00
Received By albarran Date 2015-06-29 Time 17:03 Sent To  
Notes
2015-06-29 17:53:16FIRST ELECTRICAL REVIEW WAS FAILED AS INDICATED BELOW.
 YOU NEED TO SUBMIT AN ELECTRICAL PAGE REFLECTING THE
 FOLLOWING:
 1. ELECTRICAL LOAD CALCS FOR BOTH FRONT AND REAR HOME
 2. SITE SPECIFIC RISER DIAGRAM FOR EACH UNIT.
 3. PANEL SCHEDULE FOR EACH UNIT.
 4. EXISTING ELECTRICAL OUTLETS WITHIN THE AREA OF THE
 PROPOSED WORK
 5. WHATEVER OUTLETS WILL BE ADDED AS PART OF THE NEW
 WORK
 6. LOCATION OF ANY EXISTING SMOKE DETECTOR IF ANY
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DON'T HESITATE TO
 CONTACT ME.

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2015-08-13 Cont ID  
Sent By fmittner Date 2015-08-13 Time 14:11 Rev Time 0.00
Received By fmittner Date 2015-08-13 Time 14:11 Sent To  
Notes
2015-08-13 14:11:55CONFIRMED WITH PROPERTY OWNER, WINDOW SHALL BE ALUMINUM
 NOT VINYL. QUESTIONS, CONTACT FRIEDERIKE MITTNER AT
 822-1457.
2015-08-12 18:32:17NEW DRAWINGS SUBMITTED. NEED RE-STAMPING. JG.

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2015-08-06 Cont ID  
Sent By fmittner Date 2015-08-06 Time 15:05 Rev Time 0.00
Received By fmittner Date 2015-08-06 Time 15:05 Sent To  
Notes
2015-08-03 13:45:52NEW REVISED DRAWINGS SUBMITTED. JG.

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2015-06-04 Cont ID  
Sent By fmittner Date 2015-06-04 Time 16:01 Rev Time 0.00
Received By fmittner Date 2015-06-04 Time 16:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2015-08-19 Cont ID  
Sent By skennedy Date 2015-08-19 Time 16:49 Rev Time 0.00
Received By skennedy Date 2015-08-06 Time 15:12 Sent To  
Notes
2015-08-11 15:13:59NO ROOM IN THE RESIDENTIAL BINS. PLANS ARE IN THE
 LIBRARY FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-08-10 Cont ID  
Sent By jgomez Date 2015-08-06 Time 17:33 Rev Time 0.00
Received By jgomez Date 2015-07-27 Time 14:49 Sent To  
Notes
2015-08-10 17:34:45LAST REVIEWS DONE ON 8/6/15 BY ELECTRIC AND HISTORIC.
 JG.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-07-23 Cont ID  
Sent By jgomez Date 2015-07-23 Time 18:24 Rev Time 0.00
Received By jgomez Date 2015-07-23 Time 18:31 Sent To  
Notes
2015-07-23 18:32:29GLENN MILLER E-MAILED REVISED FLOOR PLAN. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-07-22 Cont ID  
Sent By jgomez Date 2015-07-22 Time 17:24 Rev Time 0.00
Received By jgomez Date 2015-07-22 Time 17:23 Sent To  
Notes
2015-07-22 17:25:487/22/15 RECEIVED E-MAIL FROM GLEN MILLER SHOWING
 PROPOSED LAYOUT FOR BEDROOMS' EGRESS.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-07-20 Cont ID  
Sent By jgomez Date 2015-07-20 Time 17:40 Rev Time 0.00
Received By jgomez Date 2015-05-19 Time 17:43 Sent To  
Notes
2015-05-19 17:43:59SENT TO R16 SHELF FOR REVIEW. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2015-08-12 Cont ID  
Sent By jgomez Date 2015-08-12 Time 18:34 Rev Time 0.00
Received By jgomez Date 2015-08-12 Time 18:33 Sent To  
Notes
2015-08-12 18:35:01NO IMPACT FEES DUE. MU-2015-18789. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2015-08-04 Cont ID  
Sent By jgomez Date 2015-08-04 Time 07:46 Rev Time 0.00
Received By jgomez Date 2015-08-04 Time 07:46 Sent To  
Notes
2015-08-04 07:47:101-AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY BUILDING (2300 N. JOG RD.) FOR IMPACT FEES
 ASSESSMENT. BRING BACK COUNTY STAMPED PLANS AND COPY OF
 PAID RECEIPT IF FEES ARE DUE. REQUIRED BY THE COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-07-20 Cont ID  
Sent By jgomez Date 2015-07-20 Time 17:41 Rev Time 0.00
Received By jgomez Date 2015-07-20 Time 17:40 Sent To  
Notes
2015-07-20 17:44:141-AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY BUILDING (2300 N. JOG RD.) FOR IMPACT FEES
 ASSESSMENT. BRING BACK COUNTY STAMPED PLANS AND COPY OF
 PAID RECEIPT IF FEES ARE DUE. REQUIRED BY THE COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2015-08-14 Cont ID  
Sent By ccole Date 2015-08-14 Time 09:57 Rev Time 0.00
Received By ccole Date 2015-08-14 Time 09:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-07-29 Cont ID  
Sent By ccole Date 2015-07-29 Time 10:48 Rev Time 0.00
Received By ccole Date 2015-07-29 Time 10:16 Sent To  
Notes
2015-07-29 11:00:082ND REVIEW: FBC 2010 MECHANICAL
  
 1) PROVIDE A MEANS OF RETURN FROM THE NE REAR LIVING
 AREA, AND THE SW CORNER ADDITION- SECTION M1602.4
 FBC-10 RESIDENTIAL. PLEASE NOTE, DOOR UNDERCUTS DO NOT
 PROVIDE ADEQUATE RETURN AIR PER THE CODE- TRANSFER
 DUCTS OR TRANSFER GRILLS MUST ALSO BE INSTALLED
 2) PROVIDE DETAILS FOR THE NEW AC DROP IN THE ADDITION
 AT SW CORNER. INDICATE: A) DUCT TYPE AND SIZE B)
 CONNECTION POINT TO THE MAIN SYSTEM C) DIFFUSER SIZE
 AND SUPPLY CFM.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-06-22 Cont ID  
Sent By ccole Date 2015-06-22 Time 17:17 Rev Time 0.00
Received By ccole Date 2015-06-22 Time 17:17 Sent To  
Notes
2015-06-22 17:23:16 
 1ST REVIEW: FBC 2010 MECHANICAL
  
 1) ADDITIONAL DETAILS ARE REQUIRED FOR APPROVAL:
 A) PROVIDE AN AC LAYOUT PLAN: SHOW ALL NEW AND
 RELOCATED DUCTS, DIFFUSERS, RETURNS AND CONNECTION TO
 THE RELOCATED AIR HANDLER.
 B) PROVIDE A DIMENSIONED SECTION CUT OF THE NEW AIR
 HANDLER CLOSET VERIFYING COMPLIANCE WITH SECTION
 M1305.1.1 FBC-10 RESIDENTIAL: 4 INCHES CLEARANCE ALONG
 THE SIDES, BANK AND TOP WITH A TOTAL WIDTH OF THE
 ENCLOSING SPACE AT LEAST 12 INCHES WIDER THAN THE AIR
 HANDLER.
 C) INDICATE THE NEW CLOSET DOOR WILL BE A FULL LOUVERED
 TYPE FOR RETURN AIR.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 2 Status N Date 2015-08-03 Cont ID  
Sent By tklarge Date 2015-08-03 Time 05:50 Rev Time 0.00
Received By tklarge Date 2015-08-03 Time 05:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-07-21 Cont ID  
Sent By tklarge Date 2015-07-20 Time 15:01 Rev Time 0.00
Received By tklarge Date 2015-07-20 Time 15:01 Sent To  
Notes
2015-07-21 11:37:11INDICATE IF THE WATER HEATER IN THE CLOSET IS GAS OR
 ELECTRIC. A GAS WATER HEATER CANNOT BE LOCATED IN A
 SLEEPING ROOM. FBC-R, G2406.2.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2015-08-04 Cont ID  
Sent By jgomez Date 2015-08-04 Time 08:34 Rev Time 0.00
Received By jgomez Date 2015-08-04 Time 08:34 Sent To  
Notes
2015-08-04 08:36:071) SHINGLES FLORIDA PRODUCT APPROVAL FL10124-R15.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2015-07-20 Cont ID  
Sent By jgomez Date 2015-07-20 Time 17:39 Rev Time 0.00
Received By jgomez Date 2015-07-20 Time 17:39 Sent To  
Notes
2015-07-20 17:39:551- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC RULE 9N-3 FOR:
 A) ROOF MATERIAL TO BE INSTALLED.

Review Stop Z ZONING
Rev No 2 Status P Date 2015-08-06 Cont ID  
Sent By fmittner Date 2015-08-06 Time 15:05 Rev Time 0.00
Received By fmittner Date 2015-08-06 Time 15:05 Sent To  
Notes
2015-08-03 13:45:38NEW REVISED DRAWINGS SUBMITTED. JG.

Review Stop Z ZONING
Rev No 1 Status P Date 2015-06-04 Cont ID  
Sent By fmittner Date 2015-06-04 Time 16:01 Rev Time 0.00
Received By fmittner Date 2015-06-04 Time 16:01 Sent To  
Notes
***NONE***